Altivar 71: Stirrer Application Programming Manual
Altivar 71: Stirrer Application Programming Manual
Stirrer application
Programming manual
Software V2.3IE40
Concast
11/2009
AAV75143
www.schneider-electric.com
Contents
AAV75143 11/2009 3
Before you begin
Read and understand these instructions before performing any procedure on this drive.
DANGER
HAZARDOUS VOLTAGE
• Read and understand the Installation Manual before installing or operating the ATV71 drive. Installation, adjustment,
repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning
protective grounding of all equipment.
• Many parts of this variable speed drive, including the printed circuit boards, operate at the line voltage. DO NOT
TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
CAUTION
DAMAGED EQUIPMENT
Do not operate or install any drive that appears damaged.
4 AAV75143 11/2009
Documentation structure
This manual describes only specific parameters and [CONCAST] (COn-) menu .
For other functions, refer to the following Altivar 71 technical documents. They are available on the Schneider Electric website
(www.schneider-electric.com) as well as on the CD-ROM supplied with the drive.
Installation Manual
This describes how to assemble and connect the drive.
Programming manual
This describes the functions, parameters and use of the drive terminal (integrated display terminal and graphic display terminal).
The communication functions are not described in this manual, but in the manual for the bus or network used.
• The drive parameters with specific information for use via a bus or communication network.
AAV75143 11/2009 5
Steps for setting up the drive
INSTALLATION
v 1 Consult the Installation Manual
PROGRAMMING
6 AAV75143 11/2009
Setup - Preliminary recommendations
DANGER
UNINTENDED EQUIPMENT OPERATION
• Before turning on and configuring the Altivar 71, check that the PWR (POWER REMOVAL) input is deactivated (at
state 0) in order to prevent unintended operation.
• Before turning on the drive, or when exiting the configuration menus, check that the inputs assigned to the run
command are deactivated (at state 0) since they can cause the coil to start immediately.
CAUTION
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the line voltage is compatible with the supply voltage range shown
on the drive nameplate. The drive may be damaged if the line voltage is not compatible.
CAUTION
UNINTENDED EQUIPMENT OPERATION
• Avoid operating the contactor frequently (premature ageing of the filter capacitors).
• Cycle times < 60 s may result in damage to the pre-charge resistor.
AAV75143 11/2009 7
Setup - Preliminary recommendations
DANGER
UNINTENDED EQUIPMENT OPERATION
• Check that changes made to the settings during operation do not present any danger.
• We recommend stopping the drive before making any changes.
Starting
Important:
• In factory settings mode, the coil can only be supplied with power once the “forward”, “reverse” and “DC injection stop” commands
have been reset:
- On power-up or a manual fault reset or after a stop command
If they have not been reset, the drive will display "nSt" but will not start.
• If the automatic restart function has been configured ([Automatic restart] (Atr) parameter in the [1.7 FAULT MANAGEMENT] (FLt-)
menu), these commands are taken into account without a reset being necessary.
Compatibility of functions
Important:
This software version is specific. The compatibility between "common" functions of the drive and [1.14 CONCAST] (COn-) menu has not
been tested.
The user must therefore ensure that these functions can be used at the same time.
8 AAV75143 11/2009
Graphic display terminal
The graphic display terminal is a standard component on high-power drives. The graphic display terminal can be disconnected and
connected remotely (on the door of an enclosure for example) using the cables and accessories available as options (see catalog).
Description of terminal
1 Graphic display
2 Function keys
F1, F2, F3, F4,
see page 10.
7 ESC key: Aborts a value, a
3 STOP/RESET parameter or a menu to return
button to the previous selection
5 Navigation button:
• Press (ENT): - To save the current value
- To enter the selected menu or parameter
• Turn CW/ - To increment or decrement a value
CCW: - To go to the next or previous line
- To increase or decrease the reference if control via
the terminal is activated
Note: Buttons 3, 4, 5 and 6 can be used to control the drive directly, if control via the terminal is activated.
Disconnected terminal
When the terminal is disconnected, 2 LEDs become visible:
Green LED:
Red LED:
DC bus ON
Fault
HMI Modbus
AAV75143 11/2009 9
Graphic display terminal
3 1.3 SETTINGS
1.4 INPUTS / OUTPUTS CFG
1.5 COMMAND
F1 F2 F3 F4
1. Display line. Its content can be configured; the factory settings show:
• The drive state
• The active control channel:
- Term: Terminals
- HMI: Graphic display terminal
- MDB: Integrated Modbus
- CAN: Integrated CANopen
- NET: Communication card
- APP: Controller Inside card
• Frequency reference
• Current in the coil
3. Menus, submenus, parameters, values, bar charts, etc., are displayed in drop-down window format on a maximum of 5 lines.
The line or value selected by the navigation button is displayed in reverse video.
4. Section displaying the functions assigned to the F1 to F4 keys and aligned with them, for example:
• Code F1 : Displays the code of the selected parameter, i.e., the code corresponding to the 7-segment display.
• << F2 : Navigate horizontally to the left, or go to previous menu/submenu or, for a value, go to the next digit up, displayed
in reverse video.
• >> F3 : Navigate horizontally to the right or go to next menu/submenu (going to the [2 ACCESS LEVEL] menu in this
example) or, for a value, go to the next digit down, displayed in reverse video.
5. Indicates that there are no more levels below this display window.
Indicates that there are more levels below this display window.
6. Indicates that this display window does not scroll further up.
Indicates that there are more levels above this display window.
10 AAV75143 11/2009
Graphic display terminal
AAV75143 11/2009 11
Graphic display terminal
RDY Term +0.00Hz 0A When only one selection is possible, the selection made is indicated by
5 LANGUAGE Example: Only one language can be chosen.
English
Français
Deutsch
Español
Italiano
<< >> Quick
Chinese
PARAMETER SELECTION When multiple selection is possible, the selections made are indicated by
1.3 SETTINGS Example: A number of parameters can be chosen to form the [1.12 USER MENU] (UMC-).
Ramp increment
Acceleration
Deceleration
Acceleration 2
Deceleration 2
Edit
>>
9.51 s 951 s
Min = 0.01 Max = 99.99 Min = 0.01 Max = 99.99
<< >> Quick << >> Quick
The << and >> arrows (keys F2 and F3) are used to select the digit to be modified, and the navigation button is rotated to increase or
decrease this number.
12 AAV75143 11/2009
Graphic display terminal
3 seconds
5 LANGUAGE
English Automatically switches to [5 LANGUAGE]
Français
menu 3 seconds later.
Deutsch
Select the language and press ENT.
Español
Italiano
Chinese
ESC
AAV75143 11/2009 13
Graphic display terminal
ATV71HC20N4
200kW/300HP 380/480V
Config. n°1
3 seconds
10 seconds
ENT or ESC
14 AAV75143 11/2009
Graphic display terminal
AAV75143 11/2009 15
Graphic display terminal
[1 DRIVE MENU]
16 AAV75143 11/2009
Structure of parameter tables
The parameter tables in the descriptions of the various menus can be used with both the graphic display terminal and the integrated display
terminal. They, therefore, contain information for these two terminals in accordance with the description below.
Example:
7 [No] (nO)
3 USP M [+ speed assignment]
no v [No] (nO): function inactive
4 LI1 v [LI1] (LI1)
8
1. Name of menu on 4-digit 7-segment display. 5. Name of menu on graphic display terminal.
2. Submenu code on 4-digit 7-segment display. 6. Name of submenu on graphic display terminal.
3. Parameter code on 4-digit 7-segment display. 7. Name of parameter on graphic display terminal.
4. Parameter value on 4-digit 7-segment display. 8. Value of parameter on graphic display terminal.
Note :
• The text in square brackets [ ] indicates what you will see on the graphic display terminal.
• The factory settings correspond to [Macro configuration] (CFG) = [Start/Stop] (StS). This is the macro configuration set at
the factory.
AAV75143 11/2009 17
[1.4 INPUTS / OUTPUTS CFG] (I_O-)
T Maximum current.
- [LO] (LO)
W24 M [Trig level fast stop]
Level fast stop activation
LO v [LO] (LO)
HIG v [HIG] (HIG)
T
(1) This table shows the factory setting for the parameter [Max. current] (W19) according to the drive rating.
18 AAV75143 11/2009
[1.14 CONCAST] (COn-)
AAV75143 11/2009 19
[1.14 CONCAST] (COn-)
The parameters in the [1.14 CONCAST] (drC-) menu can only be modified when the drive is stopped and no run command is present, with
the following exception:
• Parameters containing the sign Tin the code column can be modified with the drive running or stopped.
• Parameters containing the sign Oin the code column are only in read access.
FrH O [Frequency ref.]: Frequency reference before ramp (signed value). 0,1 Hz
LtrA O [Current reference]: Active Ligne current reference Ltr (signed value). 0,1 A
FrO O [Freq. after ramp]: Ramp output frequency (signed value). 0,1 Hz
20 AAV75143 11/2009
[1.14 CONCAST] (COn-)
RUN Term +50.00Hz 80A RUN Term +50.00Hz 80A This screen indicates the state of the drive at the
CURRENT FAULT LIST ENT internal com. link moment the selected fault occurred.
internal com. link Drive state RDY
----- ETA status word ...
----- ETI status word ...
----- Cmd word ...
----- Motor current ...
Code Quick HELP Quick
Output frequency ...
Elapsed time ...
Line voltage ...
Motor thermal state ...
Command Channel ...
Channel ref. active ...
AAV75143 11/2009 21
[1.14 CONCAST] (COn-)
Code Name/Description
Note: The value is identical in the CiA402 profile and the I/O profile. In the I/O profile, the description of the
values is simplified and does not refer to the CiA402 (Drivecom) state chart.
bit 0:Reserved (= 0 or 1)
bit 1:Ready
= 0: Not ready, = 1: Ready
bit 2:Running
= 0: The drive will not start if a reference other than zero is applied.
= 1: Running, if a reference other than zero is applied, the drive can start.
bit 3:Fault
= 0: No fault, = 1: Fault
bit 5:Reserved (= 1)
bit 6:Reserved (= 0 or 1)
bit 7:Alarm
= 0: No alarm, = 1: Alarm
bit 8:Reserved (= 0)
22 AAV75143 11/2009
[1.14 CONCAST] (COn-)
Code Name/Description
bit 3:"Fault"
= 0: No fault, = 1: Fault
bit 8:Reserved (= 0)
bit 12:Reserved (= 0)
bit 13:Reserved (= 0)
AAV75143 11/2009 23
[1.14 CONCAST] (COn-)
- [No] (nO)
W11 M [ASM Mode]
Alternating stirring control
nO v [No] (nO)
YES v [Yes] (YES)
1 to 900 s 5s
W12 M [Cw time ASM Mode]
T ASM clockwise time
1 to 900 s 5s
W13 M [C/Ctime ASM Mode]
T ASM anti-clockwise time
- [Yes] (YES)
OPL M [Output Phase Loss]
nO v [No] (nO): Function inactive
YES v [Yes] (YES): Tripping on OPF fault with freewheel stop.
OAC v [Output cut] (OAC): No fault triggered, but management of the output voltage in order to avoid an overcurrent
when the link with the coil is re-established and catch on the fly performed (even if this function has not been
configured).
Note: [Output Phase Loss] (OPL) is forced to [Yes] (YES) if brake logic control is configured (see ATV71
programming manual).
50 to 500 V 200 V
W01 M [OutPhL Voltage]
Open circuit coil trip level.
1 to 100 ms 10 ms
Odt M [OutPhL Time]
T Output (coil) phase loss detection time
0 to 100 % 100 %
W20 M [OutputV in % InputV]
T Field weakening
(1) Range 0.01 to 99.99 s or 0.1 to 999.9 s or 1 to 6000 s according to [Ramp increment] (Inr).
24 AAV75143 11/2009
[1.14 CONCAST] (COn-)
Run commands (forward, reverse, stop, etc.) and references can be sent using the following channels:
Control Reference
• Terminals: logic inputs LI • Terminals: analog inputs AI, frequency input, encoder
• Graphic display terminal • Graphic display terminal
• Integrated Modbus • Integrated Modbus
• Integrated CANopen • Integrated CANopen
• Communication card • Communication card
• Controller Inside card • Controller Inside card
• +/- speed via the terminals
• +/- speed via the graphic display terminal
• [I/O profile] (IO): The command and the reference can come from different channels. This configuration both simplifies and extends
use via the communication interface.
Commands may be sent via the logic inputs on the terminals or via the communication bus.
When commands are sent via a bus, they are available on a word, which acts as virtual terminals containing only logic inputs.
Application functions can be assigned to the bits in this word. More than one function can be assigned to the same bit.
Note: Stop commands from the terminals remain active even if the terminals are not the active command channel.
AAV75143 11/2009 25
[1.14 CONCAST] (COn-)
0.1 to 50 Hz 5 Hz
W16 M [Coil nom. frequency]
Coil nominal frequency.
0.0 to 1600.0 Hz 0 Hz
LSP M [Min frequency]
T Coil frequency at minimum reference, can be set between 0 and [High speed] (HSP).
T Maximum current.
-3276.7 to 3276.7 Hz 0 Hz
LFr M [HMI Frequency ref.]
T Frequency reference via the graphic display terminal.
(1) If VW3A3202 extension card has been inserted, the factory setting is [AI4] (AI4).
(2) See table with factory setting for W19 page 18.
26 AAV75143 11/2009
[1.14 CONCAST] (COn-)
0 to 1000 Hz 10 Hz
W21 M [BW Current loop]
T Current loop Bandwidth.
0 to 1000 % 100 %
W22 M [Damp Current loop]
T Current loop Damping.
0 to 100 % 15 %
W23 M [Phase Comp. coeff.]
T Field weakening.
- [No] (nO)
W25 M [Freq. ramp reverse]
nO v [No] (nO)
YES v [Yes] (YES)
T With or without ramp during reverse action.
- [Yes] (YES)
W26 M [Freq ramp startstop]
nO v [No] (nO)
YES v [Yes] (YES)
T With or without ramp for start and stop.
AAV75143 11/2009 27
Communication
Logic CANopen
Code Low limit High limit Default value
address index
ACC 1 6000 50 9001 16#203C/2
Cd1 1 = (tEr): Terminals
3 = (LCC): Graphic display terminal
10 = (Mdb): Integrated Modbus
1 8423 16#2036/18
20 = (CAn): Integrated CANopen
30 = (nEt): Communication card (if inserted)
31 = (APP): Controller Inside card (if inserted)
dEC 1 6000 50 9002 16#203C/3
EtA see page 22 - 3201 16#2002/2
Fr1 1 = (AI1): Analog input
2 = (AI2): Analog input
3 = (AI3): Analog input, if VW3A3202 extension card has been inserted
4 = (AI4): Analog input, if VW3A3202 extension card has been inserted
163 = (LCC): Graphic display terminal
164 = (Mdb): Integrated Modbus 2 8413 16#2036/E
167 = (CAn): Integrated CANopen
169 = (nEt): Communication card (if inserted)
170 = (APP): Controller Inside card (if inserted)
181 = (PI): Frequency input, if VW3A3202 extension card has been inserted
182 = (PG): Encoder input, if encoder card has been inserted
FrH -16000 +16000 - 3203 16#2002/4
FrO - - 9021 16#203C/16
HSP 0 1000 50 3104 16#2001/5
LCr 0 65535 - 3204 16#2002/5
LFr -32767 +32767 0 8502 16#2037/3
Ltr 0 15000 0 8505 16#2037/6
LtrA 0 15000 - 8559 16#2037/3C
LSP 0 16000 0 3105 16#2001/6
Odt 1 100 10 7081 16#2028/52
OPL 0 = (nO): Function inactive
1 = (YES): Tripping on OPF fault with freewheel stop. 1 9611 16#2042/C
2 = (OAC): No fault triggered
PHr 0 = (AbC): Forward
0 13401 16#2068/2
1 = (ACb): Reverse
tr1 0 = (nO): Not assigned (zero torque reference).
1 = (AI1): Analog input
2 = (AI2): Analog input
3 = (AI3): Analog input, if VW3A3202 I/O card has been inserted
4 = (AI4): Analog input, if VW3A3202 I/O card has been inserted
163 = (LCC): Graphic display terminal
2 9221 16#203E/16
164 = (Mdb): Integrated Modbus
167 = (CAn): Integrated CANopen
169 = (nEt): Communication card (if inserted)
170 = (APP): Controller Inside card (if inserted)
181 = (PI): Frequency input, if VW3A3202 I/O card has been inserted
182 = (PG): Encoder input, if encoder card has been inserted
ULn 0 65535 - 3207 16#2002/8
W01 50 500 200 20501 16#20AF/2
W02 - - - 20502 16#20AF/3
W03 - - - 20503 16#20AF/4
W04 - - - 20504 16#20AF/5
W05 - - - 20505 16#20AF/6
W06 - - - 20506 16#20AF/7
28 AAV75143 11/2009
Communication
Code Low limit High limit Default value Logic address CANopen index
W07 - - - 20507 16#20AF/8
W08 - - - 20508 16#20AF/9
W09 1 500 50 20509 16#20AF/A
W10 1 500 50 20510 16#20AF/B
W11 0 = (nO)
0 20511 16#20AF/C
1 = (YES)
W12 1 900 5 20512 16#20AF/D
W13 1 900 5 20513 16#20AF/E
W14 200 480 415 20514 16#20AF/F
W15 1 15000 - 20515 16#20AF/10
W16 1 500 50 20516 16#20AF/11
W17 1 99 30 20517 16#20AF/12
W18 0 15000 0 20518 16#20AF/13
W19 According to
0 15000 20519 16#20AF/14
the range (1)
W20 0 100 100 20520 16#20AF/15
W21 0 1000 10 20521 16#20AF/16
W22 0 1000 100 20522 16#20AF/17
W23 0 100 15 20523 16#20AF/18
W24 0 = (LO)
0 20524 16#20AF/19
1 = (HIG)
W25 0 = (nO)
0 20525 16#20AF/1A
1 = (YES)
W26 0 = (nO)
1 20526 16#20AF/1B
1 = (YES)
(1) See table with factory setting for W19 page 18.
AAV75143 11/2009 29
Maintenance
Servicing
The Altivar 71 does not require any preventive maintenance. It is nevertheless advisable to perform the following regularly:
• Check the condition and tightness of the connections.
• Ensure that the temperature around the unit remains at an acceptable level and that ventilation is effective (average service life of
fans: 3 to 5 years, depending on the operating conditions).
• Remove any dust from the drive.
The first fault detected is saved and displayed, and the drive locks.
The drive switching to fault mode can be indicated remotely via a logic output or a relay, which can be configured in the [1.4 INPUTS /
OUTPUTS CFG] (I-O-) menu, see, for example, [R1 CONFIGURATION] (r1-).
30 AAV75143 11/2009
Faults - Causes - Remedies
AI2F [AI2 input] • Non-conforming signal on analog input AI2 • Check the wiring of analog input AI2 and the value of the
signal.
AnF [Load slipping] • The encoder speed feedback does not match • Check the coil, gain and stability parameters.
the reference • Add a braking resistor.
• Check the size of the coil/drive/load.
• Check the encoder’s mechanical coupling and its wiring.
bOF [DBR overload] • The braking resistor is under excessive • Check the size of the resistor and wait for it to cool down
stress • Check the [DB Resistor Power] (brP) and [DB Resistor value]
(brU) parameters.
brF [Brake feedback] • The brake feedback contact does not match • Check the feedback circuit and the brake logic control circuit
the brake logic control • Check the mechanical state of the brake
• The brake does not stop the coil quickly • Check the brake linings
enough (detected by measuring the
speed on the "Pulse input" input).
bUF [DB unit sh. Circuit] • Short-circuit output from braking unit • Check the wiring of the braking unit and the resistor.
• Braking unit not connected • Check the braking resistor
• The monitoring of this fault must be disabled by the [Brake
res. fault Mgt.] (bUb) parameter if there is no resistor or
braking unit connected to the drive.
CrF1 [Precharge] • Charging relay control fault or • Turn the drive off and then back on again
charging resistor damaged • Check the internal connections
• Inspect/repair the drive
CrF2 [Thyr. soft charge] • DC bus charging fault (thyristors)
ECF [Encoder coupling] • Break in encoder’s mechanical coupling • Check the encoder’s mechanical coupling
EEF1 [Control Eeprom] • Internal memory fault, control card • Check the environment (electromagnetic compatibility)
• Turn off, reset, return to factory settings
• Inspect/repair the drive
EEF2 [Power Eeprom] • Internal memory fault, power card
EnF [Encoder] • Encoder feedback fault • Check [Number of pulses] (PGI) and [Encoder type] (EnS).
• Check that the encoder’s mechanical and electrical
operation, its power supply and connections are all correct
• If necessary, reverse the direction of coil rotation ([Output Ph
rotation] (PHr) parameter) or the encoder signals
FCF1 [Out. contact. stuck] • The output contactor remains closed • Check the contactor and its wiring
although the opening conditions have • Check the feedback circuit
been met
AAV75143 11/2009 31
Faults - Causes - Remedies
HdF [IGBT • Short-circuit or grounding at the drive • Check the cables connecting the drive to the coil, and the
desaturation] output coil insulation.
• Perform the diagnostic tests via the [1.9 DIAGNOSTICS]
menu.
ILF [internal com. link] • Communication fault between option • Check the environment (electromagnetic compatibility)
card and drive • Check the connections
• Check that no more than 2 option cards (max. permitted)
have been installed on the drive
• Replace the option card
• Inspect/repair the drive
InF1 [Rating error] • The power card is different from the • Check the reference of the power card
card stored
InF2 [Incompatible PB] • The power card is incompatible with the control • Check the reference of the power card and its compatibility.
card
InF3 [Internal serial link] • Communication fault between the internal • Check the internal connections
cards • Inspect/repair the drive
InF4 [Internal-mftg zone] • Internal data inconsistent • Recalibrate the drive (performed by Schneider Electric
Product Support).
InF6 [Internal - fault • The option installed in the drive is not • Check the reference and compatibility of the option.
option] recognized
InF7 [Internal-hard init.] • Initialization of the drive is incomplete • Turn off and reset.
InF8 [Internal-ctrl supply] • The control power supply is incorrect • Check the control section power supply
InF9 [Internal- I measure] • The current measurements are incorrect • Replace the current sensors or the power card.
• Inspect/repair the drive
InFA [Internal-mains • The input stage is not operating • Perform the diagnostic tests via the [1.9 DIAGNOSTICS]
circuit] correctly menu.
• Inspect/repair the drive
InFb [Internal- th. • The drive temperature sensor is not • Replace the drive temperature sensor
sensor] operating correctly • Inspect/repair the drive
• The braking unit's temperature sensor • Replace the braking unit's temperature sensor
is not operating correctly. • Inspect/repair the braking unit
• The monitoring of this fault must be disabled by the [Brake
res. fault Mgt.] (bUb) parameter if there is no braking unit
connected to the drive.
InFC [Internal-time • Fault on the electronic time measurement • Inspect/repair the drive
meas.] component
InFE [internal- CPU ] • Internal microprocessor fault • Turn off and reset. Inspect/repair the drive.
OCF [Overcurrent] • Parameters in the [SETTINGS] (SEt-) • Check the parameters.
and [1.4 MOTOR CONTROL] (drC-) • Check the size of the coil/drive/load.
menus are not correct. • Check the state of the mechanism.
• Inertia or load too high
• Mechanical locking
PrF [Power removal] • Fault with the drive’s "Power removal" safety • Inspect/repair the drive
function
SCF1 [Motor short circuit] • Short-circuit or grounding at the drive • Check the cables connecting the drive to the coil, and the coil
output insulation.
SCF2 [Impedant sh. circuit] • Perform the diagnostic tests via the [1.9 DIAGNOSTICS]
menu.
SCF3 [Ground short circuit]
• Significant earth leakage current at the drive • Reduce the switching frequency.
output if several coils are connected in • Connect chokes in series with the coil.
parallel
SOF [Overspeed] • Instability or driving load too high • Check the coil, gain and stability parameters.
• Add a braking resistor.
• Check the size of the coil/drive/load.
• Check the parameters settings for the [FREQUENCY
METER] (FqF-) function, if it is configured
32 AAV75143 11/2009
Faults - Causes - Remedies
SPF [Speed fdback loss] • Encoder feedback signal missing • Check the wiring between the encoder and the drive
• Check the encoder
• Signal on "Pulse input" missing, if the • Check the wiring of the input cable and the detector used
input is used for speed measurement
tnF [Auto-tuning] • Special coil or coil whose power is not suitable • Check that the coil/drive are compatible
for the drive
• Coil not connected to the drive
• Check that the coil is present during auto-tuning
• If an output contactor is being used, close it during auto-
tuning
AAV75143 11/2009 33
Faults - Causes - Remedies
Faults that can be reset with the automatic restart function, after the cause has disappeared
These faults can also be reset by turning on and off or by means of a logic input or control bit ([Fault reset] (rSF) parameter).
APF, CnF, COF, EPF1, EPF2, FCF2, LFF2, LFF3, LFF4, ObF, OHF, OLF, OPF1, OPF2, OSF, OtF1, OtF2, OtFL, PHF, PtF1, PtF2, PtFL,
SLF1, SLF2, SLF3, SrF, SSF and tJF faults can be inhibited and cleared remotely by means of a logic input or control bit ([Fault inhibit
assign.] (InH) parameter).
APF [Application fault] • Controller Inside card fault • Please refer to the card documentation
bLF [Brake control] • Brake release current not reached • Check the drive/coil connection
• Check the coil windings
• Check the [Brake release I FW] (Ibr) and [Brake release I
Rev] (Ird) settings.
• Brake engage frequency threshold • Apply the recommended settings for [Brake engage freq]
[Brake engage freq] (bEn) only (bEn).
regulated when brake logic control is
assigned
CnF [Com. network] • Communication fault on • Check the environment (electromagnetic compatibility)
communication card • Check the wiring.
• Check the time-out
• Replace the option card
• Inspect/repair the drive
COF [CANopen com.] • Interruption in communication on the • Check the communication bus.
CANopen bus • Check the time-out
• Refer to the CANopen User's Manual
EPF1 [External flt-LI/Bit] • Fault triggered by an external device, • Check the device which caused the fault, and reset
depending on user
EPF2 [External fault • Fault triggered by a communication • Check for the cause of the fault and reset
com.] network
FCF2 [Out. contact. • The output contactor remains open • Check the contactor and its wiring
open.] although the closing conditions have • Check the feedback circuit
been met
LCF [input contactor] • The drive is not turned on even though • Check the contactor and its wiring
[Mains V. time out ] (LCt) has elapsed. • Check the time-out
• Check the line/contactor/drive connection
LFF2 [AI2 4-20mA loss] • Loss of the 4-20 mA reference on • Check the connection on the analog inputs.
[AI3 4-20mA loss] analog input AI2, AI3 or AI4
LFF3 [AI4 4-20mA loss]
LFF4
ObF [Overbraking] • Braking too sudden or driving load • Increase the deceleration time
• Install a braking resistor if necessary
• Activate the [Dec ramp adapt.] (brA) function, if it is
compatible with the application
OHF [Drive overheat] • Drive temperature too high • Check the coil load, the drive ventilation and the ambient
temperature. Wait for the drive to cool down before
restarting.
OLF [Motor overload] • Triggered by excessive coil current • Check the setting of the coil thermal protection, check the
coil load. Wait for the drive to cool down before restarting.
OPF1 [1 output phase • Loss of one phase at drive output • Check the connections from the drive to the coil
loss]
34 AAV75143 11/2009
Faults - Causes - Remedies
Faults that can be reset with the automatic restart function, after the cause has disappeared
(continued)
OPF2 [3 motor phase loss] • Coil not connected or coil power • Check the connections from the drive to the coil
too low • If an output contactor is being used, parameterize [Output
• Output contactor open Phase Loss] (OPL) = [Output cut] (OAC).
• Instantaneous instability in the coil • Test on a low power coil or without a coil:In factory settings
current mode, coil phase loss detection is active [Output Phase Loss]
(OPL) = [Yes] (YES). To check the drive in a test or
maintenance environment, without having to use a coil with
the same rating as the drive (in particular for high power
drives), deactivate coil phase loss detection [Output Phase
Loss] (OPL) = [No] (nO)
• Check and optimize the following parameters: [IR
compensation] (UFr), [Rated motor volt.] (UnS) and [Rated
mot. current] (nCr) and perform [Auto-tuning] (tUn).
OSF [Mains overvoltage] • Line voltage too high • Check the line voltage
• Disturbed mains supply
OtF1 [PTC1 overheat] • Overheating of the PTC1 probes • Check the coil load and coil size.
detected • Check the coil ventilation.
• Overheating of the PTC2 probes • Wait for the coil to cool before restarting
OtF2 [PTC2 overheat]
detected • Check the type and state of the PTC probes
SSF [Torque/current lim] • Switch to torque limitation • Check if there are any mechanical problems
• Check the parameters of [TORQUE LIMITATION]
(tLA-) and the parameters of the
[TORQUE OR I LIM. DETECT.] (tId-) fault).
tJF [IGBT overheat] • Drive overheated • Check the size of the load/coil/drive.
• Reduce the switching frequency.
• Wait for the coil to cool before restarting
AAV75143 11/2009 35
Faults - Causes - Remedies
The USF fault can be inhibited and cleared remotely by means of a logic input or control bit ([Fault inhibit assign.] (InH) parameter).
CFF [Incorrect config.] • Option card changed or removed • Check that there are no card errors.
• In the event of the option card being changed/removed
deliberately, see the remarks below
• Control card replaced by a control • Check that there are no card errors.
card configured on a drive with a • In the event of the control card being changed deliberately,
different rating see the remarks below
CFI [Invalid config.] • Invalid configuration • Check the configuration loaded previously.
The configuration loaded in the drive • Load a compatible configuration
via the bus or communication network
is inconsistent.
dLF [Dynamic load • Abnormal load variation • Check that the load is not blocked by an obstacle
fault] • Removal of a run command causes a reset
HCF [Cards pairing] • The [CARDS PAIRING] (PPI-) • In the event of a card error, reinsert the original card
function, has been configured and a • Confirm the configuration by entering the [Pairing password]
drive card has been changed (PPI) if the card was changed deliberately
PHF [Input phase loss] • Drive incorrectly supplied or a fuse • Check the power connection and the fuses.
blown
• Failure of one phase
• 3-phase ATV71 used on a single- • Use a 3-phase line supply.
phase line supply
• Unbalanced load • Disable the fault by[Input phase loss] (IPL) = [No] (nO).
This protection only operates with the
drive on load
USF [Undervoltage] • Line supply too low • Check the voltage and the parameters of [UNDERVOLTAGE
• Transient voltage dip MGT] (USb-)
36 AAV75143 11/2009
User settings tables
AAV75143 11/2009 37
Index of parameter codes
Code Page
[1.4 INPUTS / OUTPUTS CFG] (5!9!) [1.14 CONCAST] (/98!)
ACC 24
Cd1 25
dEC 24
EtA 22
Fr1 25
FrH 20
FrO 20
HSP 26
LCr 20
LFr 26
Ltr 26
LtrA 20
LSP 26
Odt 24
OPL 24
PHr 27
tr1 26
ULn 20
W01 24
W02 20
W03 20
W04 20
W05 20
W06 20
W07 20
W08 20
W09 24
W10 24
W11 24
W12 24
W13 24
W14 26
W15 26
W16 26
W17 26
W18 18 26
W19 18 26
W20 24
W21 27
W22 27
W23 27
W24 18
W25 27
W26 27
38 AAV75143 11/2009