You are on page 1of 6

Caja Arequipa Cotahuasi

HVAC Load Analysis


for

Caja Arequipa

Prepared By:

sábado, 27 de Febrero de 2021


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Caja Arequipa Cotahuasi
College Station, TX 77845 Page 2

General Project Data Input


General Project Information
Project file name: caja Arequipa.CH8
Project title: Caja Arequipa Cotahuasi
Project city, state, ZIP: LIMA
Project date: Sábado, 27 de Febrero de 2021
Weather reference city: Cotahuasi-Arequipa
Client name: Caja Arequipa
Barometric pressure: 28.214 in.Hg.
Altitude: 1617 feet
Latitude: -16 Degrees
Mean daily temperature range: 11.5 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique rooms in this project: 1

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 1.50 Watts per square foot
Equipment requirements: 2.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 275 Btuh per person
Room sensible safety factor: 5 %
Room latent safety factor: 5 %
Room heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 2
Equipment profile number: 3
People profile number: 1
Building default ceiling height: 10.00 feet
Building default wall height: 10.00 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 0 0 0 0 0 0 0 C C C C C C C C C C C C C 0 0 0 0
2 0 0 0 0 0 0 0 C C C C C C C C C C C C C 0 0 0 0
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\Users\EDINSON\Desktop\EDINSON\caja Arequipa.CH8 sábado, 27 de Febrero de 2021, 06:05 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Caja Arequipa Cotahuasi
College Station, TX 77845 Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
January 80 76 50% 77 61.02 -10
February 78 76 50% 77 68.92 -12
March 79 75 50% 77 61.37 -11
April 77 73 50% 77 51.36 -13
May 74 70 50% 77 36.67 -16
June 74 68 50% 77 28.24 -16
July 76 68 50% 72 32.37 -9
August 76 68 50% 72 32.69 -8
September 78 68 50% 72 29.88 -7
October 79 66 50% 72 17.85 -6
November 80 68 50% 72 29.14 -5
December 80 72 50% 72 52.05 -5
Winter 58 77

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 6 0.350 No No

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 A 0.300 D

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.300 10 0
2 0.250 5 0

C:\Users\EDINSON\Desktop\EDINSON\caja Arequipa.CH8 sábado, 27 de Febrero de 2021, 06:05 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Caja Arequipa Cotahuasi
College Station, TX 77845 Page 4

Building Summary Loads


Building peaks in July at 7pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 80 0 0.00 0 537 537 2.83
Wall 200 0 0.00 0 1,307 1,307 6.88
Glass 0 0 0.00 0 0 0 0.00
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 1,844 1,844 9.71
Lighting 600 0 0.00 0 2,150 2,150 11.32
Equipment 3,000 0 0.00 0 10,748 10,748 56.60
Pool Latent 0 0 0.00 0 0 0 0.00
People 4 0 0.00 1,155 1,050 2,205 11.61
Partition 640 0 0.00 0 1,943 1,943 10.23
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 5 0 0.00 102 0 102 0.54
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 0 0 0.00
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 1,257 17,734 18,991 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 102 0 102 0.54
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Room Loads 0 0.00 1,155 17,734 18,889 99.46
Plenum Loads 0 0.00 0 0 0 0.00
Fan/Duct/Misc Loads 0 0.00 0 0 0 0.00
Building Totals 0 0.00 1,257 17,734 18,991 100.00

Check Figures
Total Building Supply Air (based on a 17° TD): 1,006 CFM
Total Building Vent. Air (0.45% of Supply): 5 CFM
Total Conditioned Air Space: 400 Sq.ft
Supply Air Per Unit Area: 2.5144 CFM/Sq.ft
Area Per Cooling Capacity: 252.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0040 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 1.58 Tons

C:\Users\EDINSON\Desktop\EDINSON\caja Arequipa.CH8 sábado, 27 de Febrero de 2021, 06:05 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Caja Arequipa Cotahuasi
College Station, TX 77845 Page 5

Air Handler #1 - Mini split - Summary Loads


Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
1 Cuarto Ti 400 0 17,734 1,155 None Direct
7pm July 4 0 1,006 0 0 5
4,000 0.00 2.51 0 0 5
Runout duct size: 16 in. dia, Diffusers: 1, CFM/runout: 1,006, Velocity: 720.3 ft/min, Pressure drop: 0.061 in.wg./100ft
Room Peak Totals: 400 0 17,734 1,155
Total Rooms: 1 4 0 1,006 0 0 5
Unique Rooms: 1 4,000 0.00 2.51 0 0 5
Main trunk duct size: 16 in. dia, Velocity: 720.3 ft/min, Pressure drop: 0.061 in.wg./100ft

C:\Users\EDINSON\Desktop\EDINSON\caja Arequipa.CH8 sábado, 27 de Febrero de 2021, 06:05 p. m.


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Elite Software Development Caja Arequipa Cotahuasi
College Station, TX 77845 Page 6

Air Handler #1 - Mini split - Total Load Summary


Air Handler Description: Mini split Constant Volume - Proportion
Sensible Heat Ratio: 0.94 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 7pm in July.
Outdoor Conditions: Clg: 72° DB, 67° WB, 96.35 grains
Indoor Conditions: Clg: 72° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Room Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.943 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Room space sensible gain: 17,734 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 0 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 17,734 Btuh
Cooling Supply Air: 17,734 / (.943 X 1.1 X 17) = 1,006 CFM
Summer Vent Outside Air (0.4% of supply) = 5 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 0 Btuh 5 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 0 Btuh
Total sensible gain on air handling system: 17,734 Btuh
Room space latent gain: 1,155 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 102 Btuh
Total latent gain on air handling system: 1,257 Btuh
Total system sensible and latent gain: 18,991 Btuh

Check Figures
Total Air Handler Supply Air (based on a 17° TD): 1,006 CFM
Total Air Handler Vent. Air (0.45% of Supply): 5 CFM
Total Conditioned Air Space: 400 Sq.ft
Supply Air Per Unit Area: 2.5144 CFM/Sq.ft
Area Per Cooling Capacity: 252.7 Sq.ft/Ton
Cooling Capacity Per Area: 0.0040 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 1.58 Tons

C:\Users\EDINSON\Desktop\EDINSON\caja Arequipa.CH8 sábado, 27 de Febrero de 2021, 06:05 p. m.