MM295-NAP&NMCP

FIRE PROTECTION SYSTEM OF EQUIPMENT SCHEDULE

ITEM ELECTRIC DATA (EACH) POWER CONTROL CONTROL FUNCTION


SYMBOL QTY DESCRIPTION LOCATION FLOW RATE HEAD
No. APPROX.kW RPM Ø/Hz./V PANEL AND CONTROL DEVICES
Private Hydrant System
1 FP - 01 1 ELECTRIC MOTOR DRIVEN PUMP FOR PRIVATE HYDRANT FIRE PUMP ROOM 205 cu.m/hr 40 M 40 3000 3/50/400 EFP-MCC-G-01 (1) FIRE PUMP AND FIRE PUMP CONTROLLERS SHALL BE
( 1-DUTY) PSB LISTED AND/OR UL LISTED AND/OR FM.APPROVED.

(2) JOCKEY PUMPS CONTROLLERS SHALL BE PSB LISTED


2 FP - 02 1 DIESEL ENGINE DRIVEN PUMP FOR PRIVATE HYDRANT FIRE PUMP ROOM 205 cu.m/hr 40 M EFP-MCC-G-01 AND/OR UL LISTED AND/OR FM.APPROVED.
( 1-STAND BY)

3 JP - 01 1 JOCKEY PUMP FOR SPRINKLER FIRE PUMP ROOM 4.5 cu.m/hr 50 M 2.2 3000 3/50/400 EFP-MCC-G-01
( 1-DUTY)

HOSEREEL SYSTEM
1 HRP-01,02 2 FIRE PUMP FOR HOSEREEL FIRE PUMP ROOM 3 cu.m/hr 30 M 1.5 3000 3/50/400 EFP-MCC-G-01 (1) FIRE PUMP AND FIRE PUMP CONTROLLERS SHALL BE
( 1-DUTY,1-STANDBY) PSB LISTED AND/OR UL LISTED AND/OR FM.APPROVED.
PRESSURE VESSEL = 250 LITERS