Generator Set Data Sheet: Fuel Consumption
Generator Set Data Sheet: Fuel Consumption
Frequency: 50
Fuel Type: Diesel
Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 3325 (2660) 3000 (2400)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
gph 41.5 70.8 108.1 141.5 39.8 70.3 100.4 130.1
L/hr 189 322 492 644 181 320 457 592
Fuel flow
Maximum fuel flow, L/hr 2225
Maximum fuel inlet restriction, mm Hg 17
Maximum fuel inlet temperature (°C) 70
Air
3
Combustion air, m /min 223.00 211.00
Maximum air cleaner restriction, kPa 6.2
©2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and
Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power
Generation. Other company, product, or service names may be trademarks or service marks of others.
Exhaust Standby rating Prime rating
3
Exhaust gas flow at set rated load, m /min 522 487
°
Exhaust gas temperature, C 451 434
Maximum exhaust back pressure, kPa 6.7
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
©2007 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and
Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power
Generation. Other company, product, or service names may be trademarks or service marks of others.
Alternator data
Feature code Connection1 Temp rise degrees C Duty2 Alternator Voltage
B360 Wye, 3 Phase 125/105C S/P RTF 380-440V
B476 Wye, 3 Phase 120/105C S/P RTF 11000V
B579 Wye, 3 Phase 125/105C P/C RTF 1905/3300V
Ratings definitions
Emergency Standby Power (ESP) Limited-Time running Power Prime Power (PRP): Base Load (Continuous) Power
Applicable for supplying power to Applicable for supplying power to a Applicable for supplying power to Applicable for supplying power
varying electrical load for the constant electrical load for limited varying electrical load for unlimited continuously to a constant electrical
duration of power interruption of a hours. Limited Time Running hours. Prime Power (PRP) is in load for unlimited hours.
reliable utility source. Emergency Power (LTP) is in accordance with accordance with ISO 8528. Ten Continuous Power (COP) in
Standby Power (ESP) is in ISO 8528. percent overload capability is accordance with ISO 8528, ISO
accordance with ISO 8528. Fuel available in accordance with ISO 3046, AS 2789, DIN 6271 and BS
Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.
3046, AS 2789, DIN 6271 and BS 5514.
5514.