Unit Specification

MCV116C3201
Pressure Control Pilot Valve (PCP)
Intrinsically Safe
3500 Annapolis Lane North, Minneapolis, MN 55447
Telephone: (763) 509-2084 Telefax: (763) 559-0108 ISSUE: 1 DATE: July 1998

GENERAL DESCRIPTION
This Pressure Control Pilot (PCP) is an intrinsically safe, torque motor-actuated, double-nozzle flapper valve that produces
a differential output pressure proportional to the applied electrical input signal. It is a single-stage, stand-alone, closed-loop
pressure control valve which uses internal hydraulic pressure reactions to achieve its closed-loop control characteristics. The
PCP contains an arc suppression circuit for use in hazardous areas.

The term "intrinsically safe" refers to a design technique based on limiting energy, electrical and thermal, to a level below that
required to ignite a specific hazardous atmospheric mixture. This device is Factory Mutual certified for use in Class I, II, or III,
Division 1, Group C, D, F, and G hazardous locations as defined by the National Electrical Code, NFPA-70 when used with
approved barriers.

DIMENSIONS
MANUAL OPERATOR

NULL ADJUST
MS CONNECTOR ACCESS SCREW

CAUTION
DO NOT REMOVE The cover is filled with 45 cc of 4000 cs
78,7 COVER SCREWS (4)
(3.10) silicone oil. Ensure that minimal oil is lost
when screw is removed.

56,1
(2.21) 17,5 DIA (2) INTRINSICALLY SAFE DEVICE
(0.69) ENCLOSURE GROUNDING TERMINAL

12,7
(0.50)
ELECTRICAL OUTPUT PORT - C1 4,8 (0.19) DIA
12,8 (0.50) O.D. X 1,78 (0.07) O-RING
REPLACEMENT FILTER
CONNECTION PART NUMBER K08573 PRESSURE PORT THRU FILTER 5,6 (0.22) DIA
12,8 (0.50) O.D. X 1,78 (0.07) O-RING
5,5 (0.217) DIA (4)
RETURN PORT 4,8 (0.19) DIA
12,8 (0.50) O.D. X 1,78 (0.07) O-RING

OUTPUT PORT - C2 4,8 (0.19) DIA


D A 50,8 12,8 (0.50) O.D. X 1,78 (0.07) O-RING
Active Pins (2.00) 34,9
C B A, B,C,D MAX (1.375)
38,1 19,0
(1.50) (0.75)
2028

Pin Orientation of 4-pin,


90° MS Mating Connector. 6,3 2,5 (0.10) (2)
38,1
(1.50)
(0.25)
Part No. MS3108E-14S-S 3,0 (0.12) 70,1 (2.76)

(Sauer-Danfoss Kit 9,5 (0.38) 76,2 (3.00)


95,2 (3.75)
No. K08106).
2023
Dimensions of the MCV116C3201 in Millimeters (Inches).

ELECTRICAL CHARACTERISTICS
A C
• Dual coil • Current/voltage range: up to 170 mA at 4.50 Vdc (linear
20Ω 16Ω range) Maximum 325 mA at 7.5 Vdc
B D
• Pulse Width Modulation (PWM)
• Phasing: The PCP is designed to be controlled from a dc current
Positive voltage to pin A produces a pressure rise at source or voltage source. If a PWM signal is used, do not
output port C1 use a pulse current of more than 120% of that required.
Positive voltage to pin B produces a pressure rise at
output port C2 • Scale factor: 0.78 ± 0.08 psid / mA

K20494 UNIT SPEC © Copyright 2001, Sauer-Danfoss (US) Company.


1 OF 2 All rights reserved. Contents subject to change.
HYDRAULIC CHARACTERISTICS
• Maximum supply pressure: 1000 psid • Hydraulic Null Adjustment: The PCP null adjustment is
Recommended range: 300 - 500 psid sometimes required when configured with the servovalve
(KVF) or applied as a stand-alone. If the PCP null takes
• Maximum return pressure: 200 psid an offset of <15 psid (>15 psid, consult factory) across
C1 and C2 ports it can usually be reestablished to the
• Maximum internal leakage: 0.65 gpm original factory setting. To adjust, remove the null access
screw (see Dimensions) and with a 3/32 inch hex head
• Maximum linear psid output pressure: 200 psid at 300 Allen wrench locate the adjusting screw just inside the
psid supply cover. Turn screw in very small increments until the
servovalve neutral is established or C1 and C2 psid is as
• Load flow: the output differential flow across a 100 psid close to 0 as possible. When finished, replace access
load pressure drop at maximum current: > 30 cim screw. If the PCP is configured with an Electrical
Displacement Control (EDC) mounted to a pump, never
• Hydraulic Fluid: Petroleum based, other fluids may be adjust an EDC neutral using the PCP null adjustment.
used provided that they are compatibile with viton and EDCs are adjusted at their second stage.
fluorosilicone seals, fluid cleanliness is ISO 4406 code
18/15 or better

WIRING
A suppression circuit is incorporated in the PCP torque motor through use of a purge enclosure or mounted in a safe area.
cover but by itself does not insure intrinsic safety. An additional See Dimensions for PCP enclosure grounding. Proper
suppression circuit (Zener barrier) must be connected in connection and suggested barrier model numbers are shown
series with the valve coils. The Zener barrier and electrical in the connection diagram below . Two per application may
controller must be isolated from the hazardous area either be required.
BIDIRECTIONAL TWO STATION CONTROL, SELECT ONE OF THE FOLLOWING BARRIERS
• Stahl Barrier 9001/02-172-270-10 (12V)
Groups A, B, C, D, F and G (maximum voltage ±17.2V)
• Stahl Barrier 9001/02-308-230-10 (26V)
Groups D, E, F and G (maximum voltage ±31.8V)

A 3 (±)1
CONTROLLER
MCV BARRIER OUTPUT
B 4 2

EARTH
GROUND
D 3 (±)1
CONTROLLER
MCV BARRIER
OUTPUT
C 4 2
HAZARDOUS LOCATION EARTH
CLASS I, II, AND III GROUND
DIVISION 1
GROUPS C OR D, F AND G NON-HAZARDOUS LOCATION

BIDIRECTIONAL CONTROL, SELECT ONE OF THE FOLLOWING BARRIERS


• Stahl Barrier 9001/01-158-270-10 (12V)
Groups A, B, C, D, F and G (maximum voltage 15.8V)
• Stahl Barrier 9001/01-280-280-10 (26V)
Groups D, E, F and G (maximum voltage 31.5V)

A 3 (+)1
CONTROLLER
MCV BARRIER OUTPUT
B 4 2

EARTH
GROUND
D 3 (+)1
CONTROLLER
MCV BARRIER
OUTPUT
C 4 2
HAZARDOUS LOCATION EARTH
CLASS I, II, AND III GROUND
DIVISION 1
GROUPS C OR D, F AND G NON-HAZARDOUS LOCATION
1739

NO CHANGES TO THIS DRAWING WITHOUT PRIOR WRITTEN AUTHORIZATION FROM FACTORY MUTUAL.

K20494 UNIT SPEC


2 OF 2