SS & IEC Requirement for MCB & RCCB
MCB
Since the withdrawal of SS 359 on 30th Jan
2004, International Standard IEC 60898 was
adopted for MCB.
Scope :
AC air-break circuit-breakers
50Hz or 60Hz
Un < 440V
In < 125A
Icn < 25kA
IEC 60898 Termal Release Trip time Electromagnetic Release Trip time
Type Non-trip Trip Hour Hold Trip sec
B 1.13 In >1 3 In > 0.1
1.45 In <1 5 In < 0.1
C 1.13 In >1 5 In > 0.1
1.45 In <1 10 In < 0.1
D 1.13 In >1 10 In > 0.1
1.45 In <1 20 In < 0.1
SS & IEC Requirement for MCB & RCCB
MCB Tripping Characteristics
Miniature Circuit Breakers
Tripping of an MCB
0.5 ms
Miniature Circuit Breakers
Tripping of an MCB
1 ms after short-circuit
current is released
1 ms
Miniature Circuit Breakers
Tripping of an MCB
1.5 ms
Miniature Circuit Breakers
Tripping of an MCB
2 ms after short-circuit
current is released
2 ms
Miniature Circuit Breakers
Tripping of an MCB
2.5 ms
Miniature Circuit Breakers
Tripping of an MCB
3 ms after short-circuit
current is released
3 ms
SS & IEC Requirement for MCB & RCCB
Maximum disconnection times: TN-S System
3ms
SS & IEC Requirement for MCB & RCCB
RCCB
SS97 is a modified adoption of International
Standard IEC 61008-1
Scope :
Functionally Dependent of or Independent on
line voltage
Un < 440V
In < 125A