Professional Documents
Culture Documents
Pile Capacity Calc
Pile Capacity Calc
Janbu Vesic
The American Petroleum Institute [API (1984)] has formulated recommendations for pile
design in the form of design parameters for piles in sands, silts, sand silts, and gravels based
on a soil description ranging from very loose to very dense. This publication suggests using
Nq ranging from a low of 8 for very loose sand to 50 for a dense gravel or very dense sand.
The table is footnoted that the values are intended as guidelines only. These values seem
rather low compared to recommendations by most authorities, particularly when considering
that piles driven into loose sand will densify it a modest amount in almost all circumstances.
A study of a number of pile load tests by Endley et al. (1979) indicated the 1979 API
[reissued as API (1984)] recommendations for Nq were about 50 percent too low. Be aware
that recommended values are not requirements; however, if they are not followed, one must
be prepared to justify the use of any alternative values.
According to Shioi and Fukui (1982) pile tip resistance is computed in Japan as
^pu = quitAp (16-9)
with the ultimate tip bearing pressure qu\t computed from the SPT based on the embedment
depth ratio Lb/D into the point-bearing stratum as follows:
Example 16-1. The point of a pile of L = 25 m is founded into a dense medium-coarse sand
deposit, which has an average N-JQ = 30 in the zone of influence of about 1.5 m above the tip to 3
m below. The pile is an HP 360 X 174 with d X b = 361 X 378 mm. The GWT is 5 m below the
ground surface.
Required. Estimate the point capacity Pu using the several methods presented in this section.
the most likely explanation of why the computed agreement with load tests on short piles is
better than on long piles.
It is usually easier to back-compute a load test with considerable confidence of what the
parameter(s) should be than to make a capacity forecast with little more than SPT numbers
and possibly unconfined compression strength data from disturbed samples recovered in the
SPT sampling procedure.
According to Vesic (1975a) Eq. (16-16) may be a lower limit, and most load tests tend to
produce average values at least 50 percent greater.
For SPT data, Meyerhof (1956, 1976) suggested obtaining fs as
fs = XmN55 (kPa) (16-17)
where A ^ = average blow count in the material indicated for the pile or pile segment
length
For cone penetration data, Meyerhof (1956) and Thorburn and Mac Vicar (1971) suggest
fs = 0.005^ c (kPa) (16-18)
where qc = cone penetration resistance, kPa.
When a cone penetrometer is used and side friction qs is measured, use
fs = qs (small-volume displacement piles)
fs = (1.5 to 2.0)qs (large-volume piles)