Professional Documents
Culture Documents
ELC-SC-2447-I - Powr Cable
ELC-SC-2447-I - Powr Cable
CONTENTS
1.0 SCOPE
1. This specification describes the minimum technical requirements for design, material,
construction, inspection, testing, and shipping of solid dielectric insulated shielded copper
conductor cable, 5 kV to 46 kV, rated for use in a petrochemical or offshore topsides facility.
This specification does not specify or cover shipboard type cable.
2. This specification describes requirements in U.S. Customary units and in accordance with
North American standards in jurisdictions where National Fire Protection Association
(NFPA) 70, the National Electrical Code (NEC), governs.
Note Many electrical units are metric. For example, temperature is typically specified in
metric units (°C) for electrical equipment. In this specification, U.S. Customary units
(°F) may be shown in parentheses following metric units where required for clarity.
3. This specification does not include requirements for metric power cables governed by
International Electrotechnical Commission standards.
4. Some content herein is reproduced from PIP ELSWC07 and used under PIP’s membership
agreement.
Comment: Three-conductor cables are typically recommended for the majority of applications.
Single-conductor or triplexed (cabled/twisted together) cables may be considered for
existing facilities to match existing installations or for special cases or where
three-conductor cables are not practical.
2.0 REFERENCES
1. The following documents are referenced herein and are considered part of this specification.
2. Unless otherwise specified in Section 2.1 or 2.2, use the latest edition of the referenced
document.
3. Refer to Appendix A for additional references not cited in the text of this specification.
3.0 ACRONYMS
ASD—Adjustable Speed Drive
AWG—American Wire Gauge
CPE—Chlorinated Polyethylene
CSPE—Chlorosulfonated Polyethylene
ESC—End Sealing Cap
EPR—Ethylene Propylene Rubber
MC-HL—Metal Clad Cable for Hazardous Location
MV—Medium Voltage
PE—Polyethylene
PO—Purchase Order
PVC—Polyvinyl Chloride
TC—Tray Cable
TRXLPE—Tree-Retardant Cross-Linked Polyethylene
XLPE—Cross-Linked Polyethylene
4.2 Guarantee
The equipment warranties specification, GEN-SU-3042, shall apply.
Comment: GEN-SU-3042 should also be submitted for information and review by manufacturers.
5.0 REQUIREMENTS
Cables shall be suitable for installation in wet or dry locations, indoors, outdoors (exposed to direct
sunlight), cable tray (sunlight resistant), direct burial or conduit, underground duct or any other
raceway, or messenger supported, unless otherwise noted.
5.1.1 Conductors
1. Conductors shall be bare uncoated annealed copper in accordance with ASTM B3.
Copper shall be new; recycled copper shall not be acceptable.
2. Conductors shall be round concentric-lay-stranded in accordance with ASTM B8
Class B or compact stranded in accordance with ASTM B496 unless otherwise
specified in ELC-DS-2447 (hereafter referred to as “the data sheet”).
3. Conductor diameter shall be in accordance with ICEA S-97-682. If left blank in the
data sheet, conductors shall be either concentric stranded in conformance with
ASTM B8 or compact-round-stranded in conformance with ASTM B496. When
specified in the data sheet, the conductor shall be configured accordingly.
Comment: Manufacturer’s standard conductor configurations may vary among
vendors. Unless there is reason to select a specific configuration, leave
this portion of the data sheet blank.
It is important to check with or notify the cable accessory manufacturer of
the conductor wire size, cross section, configuration, compact, shape,
outside diameter, etc. This may affect the type/size of lug, crimping die,
etc. A convenient method of providing and verifying this information is to
provide cable catalog sheets to the accessory manufacturer.
5.1.3 Insulation
1. Insulation shall be manufactured from high-quality heat-, moisture-, ozone-, and
corona-resistant ethylene propylene rubber (EPR) compounds in accordance with
ICEA S-97-682, AEIC CS8, and UL 1072.
Comment: “Treeing” is a gradual deterioration of insulation developed under
voltage stress, especially when moisture is present. The name “treeing” is
derived from the branched appearance of the deterioration channels on
the affected insulation. This phenomenon occurs in solid dielectric
insulation and is more prevalent and may result in a greater possibility of
cable failure in polyethylene (not acceptable for medium voltage [MV]
cable), cross-linked polyethylene (XLPE), and tree-retardant polyethylene
(TRXLPE) (to an extent) than EPR. For this reason and the long life of
EPR insulation, EPR is Chevron’s insulation of choice for MV cable.
2. Insulation type, voltage rating, and insulation level (100% or 133%) shall be in
accordance with the data sheet.
3. The following requirements shall apply to EPR insulation:
a. It shall not contain fillers that would make the insulation susceptible to “treeing.”
b. The conductor shield, insulation, and insulation shield shall be single-pass triple
head or single-pass triple tandem extruded and cured simultaneously, and shall
meet or exceed the electrical and physical requirements of ICEA S-97-682, AEIC
CS8-07, and UL 1072.
c. Insulation thickness levels for shielded cables rated 2001 V to 5000 V shall be in
accordance with the 133 percent insulation level requirements of NFPA 70
(NEC Table 310.104[E]), unless otherwise specified in the data sheet. Minimum
insulation thickness shall be not less than 115 mils under any circumstances.
Comment: The 115 mil wall thickness is a more efficient thickness to triple
extrude. The 90 mil wall may not easily coordinate with the two
semiconducting layers.
d. Insulation thickness (level) for shielded cables rated 5001 V and above shall be in
accordance with the 133 percent insulation level requirements of NFPA 70 (NEC
Table 310.104[E]), unless otherwise specified in the data sheet.
Comment: 133 percent insulation level cable is recommended for MV
installations because of possible increased cable life and decreased
likelihood of faults.
Insulation thickness defined as 133 percent of the insulation level
requirements of NFPA 70 (NEC Table 310.104[E]) mimics the ICEA
standard with one exception. The ICEA standard lists the insulation
thicknesses as “minimum.” NEC Table 310.104(E) shows the same
thicknesses as minimum average (or the industry traditional means of
defining the walls). The ICEA minimum walls are shown as 95
percent of the minimum average.
4. Unless otherwise specified in the data sheet, cable shall be rated a minimum of 90°C
for normal operation, 140°C for emergency overload conditions, and 250°C for
short-circuit conditions.
Comment: The majority of EPR insulated cables produced by quality manufacturers
are now rated 105°C continuous operation as a standard, although
Chevron recommends using them at their 90°C rating. Sizing cables for
90°C continuous operation ensures maximum reliability and service life.
It also ensures that termination lugs, splices, terminations, splice/joints
are applied within their rating.
5. Unless otherwise specified in the data sheet, individual conductor phase identification
shall be manufacturer’s standard.
6. Cross-linked polyethylene (XLPE), tree-retardant cross-linked polyethylene
(TRXLPE), or other insulating materials shall not be provided without Owner’s
acceptance.
4. Unless otherwise specified in the data sheet, the metal tape shall be minimum 5.0 mil
bare copper, continuous length, and applied helically with a 12.5 percent minimum
overlap and in accordance with other requirements of ICEA S-97-682.
Comment: Shielding tape is preferred because it provides a more uniform electric
field. Wire shielding (common for utility cables) may deform or break
during installation causing a distorted electrical field and possible
insulation failure.
5. Shield drain wire(s) shall be supplied if specified in the data sheet.
Comment: Shield drain wire(s) are generally not required or recommended unless
studies indicate they are required. Chevron requires that ground
conductors be provided with power conductors in cables.
2. Cable for adjustable speed drive (ASD) applications shall be 3-conductor cable
provided with an overall sheath (continuous aluminum welded and corrugated sheath)
and shall be provided with three symmetrical ground conductors located in the outer
interstices between the phase conductors.
5.3 Shipping
cable shall be exposed to facilitate testing and to ensure that the sequential footage is
readable.
a. Cable reels shall be stored indoors when possible.
b. Cable reels stored outdoors shall be supported off the ground and covered with a
suitable weatherproof material.
c. Reel supports shall be at least twice the width of the reel flange.
5. Reel packaging and protective coverings shall be in accordance with NEMA WC 26.
If specified in the data sheet, wood lagging shall be used.
6. There shall be no water and no corrosion in the completed cable when the reel is
shipped. If the conductor shows evidence of slight corrosion and no pitting, then the
Supplier shall verify that the cable has been durably sealed before shipment to prevent
entrance of moisture.
7. Material handling equipment shall not come into contact with cable surfaces.
8. The minimum diameter of the drum of the shipping reel shall not be less than
prescribed in ICEA A-9-428.
9. The cable manufacturer minimum recommended bending radius shall not be
exceeded, and in no case shall the drum diameter be less than 15 times the cable
external diameter.
10. Lifting yokes shall be used when lifting heavy reels of cable.
11. Steel arbors of suitable diameter and length shall be used when lifting cable reels with
overhead lifting devices.
12. Weatherproof tags bar-coded with description, footage, reel number, and traceability
number shall be permanently attached to the inside flange of reel.
5.4 Documentation
APPENDIX A
ADDITIONAL REFERENCES
The following references are not cited in this specification but are listed here for further reference.
Underwriters Laboratories
UL 2225 Cables and Cable-Fittings for Use in Hazardous (Classified) Locations