Aluminium Tubular Busbars For HV Substat

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

TECHNICAL REPORT

ALUMINUM TUBULAR BUSBARS FOR HV SUBSTATIONS

In many instances HV outdoor substations with a high current rating are constructed more economically with aluminum tubular busbars rather
than with stranded conductors. The advantages realized by using aluminum tubular busbars are:

• Busbars are lighter in weight and have a greater stiffness than stranded conductors with the same current transfer capacity.
- This facilitates larger free spans;
- Which require fewer points of supports and foundations;
• impose a lower mechanical load on the foundation points and circuit equipment than stranded cables do under short circuit conditions;
• are good electrical conductors due to the skin effect: the busbar surface has a current density that is relatively lower than that of a stranded
conductor;
• are permanently corrosion resistant;
• possess excellent electric conductance properties;
• have a smooth surface;
• maintenance free;
• have a very long life span.

Tubular busbars can be welded together to provide a total length of about 140 meters.

In Southern Africa aluminum tubular busbars up to a nominal diameter of 160mm with a wall thickness of 8mm can be locally manufactured
and provided up to maximum lengths of 12 meters. Larger diameter lengths of tube are supplied by the company out of recognized foreign
manufacturers.

The following information relates to imported aluminum tubular busbars manufactured in accordance with Standard EN 755-2.

Using the information detailed hereunder, you can calculate which specifications the aluminum tubular busbars used in your projects must
meet. The guidelines and methods of calculation detailed have been determined by KEMA of the Netherlands.

It is assumed that the client knows the following details:


The nominal current during normal operation. The
required short-circuit current.
The applicable center-line distance between busbars. The
Maximum span between two busbars supports.

Based on these details a correct choice of busbar diameter and wall thickness can be made using the method described below. The

dimensions of a busbar are mainly determined by two physical loads, i.e. the thermal and mechanical loads on the busbar.

MATERIAL PROPERTIES

The alloys listed below, which comply with EN 755-2, are those most commonly used for electrical busbars. Alloy 6101B T6 has more mechanical
strength but less electrical conductivity. If higher electrical conductivity is required, alloy 6101B T7 can be used. However, this alloy has less
mechanical strength. Of course busbars made of other alloys can also be supplied.

Alloy
Property Unit
6101BT6 6101BT7
Specific gravity p Kg/m³ 2, 700 2, 700
Young’s modulus E N/mm² 70, 000 70, 000
Stress corresponding to the yield point (Rρ) N/mm² 160 120
Ultimate tensile strength (Rм) N/mm² 215 170
Elongation % 8 12
Coefficient of linear expansion ∂ (0 - 100ºC) K-1 23.5 x 10-6 23.5 x 10-6
Electrical conductivity (at 20ºC) MS/m (m/Ωmm² 30 32
THERMAL CAPACITY OF BUSBARS

The thermal capacity of a busbar is mainly determined by:


• the environment: temperature and solar radiation;
• the nominal current;
• the maximum busbar temperature as determined by the client.

When the amount of heat absorbed by the busbar is the same as the amount of heat it emits, equilibrium is reached. In this situation the busbar
temperature will remain constant. The current at this point of equilibrium is the current-carrying capacity of the busbar.

This heat balance must be considered under normal operating conditions and under the extreme condition of a short-circuit. During a short-
circuit extra heating of the busbars may occur in a short space of time.

Normal operating conditions:

In this documentation the allowable current was calculated in accordance with DIN43 670 with an ambient temperature or 35ºC, a final busbar
temperature of 80ºC, an absorption coefficient of 0.6 and a solar radiation of 600W/m².

The allowable current for the busbar dimensions and standard aluminum alloys available are given in table 2 and table 3.

It can be seen from the tables that when using aluminum alloy 6101B T7 for a current carrying capacity of 3000A, the minimum busbar
dimensions (diameter/wall thickness) of 100/10, 120/6 or 160/4 are acceptable.

For different ambient temperatures or final busbar temperatures the current carrying capacity can be determined using the load factor from
figure 1.

Example:
At an ambient temperature of 30ºC and a final busbar temperature of 65ºC, the current carrying capacity from table 2 or 3 has to be multiplied
by a factor 0.86.

If, under these conditions, a busbar has to be selected for a nominal current of 3000A, the method is as follows: The effective
load on the busbar is 3000 : 0.86 = 3488 A.
From the table (6101B T7) it can be seen that possible choices for busbar dimensions are 120/10 or 160/5.

Figure 1. Current carrying capacity as function of ambient temperature and final busbar temperature
Short-circuit

Under short-circuit conditions the final busbar temperature must not exceed 200ºC, based on an initial temperature of 80ºC. Higher
temperatures can affect the structure of the aluminum alloy, which results in changes in its mechanical properties. During short-circuits the
temperature will generally remain below the allowable temperatures of 200ºC, based on a busbar temperature of 80ºC during normal operation.

After determining the busbar cross-section, the current density during a short-circuit can be determined. This current density
(J) can be determined from the short-circuit 1K and the cross-section of the busbar.

Table 1. Current density (J) as a function of material type and duration of the short-circuit current.

Duration of the short- 6101BT6 6101BT7


circuit Jeff Jeff
current (s) (Amp./mm²) (Amp./mm²)
0.5 118 122
1.0 83 86
1.5 68 70
2.0 59 61
3.0 48 50
5.0 37 38

MECHANICAL CAPACITY OF BUSBARS

The busbar’s diameter and wall thickness are not determined on the basis of the current carrying capacity only. The sag as a result of normal and
exceptional loads must also be considered.

In accordance with the harmonization document “HD 637 Power installations exceeding 1kV a.c.”, busbars must meet mechanical requirements
that have been derived from the following loads and operating conditions: -

Normal loads considering:


• the busbar’s mass
• ice load
• wind load

These loads determine the sag of the busbar under normal operating conditions. The amount of sag depends on the stiffness of the busbar. If
the busbar’s diameter and wall thickness are determined, the sag under normal operating conditions can be determined. This can be important
for the design of a switchyard.

The sag resulting from the mass and span length of the busbar can be determined from figure 2.
Figure 2. Busbar sag as function of span length (as a result of the mass of the busbar itself)

Exceptional loads, considering:


• short-circuit forces
• switching forces.

Only forces on the busbar during short-circuits are considered below, since these forces are the determining factor in most cases.

In a three-phase system with three busbars in the same plane, the greatest force during short-circuits will occur in the centre busbar.
Electromagnetic forces will occur between the conductors as a result of the short-circuit current. The busbar must have a certain stiffness to
absorb these forces. The required section modulus was determined in accordance with the simplified calculation method of IEC 865.

Based on the required short-circuit current and phase-to-phase distance, the electromagnetic force per metre busbar can be determined using
figure 3 and figure 4 (depending on the alloy used). With this data and the required span length the required section modulus can be seen.

The calculations are based on:


• a two-point support for the busbar
• a factor of plasticity of 1.4
• automatic re-closing after the short-circuit.
DETERMINING THE BUSBAR DIAMETER AND CROSS-SECTION

With the required nominal current-carrying capacity and the required section modulus one or more suitable busbar dimensions that meet both
requirements can be found in table 2 or 3.

Example of determining a busbar dimension:

Criteria

Inormal : 4000A nominal current during operation


Ik : 50kA short-circuit current
aphase-phase : 4m phase-phase distance
Lmax : 12m span length, distance between supports
Al alloy : 6101BT6

The following busbar dimensions (diameter/wall thickness) are acceptable for the required nominal current of 4000 A:120/15, 160/8, 200/5 and
220/4 (see table 2).

Using figure 3 it can be determined that, at the given short-circuit current, phase-to-phase distance and span length, the required section
modulus is approximately 100cm³. Among others, the following busbar dimensions meet this requirement: 120/12, 160/6, 200/5 and 220/4.

Busbars 120/15, 160/8, 200/5 and 220/4 meet both the current carrying capacity requirements and the requirements from the dynamic short-
circuit load. Busbar 220/4 is the lightest in weight but is vulnerable due to its small wall thickness. Therefore, a choice should be made between
120/15, 160/8 or 200/5.

After determining the diameter and wall thickness, the client’s choice of busbar may be based on the following:
• weight saving
• standardization of busbars to be used (possibly a preference for 120mm type)
• sag of the busbar as a result of busbar mass (see figure 2)
• current density in the busbar as a result of short-circuits (see table 1)
• ease of working on the busbar (it is easier to weld termination pieces to busbars with greater wall thickness.)

Changing assumptions or parameters can be discussed with KEMA, if required. Optimization can lead to significant savings, not just on busbar
material but also on supports, e.g. lighter insulators, support structures and foundations. To this end, KEMA has advanced calculation methods
and tools at its disposal.

TUBE OPERATIONS

Aluminium tubular busbars are subject to wind-generated vibration and oscillation. Because of the low self-damping of tubular busbars very
slight excitation forces will suffice to excite the tubes to vibration amplitudes of the order of the tube diameter, when there is a resilience of the
excitation force with a natural frequency of the tube. These high amplitudes produce additional dynamic stresses inside all structural parts and
it is often necessary to dampen this tube oscillation by the insertion of AAC conductor into the busbar. The increased self-damping provided by
the insertion of damping conductor delays the onset of resilience build-up and this limits the maximum amplitudes created by a given
excitation force.

Recommended Damping Cables

As a rule it is normally sufficient to insert one conductor Permissible spacing


into a tube, but in order to increase the safety and to Tube-Ø Al-cable between supports
maintain maximum damping effect it is advisable to without damping
insert tow conductors into the tube (one at each end cables m
mm mm
running for 2/3 of the tube length). The following table (normal values)
shows recommended damping conductor sizes. A drain
hole of 10mm diameter should be drilled at bottom 63 120 3.0
centre point of tubes to facilitate drainage of 80 150 3.5
condensate moisture. 100 240 4.5
120 300 5.5
160 500 7.5
200 625 9.5
250 625 12.0

You might also like