Professional Documents
Culture Documents
Design2 Calculation
Design2 Calculation
Design2 Calculation
College of Engineering
ELECTRICAL ENGINEERING DEPARTMENT
Submitted by
Benjie R. Romano
BSEE
SN: 2019-101694
Submitted to
PROBLEM
DESIGN NO. 2
DESIGN OF CURRENT TRANSFORMER FOR WATTHOUR METER
(pp 397 -403)
PROBLEM: Design a transformer to meet the following specifications:
Ratio: 150/5
Voltage of primary circuit: 4,800
Frequency = 60 Hz
External Burden: Volt-ampere = 4
Power Factor = 0.85
Possible limits of error over range from 10 to 100 per cent of rated current:
Phase angle = 25 minutes
Ratio = 0.5 per cent
Draw the Cross section through current transformer (Fig. 180, p 401)
151. Illustrative Example. Design of Current Transformer for
Watthour Meter. The specification for this transformer is given at the top of
the design sheet shown on page 398. It is not possible to calculate the various
items in the order in which they are recorded on the design sheet, but so far
as possible this order will be followed in working out the numerical values.
-----figure 179-----
Assuming current density of 1,100 and 1,400 amp per sq. in., in
secondary and primary, respectively, we have 5/1,100 = 0.00454 as the cross
section of the secondary wire. From the wire table on page 432, we select No.
13 square wire with a cross section of 0.00465 sq. in. The current density in
the secondary is, therefore, ∆ = 5/0.00465 = 1,075 amp per sq. in.
1
equal to about twice the width D, we may try the dimensions H = 4 and D =
4
1
2 in. The width D may be altered later if necessary to accommodate the
4
coils
A rough estimate must be made of the core cross section in order that
the lengths of wire in the winding may be calculated. The total flux in the core
will depend upon the total voltage to be generated in the secondary and not
only the amount of external burden. We shall assume the total burden
(including secondary winding and connecting leads) to be 15 volt-amp which,
with secondary current of 5 amp, means that the flux in the core must develop
3 volts in the 280 turns of secondary winding. Thus,
3× 108
Φ= =4,000 maxwells
4.44 × 60× 280
Very low flux densities must be used in order to avoid exceeding the limits of
error as specified. If we use a good quality of silicon-steel, which is cheaper
material than nickel-steel, we may select a flux density as low as B’’ = 2,000
1 1
lines per sq. in. This leads to a core section about 1 by 1 in. which, with a
2 2
stacking factor of 0.89,, makes the cross section of iron equal to 1.5 × 1.5 ×
0.89 = 2 sq. in.
Items 8 to 14. For the primary winding we need a copper cross section
of about 200/1,400 = 0.143 sq. in. and, since we have to insulate for 6,000
1 1
volts, we shall assume a winding layer 3 in long, leaving in. at each end
4 2
between high-tension winding and core. Two strips in parallel, each of 0.44 by
0.16 in,. wound one on top of the other to make one layer seven turns will
probably satisfactory. The current density in primary is therefore 200/[2(0.44 ×
0.16)] = 1,420 amp per sq. in. For the secondary, the length of layer may be 3
3
in. There will be 7 layers of No. 13 square dcc wire with 0.005-in. paper
4
between layers.
5
With a window opening D = 1 in., there should be plenty of room to
8
accommodate the windings. The reason why this dimension is appreciably
1
less than the estimated 2 in. is that the windings are all on one limb instead
4
of on both limbs as in power transformers, and also that solid insulation has
been used and there are no ducts for oil circulation.
The mean length per turn of primary is 0.95 ft., and of the secondary,
0.76 ft. The weight of primary is 3.6 lb., and of secondary, 4.23 lb.
Items 15 to 18. From the wire table on page 431, the resistance per
1,000 ft. of square No. 13 wire is found to be 1.846 ohms at 60°C. Whence
the secondary resistance at 75°C is 1.846 × 0.213 × [(235 + 75)/(235 + 60)] =
0.413 ohm, and the IR drop is 0.413 X 5 = 2.065 volts. Including connections
between transformer and instrument, this drop might be 2.2 volts. In order to
calculate the total burden (internal plus external), we have for the instrument
burden, IZ = 3.5/5 = 0.7 volt; IR = 0.7 × 0.85 = 0.595 volt, and IX = 0.7 ×
0.527 = 0.369 volt. If we assume the reactance of the secondary winding and
leads to be negligible, the total IR is 2.795 and the total IX is 0.369.
1 5
Items 19 to 27. The corrected window dimensions are 4 by 1 in. The
4 8
total flux is Φ = (2.82 × 108/(4.44 × 60 × 280) = 3,780 maxwells; whence B" =
3,780/2 = 1,890 lines per sq. in. when the secondary current has its full rated
value of 5 amp.
1 5 3
The mean length of flux path in the core is 2(4 + 1 + 3) = 17 in.
4 8 4
The weight of iron is 17.75 × 2 × 0.28 = 10 lb.
Items 28 to 31. From Fig. 178 we read the ampere-turns per inch for
the iron (silicon-steel), about 0.35 for B" = 1,890, and 0.05 for B" 189. From
Fig.179 we read watts per pound = 0.0015 for B” = 1,890. It is practically
impossible to read the losses at one-tenth rated burden, from this curve, but
by assuming the iron loss to vary as B1.6, we have, for B” = 189, watts per
1 1.6
pound = 0.0015 × ( ) = 0.000037.
10
In calculating the magnetizing current component, we shall make an
allowance for joints in the magnetic circuit because the reluctance of the
-----fig180-----
Joints is negligible at very low flux densities. Then, by formula (153), at full
load,
17.75× 0.35
Io = √ 2×7
=0.628 amp
10 × 0.0015
Io = 40 × 2.82
=0.213 amp
10 × 0.000037
Io = 40 × 0.282
=0.0525 amp
Item 32. By formula (151) the tangent of the phase angle with 100 per
rent rated current is
whence α = +10’.
Item 33. If we leave the secondary winding unchanged with 280 turns,
the ratio with full-rated current, by formula (152), is
the maximum percentage ratio error being 100 × (0.128/40) = 0.32 which is
well within the specified limit of 0.5 per cent. If desired, this error can be
reduced by altering the number of secondary turns. Thus, if we remove one
9
turn of the secondary, the compensation for ratio error is 27 - 40= -0.143,
7
which makes the actual ratio at full load equal to 39.916 and at one-tenth
load, 39.985, the percentage errors being 0.21 and 0.037 respectively.
DRAWINGS
Fig. 179 Losses in transformer iron for low values of flux density.
Fig. 168. Porcelain Bushings for transformer leads
VECTOR DIAGRAMS