1.b Schedule of Loads

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

PROPOSED 3 STOREY APARTMENT BUILDING

931 Sitio Sapa, Brgy. Pag-Asa, Binangonan, Rizal


Owner: Emmanuel Lipio Jr.

SCHEDULE OF LOADS
Single Phase 2- Wires + Ground 230V Surface Mounted

PANEL NAME: Sub Panelboard 1 (Common Area & Stairs - Ground to Roof Deck)
Location: Wall Inside Hanging Cabinet at Kitchen of Unit 1, Ground Floor
Fed From: Main Distribution (Ground Floor)

Circuit No. Description


LOADS Power Voltage Current Size of Conductor ø Conduit Circuit Protection
(WATTS) (VOLTS) (AMPERE) (mm²) (mm²)
LO CO CF OTHERS AT
12(10W) + 2(8W) +
Circuit C#1 4(8W) - > Led Lighting 18 188 230 0.82 3-2.0mm2 THHN 20- PVC Pipe 15A - 2P
Outlets
7(360W) + 1(360W) - >
Circuit C#2 Waterproof & Duplex 11 2880 230 12.52 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
C.O.s
1 (1 HP) - > Water
Circuit C#3 2 1 750 230 3.26 3-2.0mm2 THHN 20- PVC Pipe 15A - 2P
Pump
TOTAL 3818 230 16.60

Gen. Lighting & Convenience Receptacle Load 3068 VA


Small Appliance Load 0 VA
Laundry Circuit Load 750 VA
Sub-Total 3818 VA

Application of Demand Factors:


First 3,000 VA at 100% DF 3000 VA
Remainder at 35%DF (818 VA x .35) 286.3 VA

Other Load: AC Circuit Load (VA x 250%) 0 VA


Total 3286.3 VA
Nominal Voltage 230 V
14.29 A

Main Circuit Breaker 30 A


Use 2 - 5.5 mm2 THHN + 1 - 5.5 mm2 TW Earth Conductor in 32mmØ IMC
Service Entrance Conductor 5.5 mm2
Use 30A, 2P Isolator (subpanel disconnection switch)

PANEL NAME: Sub Panelboard 2 (Ground Floor - Unit 1)


Location: Wall Inside Hanging Cabinet at Kitchen of Unit 1, Ground Floor
Fed From: Main Distribution (Ground Floor)

LOADS Circuit Protection


Circuit No. Description
Power Voltage Current Size of Conductor ø Conduit
LO CO CF OTHERS (WATTS) (VOLTS) (AMPERE) (mm²) (mm²) AT

7(10W) + 2(5W) - > Led


9
Lighting Outlets
Circuit G#1 150 230 0.65 3-2.0mm2 THHN 20- PVC Pipe 15A - 2P
1(60W) + 1(30W) - >
2
Exhaust & Ceiling Fans

Circuit G-#2 5 Duplex C.O.s 5 1800 230 7.83 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit G#3 1 Oven Outlet 1 2000 230 8.70 3-3.5mm2 THHN 25- PVC Pipe 20A - 2P
Circuit G#4 1 Range Outlet 1 3000 230 13.04 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit G#5 1 Refrigerator Outlet 1 1500 230 6.52 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit G#6 1 (1.5HP) ACU 1 1119 230 4.87 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit G#7 1 Washing Machine 1 1700 230 7.39 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
TOTAL 11269 230 49.00

Gen. Lighting & Convenience Receptacle Load 1950 VA


Small Appliance Load 6500 VA
Laundry Circuit Load 1700 VA
Sub-Total 10150 VA

Application of Demand Factors:


First 3,000 VA at 100% DF 3000 VA
Remainder at 35%DF (7150 VA x .35) 2502.5 VA

Other Load: AC Circuit Load (1119 VA x 250%) 2797.5 VA


Total 8300 VA
Nominal Voltage 230 V
36.09 A

Main Circuit Breaker 60 A


Use 2 - 14 mm2 THHN + 1 - 5.5 mm2 TW Earth Conductor in 32mmØ IMC
Service Entrance Conductor 14 mm2
Use 60 A, 2P Isolator (subpanel disconnection switch)

Page 1 of 4
PANEL NAME: Sub Panelboard 3 (2nd Floor - Unit 2)
Location: Wall Inside Hanging Cabinet at Kitchen of Unit 2, 2nd Floor
Fed From: Main Distribution (Ground Floor)

LOADS Power Voltage Current Size of Conductor ø Conduit Circuit Protection


Circuit No. Description
LO CO CF OTHERS (WATTS) (VOLTS) (AMPERE) (mm²) (mm²) AT

7(10W) + 2(5W) - > Led


9
Lighting Outlets
Circuit 2#1 150 230 0.65 3-2.0mm2 THHN 20- PVC Pipe 15A - 2P
1(60W) + 1(30W) - >
2
Exhaust & Ceiling Fans

Circuit 2#2 5 Duplex C.O.s 5 1800 230 7.83 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit 2#3 1 Oven Outlet 1 2000 230 8.70 3-3.5mm2 THHN 25- PVC Pipe 20A - 2P
Circuit 2#4 1 Range Outlet 1 3000 230 13.04 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit 2#5 1 Refrigerator Outlet 1 1500 230 6.52 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit 2#6 1 (1.5HP) ACU 1 1119 230 4.87 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit 2#7 1 Washing Machine 1 1700 230 7.39 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
TOTAL 11269 230 49.00

Gen. Lighting & Convenience Receptacle Load 1950 VA


Small Appliance Load 6500 VA
Laundry Circuit Load 1700 VA
Sub-Total 10150 VA

Application of Demand Factors:


First 3,000 VA at 100% DF 3000 VA
Remainder at 35%DF (7150 VA x .35) 2502.5 VA

Other Load: AC Circuit Load (1119 VA x 250%) 2797.5 VA


Total 8300 VA
Nominal Voltage 230 V
36.09 A

Main Circuit Breaker 60 A


Use 2 - 14 mm2 THHN + 1 - 5.5 mm2 TW Earth Conductor in 32mmØ IMC
Service Entrance Conductor 14 mm2
Use 60 A, 2P Isolator (subpanel disconnection switch)

PANEL NAME: Sub Panelboard 4 (2nd Floor - Unit 3)


Location: Wall Inside Hanging Cabinet at Kitchen of Unit 3, 2nd Floor
Fed From: Main Distribution (Ground Floor)

LOADS Power Voltage Current Size of Conductor ø Conduit Circuit Protection


Circuit No. Description
LO CO CF OTHERS (WATTS) (VOLTS) (AMPERE) (mm²) (mm²) AT

7(10W) + 2(5W) - > Led


9
Lighting Outlets
Circuit 3#1 150 230 0.65 3-2.0mm2 THHN 20- PVC Pipe 15A - 2P
1(60W) + 1(30W) - >
2
Exhaust & Ceiling Fans

Circuit 3#2 5 Duplex C.O.s 5 1800 230 7.83 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit 3#3 1 Oven Outlet 1 2000 230 8.70 3-3.5mm2 THHN 25- PVC Pipe 20A - 2P
Circuit 3#4 1 Range Outlet 1 3000 230 13.04 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit 3#5 1 Refrigerator Outlet 1 1500 230 6.52 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit 3#6 1 (1.5HP) ACU 1 1119 230 4.87 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit 3#7 1 Washing Machine 1 1700 230 7.39 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
TOTAL 11269 230 49.00

Gen. Lighting & Convenience Receptacle Load 1950 VA


Small Appliance Load 6500 VA
Laundry Circuit Load 1700 VA
Sub-Total 10150 VA

Application of Demand Factors:


First 3,000 VA at 100% DF 3000 VA
Remainder at 35%DF (7150 VA x .35) 2502.5 VA

Other Load: AC Circuit Load (1119 VA x 250%) 2797.5 VA


Total 8300 VA
Nominal Voltage 230 V
36.09 A

Main Circuit Breaker 60 A


Use 2 - 14 mm2 THHN + 1 - 5.5 mm2 TW Earth Conductor in 32mmØ IMC
Service Entrance Conductor 14 mm2
Use 60 A, 2P Isolator (subpanel disconnection switch)

Page 2 of 4
PANEL NAME: Sub Panelboard 5 (3rd Floor - Unit 4)
Location: Wall Inside Hanging Cabinet at Kitchen of Unit 4, 3rd Floor
Fed From: Main Distribution (Ground Floor)

LOADS Power Voltage Current Size of Conductor ø Conduit Circuit Protection


Circuit No. Description
LO CO CF OTHERS (WATTS) (VOLTS) (AMPERE) (mm²) (mm²) AT

7(10W) + 2(5W) - > Led


9
Lighting Outlets
Circuit 4#1 150 230 0.65 3-2.0mm2 THHN 20- PVC Pipe 15A - 2P
1(60W) + 1(30W) - >
2
Exhaust & Ceiling Fans

Circuit 4#2 5 Duplex C.O.s 5 1800 230 7.83 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit 4#3 1 Oven Outlet 1 2000 230 8.70 3-3.5mm2 THHN 25- PVC Pipe 20A - 2P
Circuit 4#4 1 Range Outlet 1 3000 230 13.04 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit 4#5 1 Refrigerator Outlet 1 1500 230 6.52 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit 4#6 1 (1.5HP) ACU 1 1119 230 4.87 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit 4#7 1 Washing Machine 1 1700 230 7.39 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
TOTAL 11269 230 49.00

Gen. Lighting & Convenience Receptacle Load 1950 VA


Small Appliance Load 6500 VA
Laundry Circuit Load 1700 VA
Sub-Total 10150 VA

Application of Demand Factors:


First 3,000 VA at 100% DF 3000 VA
Remainder at 35%DF (7150 VA x .35) 2502.5 VA

Other Load: AC Circuit Load (1119 VA x 250%) 2797.5 VA


Total 8300 VA
Nominal Voltage 230 V
36.09 A

Main Circuit Breaker 60 A


Use 2 - 14 mm2 THHN + 1 - 5.5 mm2 TW Earth Conductor in 32mmØ IMC
Service Entrance Conductor 14 mm2
Use 60 A, 2P Isolator (subpanel disconnection switch)

PANEL NAME: Sub Panelboard 6 (3rd Floor - Unit 5)


Location: Wall Inside Hanging Cabinet at Kitchen of Unit 5, 3rd Floor
Fed From: Main Distribution (Ground Floor)

LOADS Power Voltage Current Size of Conductor ø Conduit Circuit Protection


Circuit No. Description
LO CO CF OTHERS (WATTS) (VOLTS) (AMPERE) (mm²) (mm²) AT

7(10W) + 2(5W) - > Led


9
Lighting Outlets
Circuit 5#1 150 230 0.65 3-2.0mm2 THHN 20- PVC Pipe 15A - 2P
1(60W) + 1(30W) - >
2
Exhaust & Ceiling Fans

Circuit 5#2 5 Duplex C.O.s 5 1800 230 7.83 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit 5#3 1 Oven Outlet 1 2000 230 8.70 3-3.5mm2 THHN 25- PVC Pipe 20A - 2P
Circuit 5#4 1 Range Outlet 1 3000 230 13.04 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit 5#5 1 Refrigerator Outlet 1 1500 230 6.52 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P

Circuit 5#6 1 (1.5HP) ACU 1 1119 230 4.87 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
Circuit 5#7 1 Washing Machine 1 1700 230 7.39 3-3.5mm2 THHN 20- PVC Pipe 20A - 2P
TOTAL 11269 230 49.00

Gen. Lighting & Convenience Receptacle Load 1950 VA


Small Appliance Load 6500 VA
Laundry Circuit Load 1700 VA
Sub-Total 10150 VA

Application of Demand Factors:


First 3,000 VA at 100% DF 3000 VA
Remainder at 35%DF (7150 VA x .35) 2502.5 VA

Other Load: AC Circuit Load (1119 VA x 250%) 2797.5 VA


Total 8300 VA
Nominal Voltage 230 V
36.09 A

Main Circuit Breaker 60 A


Use 2 - 14 mm2 THHN + 1 - 5.5 mm2 TW Earth Conductor in 32mmØ IMC
Service Entrance Conductor 14 mm2
Use 60 A, 2P Isolator (subpanel disconnection switch)

Page 3 of 4
PANEL NAME: Main Distribution PanelBoard
Location: Wall Inside Hanging Cabinet at Kitchen of Unit 1, Ground Floor
Fed From: Service Entrance (Service Provider 2-Wire, 1 dia, 230-V Supply)

Connected Load (in VA) Size of Conductor ø Conduit Circuit Protection


Circuit No. Description Location
WATTS VOLTS AMPERE (mm²) (mm²) AT
Common Area & Stairs - Ground
1 Sub Panelboard 1 3286.3 230 14.29 3-3.5mm2 THHN 32- IMC Pipe 20A - 2P
to Roof Deck
2 Sub Panelboard 2 Ground Floor - Unit 1 8300.0 230 36.09 3-3.5mm2 THHN 32- IMC Pipe 60A - 2P
3 Sub Panelboard 3 2nd Floor - Unit 2 8300.0 230 36.09 3-3.5mm2 THHN 32- IMC Pipe 60A - 2P
4 Sub Panelboard 4 2nd Floor - Unit 3 8300.0 230 36.09 3-3.5mm2 THHN 32- IMC Pipe 60A - 2P
5 Sub Panelboard 5 3rd Floor - Unit 4 8300.0 230 36.09 3-3.5mm2 THHN 32- IMC Pipe 60A - 2P
6 Sub Panelboard 6 3rd Floor - Unit 5 8300.0 230 36.09 3-3.5mm2 THHN 32- IMC Pipe 60A - 2P
7 Spare 0.0 230 0.00 3-3.5mm2 THHN 32- IMC Pipe 60A - 2P
8 Spare 0.0 230 0.00 3-3.5mm2 THHN 32- IMC Pipe 60A - 2P
TOTAL 44786.3 230 194.72

Gen. Lighting & Convenience Receptacle Load 12818 VA


Small Appliance Load 32500 VA
Laundry Circuit Load 9250 VA
Sub-Total 54568 VA

Application of Demand Factors:


First 3,000 VA at 100% DF 3000.0 VA
Remainder at 35%DF (51568 VA x .35) 18048.8 VA

Other Load: AC Circuit Load (5595 VA x 250%) 13987.5 VA


Total 35036.3 VA
Nominal Voltage 230 V
152.33 A
Safety Factor: 152.33 x 1.25 = 190.41 A

Main Circuit Breaker 200 A


Use 2 - 80 mm2 THWN + 1 - 14 mm2 TW Earth Conductor in 50mmØ IMC
Service Entrance Conductor 125 mm2

Use 200 AT, 2P, 230V Molded Case Circuit as Main Protection

Page 4 of 4