Specification HITPL/146/08/D17 Implementation Date

Section
Title STANDARD SPECIFICATION FOR LIGHTING, SMALL POWER,
TELEPHONE, DATA COMMUNICATION, LOCAL PUSH BUTTON
STATION

INDEX
Page No.
1.0 General ............................................................................................................. 2
2.0 Lighting ............................................................................................................. 3
3.0 Small Power ..................................................................................................... 6
4.0 Telephone......................................................................................................... 6
5.0 Data Communication ........................................................................................ 7
6.0 Local Push Button Station Control Station ....................................................... 7
7.0 Junction Box ...................................................................................................... 7
8.0 Earthing............................................................................................................. 7

Page 1 of 7
1.0 GENERAL

The lighting systems shall be as described within this specification in conjunction with the General
Specification and drawings.

All lighting, fixtures with control gear and lamps required for the indoor area (buildings and
product area), outdoor lighting fixtures required lighting posts along with fixture fixing brackets
and fixing accessories shall be supplied and installed by the Contractor. The foundations for the
flood light poles will be arranged by contractor.
The Contractor shall co-ordinate with the Civil & Building Contractor while carrying out the work of
outdoor lighting system
The Contractor shall supply and install all the cables, wires and electrical accessories such as
cable trays and conduits, cable trunks, switches, sockets, isolators Distribution boards (Main &
Sub) etc. for the complete lighting and small power installation system of the entire facility.
The lighting system shall be such that all areas of the facility building and external areas are
adequately illuminated.
The system shall be designed to obtain the following minimum illuminance levels, and shall
generally be in accordance with approved International Standards.

Location Average Illuminance (Lux)

Switch gear room in general 500


Control room in general 500
Pump room indoors 150
Compressor room indoors 150
Blower indoors 100
Around pump outdoors 100
Guard room 200
Gauge glass instrument on-site 70
Indoor parking place 50
Structural stage 100
Outdoor parking place 20
Rest room 100
Power facility outdoors 50
Local instrument panel Outdoor 200
Switch rack 70
Packing area 200
Product storeroom 100
Small material store 100
Large material store 70
Substation indoor 400
Generating station 100
Fire house 250
Stairway, passage 50
Emergency stairway 30

Page 2 of 7
Outdoor raw material yard 20
Tank yard 20
Tank roof and sample point 50
Outdoor material yard 20
Centre road 13
General road 10
Road of little traffic 5

The Bill of quantities for light fittings, plug points and telephone outlets and emergency fittings
shall be furnished. The Contractor shall carryout the complete lighting design and submit lighting
layout drawings with calculations.
All switched sockets shall be provided with plug tops.

2.0 LIGHTING

The Contractor smns according to Bhall price the various items based on the types of luminaires
given in the schedules for the tender purposes. Samples shall be submitted for e
all luminaires for approval.
All luminaires in areas of false ceilings are to be supplied via a plug and socket of 3 Amps (min)
with a flexible lead to the luminaries.
All lighting fittings shall be mounted/installed on supports or concrete foundations in an approved
manner. All chasing in walls-for conduiting, laying of conduits in RC floor/roof slab required for
lighting and small power installation works shall be done by the Contractor.
Lighting of control room instrument boards-shall be designed to illuminate vertical board mounted
equipments with art glass.

The lighting DB's in general shall have circuit breakers rated 16 amperes for branch circuit
protection. Circuit loading shall not exceed 70%.
For lighting fixtures located in hazardous area shall be explosion proof type and temperature
group shall be T4.
Fixtures and accessories shall be corrosion resistant and withstand the corrosive and high
humidity atmosphere.
All bolts, machine screws, spring washers, washers, nuts and exposed accessories shall be
made of corrosion resistant materials.
Columns for street and flood lighting shall be Sling Down octagonal or round steel coluS
Standard, columns shall be hot dip galvanised to 85 microns. When the columns have a direct
buried part, a cable entry of 0.5'in below grade shall be provided.
All galvanised street light poles and flood light poles shall be further prepared and overcoated as
follows.

- Removal of contaminates by water or steam jetting.


- Application of etching primer.
- Finish coat by application of aliphatic polyurethane 100 microns dft light grey colour
RAL 7035.

Page 3 of 7
Lighting cabling including supply and installation of cable tray shall be in the scope of the
Contractor. Lighting cables shall be copper conductor, XLPE insulated, PVC outersheathed
complying to IEC 502 and 332 - 1, and BS 5467 and 6360.

The type of lighting wiring inside office building and substation shall be of concealed type in PVC
conduits. Where required G.I conduits shall be provided in hazardous areas as per IEC 79, BS
5345 and wiring regulations, and to the approval of local authorities and Engineer.

All light fittings with lamps and control gears shall be supplied and installed by the Contractor
including wiring, conduiting, light switches 1 switch boxes, Junction / pull boxes… etc.

The Contractor shall submit detailed lighting layout for all areas, the type and quantity of light
fitting shall be min. as per this schedule, along with calculations.
The emergency light fittings of the type as indicated in the legend of this schedule shall be
mounted on side walls and / or columns in the product area. In all other areas they shall be
mounted on side walls / on the ceiling / roof.

2.1 Luminaires

In general , the distribution and type of luminaries in various areas shall be as given below:
However this is only for guidelines. Contractor to select best suitable fittings as per Lighting
calculation-

Supply of light fittings with lamps, control gear and associated accessories meeting the
specification, in the location as per the drawings.

TYPE OF FITTING AREA

Modular recessed fluorescent luminaries with fluorescent tubes Indoor - Building


3 x 18 w, 600 x 600 mm, mirror Brita anodised aluminium
louvers, body of sheet steel with high reflectivity white stove
enamelled finish, all switching and sub circuit wiring

Zone - 2, Ex'd' IP65 well glass fitting with GRP body and 125 W Tank Farm Product
MBF lamp mounted on 100 mm dia GI pole, fixed to ground with Pumps foundation
concrete foundation.

Street light luminaires with 400 W SON-T standard lamp, IP 65 Switch-gear building(for
exterior lighting
moulded GPP body and hinged control gear tray and suitable for
mounting on G.I pipe, complete with GI pipe and accessories.

Round white recessed luminaire with acrylic diffuser and Building


integral control gear for 28W 2D lamps.

Page 4 of 7
Fluorescent Luminaire 1200 mm, 2 x 36 W with high Switchgear building/
performance optical system, sheet steel with low gloss stove Office building rooms.
enamelled white finish and Aluminium reflector system, suitable
for ceiling mounting
Street light luminaire with injection moulded GRP body,
detachable control gear tray with Class II insulation and 400 W Street lighting
SON -T tubular lamps and IP 65 rating.

Flood light luminaires with 400 W SON-T lamp and control gear Tank farm lighting
reflector, front frame of die cast aluminium alloy (LM 6) finished
in grey powder coat paint, hinged for front relamping, suitable for
mounting an column / poles, IP 65 rating with all accessories.

Supply and install outdoor corrosion resistant, G. I lighting Street lighting


columns, complete with breakers and fixing accessories
suitable to carry one 400 W HPSV including supply of light
fixture.
(a) 12m high GI columns
Supply and install outdoor corrosion resistant, G. 1 lighting Tankfarm
columns, complete with breakers and fixing accessories
suitable to carry one HPSV but excluding supply of light fixture.
(a) 14m high GI columns
Supply and install maintained single sided 2 x 18 W fluorescent Switch gear,
EXIT sign engraved In English of steel construction with three Transformer, Control
room, pump Buildings
hour duration and suitable for ceiling or wall mounting luminaire
etc.
type

Supply and install maintained three hour rated emergency light Switch gear,
with 2 x 18 W 300 mm fluorescent" lamp suitable for ceiling / Transformer, Control
wall mounting. Luminaire type room, pump Buildings etc
Supply and installation of single phase twin 20 A plug socket. All Buildings, pump
houses

Supply and installation of single phase twin switched 13 A plug All buildings, Pump
socket houses

Supply and installation of BASEEFA certified explosion proof Near switch gear & Pump
240 V 16A plug socket with interlocked switch and plug top with houses
two cable entries
Supply and installation of following safety items: Switch gear and Control
a) Rubber mat for installation Room
12 mm - ditto -
6 mm - ditto -
b) First aid box - ditto -
d) 415 grade rubber gloves

Page 5 of 7
Supply and installation of miscellaneous items: Switchgear Building
i) Hand dryer At various locations
ii) Heater connection element
iii) UPVC pipes of dia
a) 50 mm
b) 100 mm
e) 150 mm

Supply and installation of BASEEFA certified explosion proof 41 Pump house(Crane)


5 V, 3 phase, 30 A load break
switch of cast aluminium material with
padlocking facility in ON and OFF position

3.0 SMALL POWER

The small power system shall be as per the schedule for Lighting vide Item1.8.2.1 above. The
Contractor shall co-ordinate with the Civil and Building Contractor for the concealed conducting in
concrete/block work and for making penetrations/cuttings in cladding/false ceiling.
Socket outlets shall be of the switched type unless otherwise stated. Light switches where
required shall be of the grid switch type with each switch being 'x' rated at 20 amps AC inductive.
When required or applicable, switch
service legend shall be engraved upon the switchplate or faceplate of the unit.
All switches shall be in accordance with BS 3676. Generally all wiring
accessories shall be of the recessed type and conduits, cable trunking etc.
concealed in the ceiling void or embedded in the structure.
Embedded, flush floor trunking shall be installed where indicated on the drawing. Such trunking
shall be heavy duty galvanised steel modular type allowing interchanging of cover plates/lids
with access boxes and flexibility for future modification. The design shall allow flush mounting of
the trunking in the floor screed and installation of carpets or floor tiles on top to provide a
uniform floor finish. Floor access boxes shall be provided with power socket outlets as
indicated. Access boxes shall also be provided where necessary to assist in the installation of
the cables such that no more than the equivalent of one 90° bend exists between access boxes.
All accessories such as junction/draw boxes, vertical to horizontal transitions, etc. shall also be
compatible with the trunking. The entire trunking system with the accessories shall be from one
manufacturer e.g. Dains/Egatube/MK or equivalent.
Access boxes shall be of a standard design such that service outlets may be installed in access
boxes at a later date and shall be designed to suit the floor screed depth with adjustable frame to
allow for irregularities in screed and floor finish.

4.0 TELEPHONE

The Telephone device is to be in all respects to the approval of local telecom authority. The
Contractor is responsible for ensuring this compliance is fulfilled.

Page 6 of 7
It shall consist of junction boxes, trunking, tray, conduits and outlets for all internal works and an
external network of underground duets, manholes, drawpits, etc. shall be under this contract.
Supply and installation all material, sockets, cover plates etc. and all wiring shall be included in
this contract.
The outlet plates shall be of a quality and finish matching the rest of the electrical accessories in
the respective areas.

5.0 DATA COMMUNICATION.

Contractor shall supply and install plug sockets for computers including all necessary conduits,
draw wires, junction boxes, etc. All required concealed ducting / conduiting system shall be
supplied and installed by the Contractor as per the requirement and drawings and to the
approval of the Engineer.

6.0 LOCAL PUSH BUTTON CONTROL STATIONS

The local push button control stations shall be of flame proof, weather proof, cast aluminium with
corrosion resistant cover screws, minimum IP 65 degree of protection and provided with suitable
fixing / mounting arrangement. All equipments shall be delivered with Certification of Conformity
according to CENELEC / BASEEFA. The contact rating for switch and push buttons shall be at
least for AC - 415V - 4A and DC - 24V - 4A. All push buttons shall be 2 Nos. + 2 NC spare
contacts.
Pump local push-button station shall be with Auto-OFF-manual selector switch, START-STOP
push-button.

7.0 JUNCTION BOXES

Junction boxes for hazardous areas shall be certified E Exd II B T4 by BASEEFA / CENELEC.
Junction boxes shall be protected according to IEC Class IP 65.
In general Material of flame proof junction boxes shall be of cast aluminium.
For all junction boxes used in hazardous area, a "Certificate of Conformity" according to
BASEEFA / CENELEC shall be delivered.

8.0 EARTHING
Refer Standard Earthing Specification for details.

Page 7 of 7