Specification For Uishers, Cabinets and Accessories: Exting

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

m WorleyParsons

resources & energy


EcoNomic$ :m
KUWAIT OIL COMPANY

SPECIFICATION FOR FIRE


EXTING UISHERS, CABINETS
AND ACCESSORIES

1 1C8972-00-AR-SPC-0016 Rev 0A

27, January 2O13

LOWER FARS HEAVY OIL DEVELOPMENT

WorleyParsons Canada Services Ltd.


Calgary Division Heavy Oil Business Unit
540 - 1 2'n Avenue SW
Galgary, Alberta
T2R OH4

Telephone: (403) 508-5300


Facsimile: (403)508-5301
www.worleyparsons.com
ABN 61 001 279812
@ Copyrlght 2010 WorleyParsons

ÉR
o
,Í zÞ
iltL
*
@ llUodeyFarsonr
relources & energy
€coNomicS .ffi
KUWAIT OIL COI¡|PANY
TOWER FARS HEAW OIL DEVELOPIJ|ENT
SPECIFICATION FOR FIRE EXTNGUISHERS, CABWEN¡ AND ACCESSORIES

SYNOPSIS
This document prêsents the Speciflcalion lor Fire Extlnguishers, Cabinels and Accessoriee for the Kuwait Oll
Company Lower Farc Heavy Oil Development Feed Project.

Dlsclalmer

This design guÍde Ís ænceptual ln nalurc and represents the work ol WorleyParsons perlormd to recogntzed
engineerÍng prlnclplss and practlces apprqñde Íor conceptual engineerlng work and the terms ot reference
provÍded by WorleyParsons' æntnctual Customer, Kuwait Oil Conpany (the'Customef). Thls dæument may
not be relÍed upon lor detailed tmplementatlon ot any othet putpose not sry¡llælly idantífred vdthln this
dæument Thß documanl is ænfrdentlal and preprcd sotety lor the use of the Customer. me contents oî thts
desígn gulde may not E used or relled upon by any party other than the Customer, and nelther
WorleyParsons, its sub ænsultants nor thelr respective employæs assume any liatÍllty tor any reason,
Includlng, but not limlted to, neglìgetrce, to any other party lor any lnîormatlon or npresentatton heß¡n, The
erteil ol any wananty or guuantae of tils úcument or the lnlormatlon cf/nta¡ned thereln in fdvour oî lhe
Customer ls llmlted to the warranty ot guanntee, iî ury, conta¡ned ln the contract between the Customer and
WorleyParsons.

DOC. NO. I 1C8972-00-AR-SPC-ool 6-RoA-dar:


NEV DESCflFTþN OâIGIll^TOR FEVIEW
WOFT,EVPARSOM¡
APPROVáL
DATÉ
CIIENÎ
APPnOV t DAIE

hrßl lor Oülñ | Flt'rhr G Efn¡r¡¡l *anm,


"-"Jton., ^
RGI&ad lü D.&ñ

r ,røt7r.ûl?

1 r ct 72{ûAFSFCÐ|6R0À(bG P¡e. 2 ol 1ô
4 qt/0¡r¿013 ER
o
,Í z. t"ll/"
Þ

d *
m WorleyParsonsresources & energy
tcoNomicS

KUWAIT OIL COMPANY


LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

CONTENTS
1.0 scoPE 5

1.1 General 5

2.0 SPECIFICATIONS, CODES AND STANDARDS 6

2.2 Definitions 6

2.3 Language 6

2.4 Related Specifications And Documents 6

3.0 GENERAL REQUIREMENTS............. I


3.1 EnvironmentalAndGeotechnical Data........... I
3.2 Quality Assurance I
3.3 Warranty 9

4.0 TECHNICAL REQUIREMENTS 10

4.1.2 Mounting Brackets 10

4.1.3 Fire Extinguisher Cabinets ....................10

4.2 lnstallation... .............12

5.0 OA/INSPECTION AND TESÏING 14

5.1 General 't4

5.2 Quality Assurance. 14

6.1 General 15

6.2 Delivery, Storage And Handling 15

Bago

I 1 C8972-00-AR-SPC-00 1 6-F0A.doc Page 3 of 16


4 03/06/2013
ÊR
o rtll,
tr ?
o Þ

*
M WorleyParsons resources & energ!¡
tcaNomic$ .ffi
KUWAIT OIL COMPANY
LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

7.0 SELLER DOCUMENTATION .......16

7.1 General 16

7.2

1 1 C8972-00-AR-SPC-001 6-R0A.doc Pags 4 of 16

4 03/06/2013 (,
,r{
þ
Þ WL

*
m WorleyParsons
resources & energy
ÊroNomicS m
KUWAIT OIL COMPANY
LOWER FARS HEAVY OIL DEVELOPMENT
SPEC¡FICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

1.0 scoPE

1.1 Ge¡¡eRrt
This specification covers the minimum general requirements for Fire Extinguishers, Cabinets, and
Accessories.

a Fire Extinguishers

a Mounting Brackets

a Fire Extinguisher Cabinets

Signage

Bass
I 1C8972-00-AF-SPC-00 1&R0A.doc Pags 5 ol 16
4 03/06/2013 Ê
(, tilL
,r Þ

*
M WorleyPar$ons resources & energy
tcoNomic$ ffi
KUWAIT OIL COMPANY
LOWER FARS HEAVY O¡L DEVELOPMENT
SPECIFICATTON FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

2.O SPECIFICATIONS, CODES AND STANDARDS

2.1 D¡scRrpaNctEs
The applicable revision, issue and addenda of all Standards and Specifications will be stated by the
Buyer in the purchase document. ln cases of any conflict between this specification and other purchase
documents, Seller shall call attention to the conflict and request an interpretation by the Buyer. The seller
shall not assume which requirements should govern.

lf a document is referenced in any of the purchase documents or its related documents but is not
available to the Seller, it shall be the responsibility of the Seller to obtain the document from the Buyer or
the appropriate Publisher.

This specification shall be used in conjunction with the related sections of KOC Specification
015-RH-1001; "Architectural Building Materials, Finishes and Fittings" and KOC Standard 3811022;
"General Specification for Civil Engineering and Building Works". Where conflicts occur between these
and other project documents, the more stringent requirement shall apply unless approved in writing by
KOC's designated representative. ln cases of conllicts where a more stringenl requirement is not
obvious or applicable, written request for clarification shall be submitted.

2.2 Dep¡¡¡rno¡¡s

"Company", "Owner", "EPC Contractor" or "Contractor"


(in the sense of prime contractor).

Seller "Vêndor", "Manufacturer", "Supplier" or "Contractor"


(in the sense of service supplier/subcontractor)

2.3 Ll¡¡curce
All documents requiring submission by this specification shall be provided in the English language.

2.4 Reunreo Speclr¡cartoNs Ano DocUMENTS


This section lists specifications and other documents that are applicable to this specification. Unless
otherwise specified herein, use the latest edition.

Bas
1 1 C8972-00-AH-SPC-001 6-H0A.doc PagB 6 ol 16
4 03/06/2013
Ê

qC, zÞ i"ilL
L¡-

*
m WorleyParsons resources & energy
EcoNomicS ffi
KUWAIT OIL COMPANY
LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR F¡RE EXTINGUISHERS, CABINETS AND ACCESSORIES

11 C8972-00-AR-SPC-0004 Specification for Painting - Buildings

11 C8972-00-AR-SPC-0020 Specification for Gypsum Board Assemblies

KOC Specification 01 5-RH-1 001 ............. Architectural Building Materials, Finishes and Fittings

KOC Standard3811022 General Specification for Civil Engineering and Building


Works

KOC-G-004 Standard for Packing, Marking and Documentation

KOC-G-007 Standard for Basic Design Data

KOC-L-009 Standard for Fire Protection Systems and Safety


Equipment
KOC-L-020.
Fire Protection in Non-Plant Buildings

2.5 COOES AruO STAruDARDS


This section lists codes and standards that are applicable to this specification. Unless otherwise specified
herein, use the latest edition at the date of the Award of Contract.

American Society ol Testlng Malerials (ASTM)


A 666 Standard Specification for Annealed or Cold-Worked Austenitic Steel, Strip,
Plate, and Flat Bar

A 1008 Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural,


High-Strength Low-Alloy, High-Strength Low-Alloy with lmproved Formability,
Solution hardened, and Baked Hardenable.

B 209 Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate'

B 221 Slandard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods,
Wire, profiles, and Tubes.

E 814 Standard Test method for Fire Tests of Through-Penetration Fire Stops.

Brltlsh Standardg lnstitute (BSl)


BS-EN-3 Standard for Portable Fire Extinguishers

Natlonal Fire Protection Associatlon (NFPA)


NFPA 1O Portable Fire Extinguishers

Côrnôralê Besê
1 1 C8972-00-AF-SPC-001 6-R0A.doc Page 7 of 16
4 03/06/201 3 L

{J eÊ þ4tL
'qî f,
Èr-
* þ
ú.
..L-
m WorleyPar$ons resources & energy
fcoNomic$ ffi;
KUWAIT OIL COMPANY
LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

154 Standard for Carbon Dioxide Fire Extinguishers

299 Standard for Dry Chemical Fire Extinguishers

2129 Standard for Halocarbon Fire Extinguishers

ti

1 1 C8972-00-AR-SPC-001 6RoA.doc Page I ol 16


4 03/06/20't3
o I.

tIùL

*
m WorleyParsons resources & energy
EcoNomic$ ffi
KUWAIT OIL COMPANY
LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

3.0 GENERAL REQUIREMENTS

3.1 Er,¡vlnoruuENTAL Ano GeorEcHNlcAL Dlrl


Environmental and geotechnical data is defined by document KOC-G-007, Standard for Basic Design
Data.

3.2 Qunlrrv AssuRnruce


a) Fabrication, marking and labeling of f¡re extinguishers to comply with KOC-L-009, BS-EN-3
and NFPA 10, "Portable Fire Extinguishers."

b) Obtain KOC controlling team and local authorities' approval; having jurisdiction over this
project, prior to ordering, supply of the products.

c) Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent
testing agency, UL, FM, LPC, etc., acceptable to author¡ties having jurisdiction.

d) Coordinate type and capacity of fire extinguishers with fire protection cabinets to ensure fit
and function;

3.3 WnRnlrurv
Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace fire
extinguishers that fail in materials or workmanship within a specified warranty period, as approved by
KOC Controlling team and local authorities having jurisdiction over the works.

Failures include, but are not limited to, the following:

a) Failure of hydrostatic test according to NFPA 10, BS-EN-3 and KOC-L-009

b) Faulty operation of valves or release levers

Warranty Period: Six years from date of Substantial Completion'

C8972-00-AR-SPC-001 6-R0A.doc Pago 9 of 16


1'l
ÉR
4 03/06/20 1 3
(,
f Þ
þuL

*
M WorleyParson$ ËcoNomic$ .m:
resources & ene¡gy

KUWAIT OIL COMPANY


LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

4.0 TECHNICAL REQUIREMENTS

4.1 Pnooucts

4.1.1 Portable, Hand-Carried Fire Extinguishers


a) The vendors shall be from the list of company approved manufacturers / vendors.
b) Marking / labeling shall be as per KOC-L-009, BS-EN-3, NFPA 10 "Portable Fire
Extinguishers" and other relevant standards.

c) Multipurpose Dry-Chemicaltype shall be 9 kg capacity, UL-rated nominal capacity, with


mono-ammonium phosphate-based dry chemical powder from KOC approved vendor list, in
manufacturer's standard enameled container, as per KOC-L-009 and approved by KOC
Controlling team and Fire team.

d) CO2 fire extinguishers (FE-2) shall be Skg and 2 kg capacity'

e) Halocarbon type fire extinguishers (FE-3) shall be deleted and replaced by CO2 type (FE-2).

f) Water type (9 ltr. CO2 gas cartridge operated) fire extinguishers required for office areas are
not mentioned in the specifications.

g) 63 kg. Wheeled DPC fire extinguishers required for oil installations, transformers area etc.
are not defined in the specification.

4.1.2 Mounting Brackets


a) Mounting Brackets: Manufacturer's standard galvanized steel, designed to secure fire
extinguisher to wall or structure, of sizes required for types and capacities of fire
extinguishers indicated, with plated or red baked-enamelfinish.

b) ldentification: Lettering complying with authorities having jurisdiction for letter style, size,
spacing, and location. ldentify bracket-mounted fire extinguishers with the words "FIRE
ExlNcu¡sHER" in red letter decals applied to mounting surface.

c) Orientation: Vertical.

4.1.3 Fire Extingu¡sher Gabinets


a) Stainless-Steel Sheet: ASTM A 666, Type 304.
b) Cold-Rolled Steelsheet: ASTM A 1008/A 1008M, CommercialSteel(CS), Type B.

I I C8972-00-AR-SPC-00 1 6-R0A.doc Pags l0 ot 16

4 03/06/2013

illL
m WorleyParsons [coNomicS :m
resources & energy

KUWAIT OIL COMPANY


LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

c) Cabinet Type: Suitable for fire extinguisher.


d) Products: Subject to compliance with requirements, available products that may be
incorporated ¡nto the work include, but are not limited to, the following:

- Fire End and Croker Corporation

- J.L. lndustries, lnc., a division of Activar Construction Products Group

Kidde-Residential and Commercial Division, Subsidiary of Kidde plc

- Larsen's Manufacturing Company

- Modern Metal Products, Division of Technico lnc.

Moon-American

- Potter Roemer LLC

- Watrous Division, American Specialties, lnc.

e) Cabinet Construction: 1-hour fire rated.


f) Fire-Rated Cabinets: Construct f ire-rated cabinets with double walls fabricated from 1.'l mm
thick, cold-rolled steel sheet lined with minimum 16 mm thick, fire-barrier material. Provide
factory-drilled mounting holes.

g) Cabinet Material: Stainless-steel sheet.


h) Semi-Recessed Cabinet: Cabinet box partially recessed in walls of suflicient depth to suit
style of trim indicated; with one-piece combination trim and perimeter door frame overlapping
surrounding wall surface with exposed trim face and wall return at outer edge (backbend).
Provide where walls are of insufficient depth for recessed cabinets but are of sufficient depth
to accommodate semi-recessed cabinet installation.

- Square-Edge Trim: 32 mm to 38 mm backbend depth

- Rolled-Edge Trim: 102 mm backbend depth

i) Surface-Mounted Cabinet: Cabinet box fully exposed and mounted directly on wall with no
trim. Provide where walls are of insufficient depth for semi-recessed cabinet installation.
j) Cabinet Trim Material: Stainless-steel sheet.

k) Door Material: Stainless-steel sheet.

l) Door Style: Flush opaque panel, frameless, with no exposed hinges.

C8972-00-AR-SPC-001 6-RoA.doc Page11of16


1 1

e
4 03/06/2013

o
,f a.
w
Þ
o
*
ffi WorleyParsons ËcoNomic$ :m
resources & energy

KUWAIT OIL COMPANY


LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

m) Door Hardware: Manufacturer's standard door-operating hardware of proper type for cabinet
type, trim style, and door material and style indicated.

n) Accessories:

- Mounting Bracket: Manufacturer's standard steel, designed to secure fire extinguisher


to fire protection cabinet, of sizes required for types and capacities of fire
extinguishers indicated, with plated or baked-enamel finish.

Door Lock: Cam lock that allows door to be opened during emergency by pulling
, sharply on door handle.

- ldentification: ldentification labels shall be in bilingual (English and Arabic) and as per
KOC-L-009. Locate as directed by Buyer.
. ldentify lire extinguisher in fire protection cabinet with the words "FIRE
ExlNGUtsHER" in both English and Arabic.

. Location: Applied to cabinet door


. Application Process: Pressure-sensitive vinyl letters
. Lettering Colour: Red
. Orientation: Vertical

o) Finishes:

- Stainless Steel: No. 6 (Polished, Soft Satin)

4.2 lnsrallltlo¡¡
Examine fire extinguishers for proper charging and tagging.

Remove and replace damaged, defective, or undercharged fire extinguishers.

lnstallfire extinguishers and mounting brackets in locations indicated and in compliance with
requirements of authorities having jurisdiction.

a) Mounting Brackets: 1372 mm above finished floor to top of fire extinguisher.

b) Mounting Brackets: Fasten mounting brackets to surfaces, square and plumb, at locations
indicated.

lnstalt fire extinguisher cabinets in locations indicated and in compliance with requirements of authorities
having jurisdiction.
Basâ

1 1 C8972-00-AR-SPC"00'l 6-RoA.doc Page 12 of 16

4 03/06/201 3

W
@ WorleyParsons
resources & energy
€coNomicË ffi
KUWAIT OIL COMPANV
LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

a) Examine walls and partitions for suitable framing depth and blocking where semi-recessed
cabinets will be installed and prepare recesses as required by type and size of cabinet and
trim style.

b) lnstall fire protection cabinets in locations and at mounting heights indicated or, if not
indicated, at heights acceptable to authorities having jurisdiction.

c) Fire Protection Cabinets: Fasten cabinets to structure, square and plumb.

d) ldentification: Apply vinyl lettering at locations indicated.

e) Adjust fire protection cabinet doors to operate easily without binding. Verify that integral
locking devices operate properly.

f) Replace fire protection cabinets that have been damaged or have deteriorated beyond
successful repair by finish touch-up or si;nilar minor repair procedures.

I 1 C8972-00-AR-SPC-001 6-R0A.doc Page l3 ol 16


4 03/06/2013 ER
o l-llt
..r

v *
m WorleyParsons resources & energy
fcoNomic$ m:
KUWAIT OIL COMPANY
LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

5.0 QA/INSPECTION AND TESTING

5.1 Ge¡reRr¡-
lnspection and testing of equipment and materials shall be carried out by the Seller in accordance with
the data sheets, related specification, and the Buyer's lnspection and Test Plan. A set of each type of fire
extinguisher and cabinet shall be submitted to KOC Fire Team for inspection and approval before
installation at site.

5.2 Qual¡rY AssuRn¡¡ce


The following are additional requirements pertaining to inspection and testing as applicable to this
specification:

a) NFPA / BS-EN-3 / KOC-L-009 Compliance: Fabricate and labelfire extinguishers to comply


with NFPA 10, "Portable Fire Extinguishers"

b) Fire Extinguishers: Listed and labeled for type, rating, and classification by an independent
testing agency acceptable to authorities having jurisdiction (UL).

c) Coordinate type and capacity of fire extinguishers with fire protection cabinets to ensure fit
and function.

d) Fire-Rated, Fire Protection Cabinets: Listed and labeled to comply with requirements in
ASTM E 814 for fire-resistance rating of walls where they are installed.

e) Coordinate size of fire protection cabinets to ensure that type and capacity of fire
extinguishers indicated are accommodated.

f) Coordinate sizes and locations of fire protection cabinets with wall depths.

1 1 C8972-00-AR-SPC-001 6.R0A.doc Page 14 of 16


4 03/06/2013
ÊR
o l"w
'Ío
ç
WorleyParsons €coNomic$
resources & energy

KUWAIT OIL COMPANY


LOWER FARS HEAVY OIL DEVELOPMENT
SPECIFICATION FOR FIRE EXTINGUISHERS, CABINETS AND ACCESSORIES

6.0 PACKING, SHIPPING AND DELIVERY

6.1 Genennl
The minimum requirements to be applied at a Seller's shop to protect materials from deterioration during
shipment, storage and construction shall be as defined by document KOC-G-004, Standard for Packing,
Marking and Documentation.

The duration for the required protection, be it temporary, short-term or long-term, shall be defined at the
Award of Contract.

6.2 DeuveRv, StonacE AND Hn¡¡ollt¡c


Do nol deliver equipment and materials until buildings are enclosed and weatherproofed, wel work in
space is completed and nominally dry, work above ceilings is complete, and ambient conditions of
temperature and humidity will be continuously maintained at values near those indicated for final
occupancy.

Materials shall be delivered in the manufacturer's original unopened, protective packaging, with intact and
legible manufacturer's labels indicating brand name, pattern, size, thickness, and fire rating.

Materials shall be stored in their original protective packaging to prevent soiling, wetting, or other damage.

I 1 C8972-00-AB-SPC-00 1ÈR0A.d0c Pags l5 of 16


4 03/06i2013 (,
,r Þ I,ll/-

*
WorleyParsons
resources & energy
EcoNomic$ ffi
KUWAITOIL COMPANY
LOWER FARS HEAVY OIL DEVELOPMENT
SPECTFTCATION FOR FIRE EXTINGUISHEFS, CABINETS AND ACCESSORIES

7.0 SELLERDOCUMENTATION

7.1 Ge¡¡eRnt
The general seller's documentation requirements shall be defined by the Buyer during the Award of
Contract.

7.2 Susli ¡rrrls


The following are submittal requirements pertaining to seller documentation applicable to this
specification:

a) Product Data: For each type of product indicated

b) Operation and maintenance data


c) Warranty: Sample of special warranty.
d) Shop Drawings: For fire protect¡on cabinets, including plans, elevations, sections, details,
and attachments to other work

e) Samples: For each exposed product and for each colour and texture specified