Professional Documents
Culture Documents
Lect 9 FRP Shear Design1
Lect 9 FRP Shear Design1
rebars.
3 4
FRP Shear Design FRP Shear Design
FRP Shear Design (Cont’d) FRP Shear Design (Cont’d)
¾ In LRFD method/approach, the factored nominal shear must ¾ The ACI code 440.1R-15:8.2a provides equation to compute
be more than the factored ultimate moment, i.e. Vc in both FPS and SI systems
ϕVn > Vu (for FPS units) (1)
¾ The nominal shear capacity Vn of an FRP beam is give by (for SI units)
(ACI code 440.1R-15).
Vn = Vc + Vf where k is neutral axis depth factor, bw is width of the beam
where Vc is the shear capacity of concrete and Vf is the shear web.
capacity of FRP stirrups.
(2)
¾ If Vu < 0.5ϕVc, then no shear reinforcement required.
¾ If Vu > 0.5ϕVc, then provide minimum amount of shear ¾ The strength reduction factor ϕ for shear is taken as 0.75.
reinforcement.
¾ If Vu > ϕVc, then design for additional reinforcement
7 8
FRP Shear Design FRP Shear Design
Limits on FRP Shear Design Limits on FRP Shear Design (Cont’d)
¾ The maximum spacing permitted by the ACI code is d/2 or ¾ To prevent shear crushing failure, check the shear capacity
24 in. (This condition ensures that shear crack at 45° must be of concrete
intercepted by at least one stirrup). (6)
¾ The tail length of 90° hook of stirrups should be at least
12db.
¾ All stirrups hook must be anchored in compression zone.
Why ?
¾ The minimum amount of shear reinforcement is required if
Vu > 0.5ϕVc (in order to prevent brittle shear failure) as
given by ACI 440.1R-15:8.2.2.
ೢ
(for FPS units) (5)
ೡ
Step 3
¾ Check if additional shear reinforcement is required.
If Vu > 0.5ϕVc, then provide minimum amount of shear
reinforcement as defined in Eq. (5) on Slide # 8).
= 4.18 kips
15 16
Sample Problem Sample Problem
19 20
Sample Problem FRP Punching Shear Design
dL = 6.31 in.
23 24
Sample Problem Sample Problem
OK
27 28
Case Study Case Study
Case Study: Punching Shear Failure Case Study: Punching Shear Failure
¾ Collapse of 2000 Commonwealth Avenue, Boston ¾ Collapse of 2000 Commonwealth Avenue, Boston (Cont’d)
A 16-story apartment building collapsed under The design (28-day) strength of 3,000 psi.
construction. At the time of the failure, 47 days after casting, the
A cast-in-place reinforced concrete flat slab. concrete strength was less than 3,000 psi.
The punching shear was believed to be the cause of the concrete at the
collapse. point of the collapse had been cast on December 3 or 9,
failure took place in three phases: 1970.
• The punching shear failure in the main roof; The concrete strength was at 1,600 and 1,900 psi at 47
• Collapse of the roof slab; and 53 days, respectively.
• The progressive collapse of remaining structure The slab thickness did not meet code requirements at the
• The mishap happened during the construction in front point of failure against the punching shear.
of the workers: The construction loading was limited to 30 psf but actual
• ‘‘I can’t believe my eyes. I see this slab coming down load was 130 psf.
around the column.’’