07KP95
CI520
F R
07KP95
1 Fixing screws above and below
CI520
for fastening on the earthed mounting surface. With this
4 F R
fastening the earthing for the coupler is also performed.
7
2 Supply voltage 24 V DC (red = L+, blue = M)
5
3 Networking interface for the AC31 basic unit
(e.g. 07 KT 94)
4 Communication interface CI520
6
5 Serial interface for modem coupling
1.5.1 Application examples for AF100 coupling • The connection of the communication processor
07 KP 95 to the modem(s).
with modem, coupler 07 KP 95 and basic
unit • Looping through the supply voltage (24 V DC) from
the 07 KT 94 to the 07 KP 95 R101
The following figures show two application examples for
single-channel and redundant configuration. Attention • Earthing the switch cabinet mains sockets
must be paid to the following in detail:
• Using the AF100 bus with coaxial cable
CI520
F R
07 KT 94
Advant Controller 31
Basic Unit
AF100
3
Switch-gear cabinet
230 VAC / 24 VDC
Hardware 07 KP 95 R101
earthing
+
L1 L+
N M
–
PE
Fig. 3: Application example of an AF100 coupling with modem, coupler and basic unit (typical switch-gear cabinet configuration)
8.6 SB512 TC625 SB512 TC625 07KP95
CI520
F R
Hardware 07 KP 95 R101
07 KT 94
Advant Controller 31
Basic Unit
AF100 AF100
4
Fig. 4: Application example of an AF100 coupling with modems, coupler and basic unit, redundant configuration (typical switch-gear cabinet configuration)
1.5.2 Connection of the supply voltage 24 V DC Mounting the communication processor at the net-
working interface
As shown in Fig. 3 and Fig. 4, the supply voltage for the
07 KP 95 is looped through from the AC31 basic unit (red 1. Detach the cover on the basic unit (e.g. 07 KT 94)
wire = L+, blue wire = M). from the networking interface.
1.5.3 Networking interface 2. Plug the socket strip of the 40-pole ribbon cable se-
cured to the 07 KP 95 R101 onto the networking con-
The networking interface, a special parallel interface, al-
nector of the AC31 basic unit.
lows the 07 KP 95 communication processor to be con-
nected to AC31 basic units 07 KT 93 and 07 KT 94. The 3. Slide both units together.
housing of the communication processor is connected to
the housing of the ABB Procontic basic unit by a snap-fit 4. Slide the replacement cover provided with the 07 KP 95
connection. The electrical connection is via a 40-pole rib- unit with its cut-out onto the networking interface.
bon cable with socket connector, soldered onto the 1.5.4 Measures for RFI
07 KP 95 R101 side.
(Radio Frequency Interference)
Note: Attachment and disconnection of units on the net- Installation in a metallic switch-gear cabinet
working interface may only be performed when all supply
voltages are switched off. Mains filters
TC625 07KP95
CI520
F R
Bore hole distance 163
178
Advant Controller 31
Basic Unit
AF100
46 46
ca. 375 inclusive basic unit
All dimensions in mm.
The device is 170 mm deep without CI520 inserted. The depth is 191 mm with CI520 inserted. There must be
enough space for interface connectors and cables.
Further literature
System description Advant Controller 31, English 1SAC 1316 99 R0201
Software
907 KP 95 R0102, Documentation, CE library GJP5 2065 00 R0102 (German documentation)
GJP5 2066 00 R0102 (English documentation)
Additional components (see also Figures 3 and 4)
CI520 Communication interface
TC625 AF100 modem for coaxial cable (contains interface cable CI520 <> TC625)
TC512 AF100 modem for twisted pair (contains interface cable CI520 <> TC512)
SB512 Power supply unit for modem
These components can be ordered under the following address:
ABB Industrietechnik AG
Abteilung IND / OM
Dudenstraße 4446
D-68167 Mannheim
Tel.: +49 621 381 1847 (Mr. Bräuler)
Additional literature
Users Guide Advant Fieldbus 100 Document 3BSE 000 506R0101 (English)
Installation Rules Document 3BSE 009 178R0001 (English)