This document summarizes the test results of protective relays. It reports the operating values and times for over current, under voltage, over voltage, and current unbalance protection settings. It also provides the specifications and test results of the master trip relay. All results were found to be within the permissible tolerance ranges specified in RDSO standards.
This document summarizes the test results of protective relays. It reports the operating values and times for over current, under voltage, over voltage, and current unbalance protection settings. It also provides the specifications and test results of the master trip relay. All results were found to be within the permissible tolerance ranges specified in RDSO standards.
This document summarizes the test results of protective relays. It reports the operating values and times for over current, under voltage, over voltage, and current unbalance protection settings. It also provides the specifications and test results of the master trip relay. All results were found to be within the permissible tolerance ranges specified in RDSO standards.
Aux. Voltage: 110 VDC CT-1: 5Amp. CT-2: 1Amp * Operating Value Test Operating Value Test for I1> IDMT: I1>1 Pickup Operating Value in Tolerance value in setting Amp Amp 20% = 1.0A 1.05 A 0.95-1.05 80% = 4.0A 4.16 A 3.80-4.20 100% = 5.0A 5.20 A 4.75-5.25 Observation: The error in relay operating value was observed within ± 5%.
Operating Value Test for Current Unbalance:
ICU1> Setting Operating Value in Tolerance value in Amp Amp 5% = 0.05A 0.051 A 0.0475-0.0525 50% = 0.50A 0.515 A 0.475 – 0.525 100% = 1.00A 1.029 A 0.90 – 1.050 Observation: The error in relay operating value was observed within ± 5%. * Operating Time Measuring Test: Time Testing for IDMT: Setting: I1> = 50%, TMS = 1.0 I(I/ I1>1) Expected Time Observed Tolerance in from curve Time in sec sec 5A(2N) 10.03s 10.09 9.528 – 10.531 12.5A(5N) 4.28s 4.31 4.066 – 4.494 25.0(10N) 2.97s 3.00 2.820 – 3.110 Observation: The Relay operating time found within +/-5%
Time Test for Current Unbalance:
ICU1> Setting: = 20%=0.40A Set Injected Observed Time Tolerance(Sec) Time(Sec) current (Sec) 0.100 0.40A 0.103 0.095 – 0.105 0.500 0.40A 0.514 0.475 – 0.525 1.000 0.40A 1.02 0.950 – 1.050 Observation: The Relay operating time found within +/-5%. SSE/RC/NDLS SSE/RE/JP M/S L&T M/S ASHIDA (CAPACITAR BANK)
As Per RDSO Specs: TI/SPC/PSI/PROTCT/6071
TYPE: A26R
Sr. No.: 17LA26R0013. Date: 05/12/2018
Aux. Voltage: 110VDC PT: 27.5/110VAC
* Operating Value Test
Under Voltage Operating Value Test for (UV): UV Pickup Operating Value in Tolerance value in setting Volt Volt 20% = 22.0V 22.39 V 20.90 – 23.10 55% = 60.5V 59.64 V 57.48 – 63.35 90% = 99.0V 96.79 V 94.05 – 103.95 Observation: The error in relay operating value was observed within ± 5%.
* Over Voltage Operating Value Test for (OV):
OV Pickup Operating Value in Tolerance value in setting Volt Volt 100% = 110.0V 112.32 V 104.50 – 115.50 150% = 165.0V 169.52 V 156.75 – 173.25 200% = 220.0V 229.25 V 209.00 – 231.00 Observation: The error in relay operating value was observed within ± 5%.
* Operating Time Measuring Test:
UV Operating Time Testing for IDMT: AT TMS 1 Initially keep voltage 105 Volts SET UV Applied Expected Observed Tolerance in TRIP (%) voltage Time (Sec) Time (Sec) Sec 20% 80%=17.60V 14.10 14.19 13.40 – 14.81 55% 40%= 24.20V 6.810 6.91 6.47 – 7.15 90% 0%= 0.00V 5.000 5.06 4.75 – 5.25 Observation: The Relay operating time found within +/-5%.
SSE/RC/NDLS SSE/RE/JP M/S L&T M/S ASHIDA
* UV Operating Time Testing for DT: SET UV TRIP=90%; initially keep voltage 105 Volts Set Observed Time Tolerance(Sec) Applied voltage Time(Sec) (Sec) 0.10 0%= 0.00V 0.104 0.095 – 0.105 1.00 0%= 0.00V 1.01 0.950 – 1.050 10.0 0%= 0.00V 10.11 9.50 – 10.50 Observation: The Relay operating time found within +/-5%. OV Operating Time Testing for IDMT: AT TMS 1 Initially keep voltage 0 Volts SET OV TRIP Applied Expected Observed Tolerance in (%) voltage Time (Sec) Time (Sec) Sec 100% 200%=220.0V 3.500 3.51 3.33 – 3.68 150% 160%= 264.0V 5.833 5.85 5.54 – 6.12 200% 120%= 264.0V 17.500 17.33 16.63 – 18.38 Observation: The Relay operating time found within +/-5%.
OV Operating Time Testing for DT:
SET OV TRIP=100%; initially keep voltage 105 Volts Set Observed Time Tolerance(Sec) Applied voltage Time(Sec) (Sec) 0.10 165.0V 0.102 0.095 – 0.105 1.00 165.0V 1.01 0.950 – 1.050 10.0 165.0V 10.11 9.50 – 10.50 Observation: The Relay operating time found within +/-5%.