Changing the Unity ID Internet Address

These instructions have not been officially validated by GE

Note:
Laptops equipped with Windows 7 no longer have HyperTerminal. To install you
will need to find two files from your XP installation and copy them over to
Windows 7.

The two files you will need are hypertrm.dll and hypertrm.exe. Simply copy
those files into any directory on your machine and it will work. You should be
able to find hypertrm.exe in C:\Program Files\Windows NT and hypertrm.dll in
C:\Windows\System32.

If you have the Windows XP CD, you should be able to find both of these files in
the i386 directory on the CD.

Also please note that GE laptops no longer come with an RS232 serial port.
Using the ATEN UC-232A USB-to-serial adapter works fine. This is the one
recommended for the CARESCAPE Monitor B850/B650 and the S/5 Collect
software.

Short instructions:

1. Connect power cord to Unity ID and power outlet. Keep power switch turned off.
Make sure all device interface cables are unplugged from Unity ID.
2. Connect serial cable to laptop and Unity ID. Serial cable is a 9 pin female/male.
3. Start ‘HyperTerminal’ program (Start  All Programs  Accessories 
Communications  HyperTerminal):

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

4. Enter a name and chose an icon for the connection. Press ‘Enter’ or select ‘OK’
5. In the Connect to: menu, select the communication port on your laptop. Typically
COM1.
6. In the Port Settings menu, select the following:

7. Press ‘Enter’ or select ‘OK’

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

8. Press and hold the ‘B’ key while turning on the Unity ID using the green power
switch.
9. Release the ‘B’ key when the following menu appears:

10. Wait until the following menu appears (may take about minute):

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

11. Enter ‘2’ to: Change Internet Address


(NOTE: DO NOT select option #1: Change Ethernet Address)

12. Enter ‘2’ for Yes


13. Set the Unity ID’s Internet address as follows:
a. The DASH requires the 1st octet be set to 126 (factory preset)
b. The Solar requires the 1st octet be set to 10
c. The B850 requires the:
i. 1st octet be set to 192
ii. 2nd octet be set to 168
iii. 3rd octet be set to 253
iv. 4th octet is X, where X is not 1 and not the same as any of the other
devices on the M-Port. 
14. Message “Change was successful. System will now restart” is displayed.
15. Cycle power to the Unity ID and wait until ‘Main flash test passed.” message
appears.
16. Wait another 10 seconds before proceeding to next step.
17. Type ‘service’ and press Enter to access the Service Menu. Note: Newer Unity
ID’s display the asterisk (*) symbol for each character. Older models do not
display any characters while typing.
18. Select the ‘Location Menu’
19. Type the unit name and press Enter
20. Type the bed name and press Enter

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

21. Verify the unit name and bed name now appear in the parentheses next to the
Location Menu. Note: The system automatically places a plus (+) sign after the
bed name.
22. Turn off Unity ID power and disconnect serial cable

Detailed instructions (from Service Manual):

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

NOTE: DO NOT select option #1: Change Ethernet Address

*** INTERNAL GE USE ONLY – Not for Distribution ***


Changing the Unity ID Internet Address

1. Enter ‘2’ to: Change Internet Address


2. Enter ‘2’ for Yes
3. Enter first octet (either 10 for Solar or 126 for Dash) and
press ‘Enter’
4. Press ‘Enter’ three more times to keep the remaining 3 octets
the same.
5. Message “Change was successful. System will now restart” is
displayed.
6. Turn off Unity ID power and disconnect serial cable