SPLIT CASE FIRE PUMPS

FAIRBANKS NIJHUIS™ 900 SERIES


Split Case Fire Pumps

Horizontal split case pumps are the most common type of fire
pump. These pumps are specifically designed and tested for
fire service applications where reliability of performance is of
vital importance. Split case pumps are characterized by:

• Easy access to all working parts;

• Rugged construction;

• Liberal water passages; and

• Efficient operation.

Split case fire pumps are specified when the source of water
is located above the surface of the ground and provides a
positive suction pressure to the pump at any performance point.
Single-stage or multistage pumps are available dependent upon
discharge pressure requirements.
In addition to horizontal split case pumps, Fairbanks Nijhuis
Fairbanks Nijhuis split case fire pumps are built per the also offers split case performance in a vertical format. Vertical
rigid standards of NFPA 20 and are listed by Underwriters fire pumps provide distinct advantages over horizontal pump
Laboratories (UL) and approved by Factory Mutual (FM). constructions.

• Less floor space is required.


Available in a broad range of operating pressures and flows
from a minimum of 250 GPM, Fairbanks Nijhuis split case • In-line piping arrangement allows piping in any direction
pumps can be driven by either an electric motor or diesel in most cases.
engine. Fairbanks Nijhuis’ UL-Listed, FM-Approved fire pump
• Elevated motor protects against potential flooding if the
packages also include the system controller, with a full range
pump station is in a low area.
of options and accessories available to complete the NFPA-
compliant fire pump package. • Components are register-fitted to prevent misalignment.

2
SPLIT CASE FIRE PUMPS

1
Pump Features
7
2
8 15 16
14
17
3 9 13

10
5 11 12
6 18
VERTICAL HORIZONTAL
SPLIT CASE SPLIT CASE

1. Computer Machined 8. Internal Water Seal Passages 14. Split Case Design
major components with 360 degree registered between volute and stuffing box cannot simplifies disassembly. The suction and
fits to assure concentricity of parts. be damaged. discharge piping and shaft alignment are
not disturbed.
2. Integral Bearing Arms 9. Interwoven, Graphite
eliminate bearing misalignment and Impregnated T.F.E. 15. O-Ring Sealed Shaft Sleeves
simplify maintenance. prevent corrosion of the shaft. This eliminates
diagonally cut packing rings seal
the need for stainless steel shafts.
the pump shaft.
3. Enclosed Impeller Design
provides high efficiency and performance. 10. Stuffing Boxes 16. Case Wearing Rings
and throttle bushings protect the
are extra deep for proper sealing. Split packing
casing from wear and are easily and
4. Dynamically Balanced Impeller glands simplify packing maintenance.
inexpensively replaced.
is keyed to the shaft and secured by adjustable
shaft sleeves. 11. Double Row Thrust 17. Bronze Shaft Sleeve
ball bearing.
prevents shaft wear, is slip fit over the shaft,
5. Double Suction Impeller keylocked, and extends the entire length
balances hydraulic thrust loads. 12. Grease Seals of the seal box.
and nonsparking neoprene rotating slingers
6. Cast Iron Drip Rim Base protect both bearings during pump operation
18. Certified Performance Test
directs condensation and any stuffing box and washdown.
leakage to drain. with Positive Suction Pressure
is provided for each fire pump for customer
13. Bearings approval. Pumps are also hydrostatically tested
7. Short Bearing Span selected for 50,000 hour minimum life
per NFPA 20 at no less than 250 psi.
holds shaft deflection to .002" at face of at maximum load. Average bearing life
stuffing box at maximum load. 5 x minimum.

www.FairbanksNijhuis.com 3
Fire Pump Feature Selector
Standard Optional
• Bronze fitted pump construction • Ductile iron casings (available in selected 1800 and 1900 models)

• Bronze shaft sleeves • Some models available in 316 SST, duplex and super duplex

• Bronze case wearing rings • Right- or left-hand rotation

• Dynamically balanced impellers • Impeller wearing rings

• Stainless steel impeller key • Stainless steel shafts

• Carbon steel shaft • Double row ball bearings on inboard side

• Corrosion-resistant lantern rings* • External bypass line from casing to stuffing boxes
(optional on Model 1800s and 1900s, standard on Model 2800s and 5800s)
• Bronze stuffing box bushings
• Formed steel drip-rim base (horizontal electric driven units only)
• Bronze or stainless steel glands
• 15' Suction lift test to verify performance at 150% of rated flow
• Interwoven graphite-impregnated T.F.E. packing rings
• Available accessories include valves, headers, main relief valves, increasers and
• Cast integral bearing arms (most models) reducers, waste cones, and more.
• Regreaseable ball bearings

• Double row thrust bearing (outboard side)

• Upper casing lifting lugs

• Water slingers and grease seals

• Hydrostatic and Certified Performance test**

• Coupling guard
VERTICAL PUMPS PROVIDE
SUCTION IN-LINE PIPING IN ANY DIRECTION SUCTION
• Suction and discharge gauges with shutoff cocks STANDARD
(ALSO AVAILABLE RIGHT- OR LEFT-HAND)
OPTIONAL
RIGHT-HAND ROTATION LEFT-HAND ROTATION
(TOP VIEW HORIZONTAL PUMP) (TOP VIEW HORIZONTAL PUMP)

• Automatic air release valve


* Standard on Model 2800s and 5800s; furnished when suction pressure is below 40 psi on Model 1800s and 1900s.
• Casing relief valve (electric driven units only) ** Test is performed with positive suction pressure.
LIC
IN
AU

ST
IT
DR

UT
HY

19 17

www.FairbanksNijhuis.com

800 AIRPORT ROAD, NORTH AURORA, ILLINOIS 60542 USA


PARALLELWEG 4, 7102 DE, WINTERSWIJK, THE NETHERLANDS
GULF VALVE, HAMRIYA FREE ZONE, PO BOX 41721, SHARJAH, UAE
NO. 10 JIA YE ROAD BIN HU DISTRICT, WUXI CITY, JIANG SU PROVINCE, CHINA 214124

Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
FMF-02-1048 04/01/16 © 2016 Pentair Ltd. All Rights Reserved.
Customer : Engie Services Perú Pump Performance Curve
S.A. Encompass 2.0 - 20.3.5
Project name : 750 195 SC D H.
INDIGO
300

270

240

210
14.94 in

180
Head - psi

150

120

90

60

30

240

180
Power - hp

Power

120

60

0
0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400

Flow - USgpm

Item number : 001 Size : 5"-1823AF


Service : Stages :1
Quantity :1 Driver type : Engine
Quote number : 1251003 Frequency : 0 Hz
Date last saved : 08 Oct 2020 11:52 AM Speed, rated : 2600 rpm
Flow, rated : 750.0 USgpm Based on curve number : 481-5x6x15A-2600
Differential head / : 195.0 psi Efficiency : 59.58 %
pressure, rated Max working pressure, allowable : 370.0 psi.g
Flange rating (suction / : 125/250 Shutoffhead, Typical : 216.8 psi
discharge)
Max suction pressure, allowable : 153.2 psi.g
Secondary Point (150% : 1,125.0 USgpm
of rated flow) Suction pressure, max (user : 0.00 psi.g
specified)
Secondary Point (65% of : 126.7 psi
rated head) Pump shutoff w/ suction pressure : 216.8 psi.g

Max Shutoff per NFPA : 273.0 psi Power driver, minimum : 164 hp

Curve performance is typical. Contact factory for guaranteed performance curve.


Encompass 2.0 - 20.3.5

General Arrangement
Pump Data
Series Horizontal Splitcase
Model 5" 1823AF
Size 5x6x15
Flow 750.0 USgpm
Rated Pressure 195.0 psi.g
RPM 2600 rpm
Rotation Right handed
Liquid Type Water
Discharge Size 5.00 in
Suction Size 6.00 in
Impeller Diameter 15.00 in
Connection Type Flanged
Base Type Structural steel base
- -
Pump Materials of Construction
Pump Bronze fitted with Ductile Iron casing
Shaft Carbon Steel AISI C1046
Engine Data
Engine Model JU6H-UF52
Power Rated 210 hp
Power Available 210 hp
Speed 2600 rpm
Tier T1
Manufacturer Clarke
Cooling Type Heat exchanger
Heater Voltage 230 Volt
Muffler Type Commercial Grade, 5" (Qty 1)
Exhaust Connection Flanged
Battery Type Lead acid
Battery Voltage 12 Volt DC
Site Information
EY EL EX DSL CP W EW EW1 EW2 EZ YY X
Elevation 300.0 ft
45.40 48.00 25.60 15.60 28.50 16.00 37.10 16.40 20.70 4.90 15.00 13.25
Temperature 77.00 deg F
S Z HD HG HP HF1 HY HB HP1 HE HA Estimated Weights
6.25 6.25 20.00 6.00 5.00 39.00 14.00 88.00 1.00 30.00 32.00 Pump 1,000.0 lb
Driver 2,050.0 lb
NOTES: Quote Information
Not for construction, installation, or application purposes unless certified. Customer Engie Services Perú S.A.
All dimensions are in inches Customer Quote 1251003
Dimensions may vary ± .38" (10mm) due to normal manufacturing tolerances. Job Name 750 190 SC D H. INDIGO
Bases are designed to be completely filled with grout. Market -
See configuration for estimated total weight. Quote Item 001
For additional dimensions, refer to engine manufacturer's website. Quote Date 08 Oct 2020
MODELS
JU6H-UFD0 JU6H-UF34 JU6H-UF58
R JU6H-UF62 JU6H-UF94
JU6H-UFD2 JU6H-UFM8 JU6H-UF50 JU6H-UFAAQ8 JU6H-UFAAS0
JU6H-UF30 JU6H-UFM0 JU6H-UF52 JU6H-UFAAPG JU6H-UFAAT0
JU6H-UF32 JU6H-UFM2 JU6H-UF54 JU6H-UFAARG JU6H-UFAAT2
UL/FM - cUL APPROVED RATINGS BHP/KW JU6H-UF60 JU6H-UF84 JU6H-UFAAT8

JU6H RATED SPEED (BHP / kW)


MODEL
1470 1760 1900 2100 2350 2600 2800 3000

UFD0 110 82 144 107 148 110


UFD2 148 110 148 110
UF30 94 70 140 104 160 119 160 119
UF32 160 119 160 119
UF34 160 119 175 131
UFM8 136 101 175 131
UFM0 175 131 207 154 200 149
UFM2 200 149 200 149
UF58 138 103 183 137
UF50 183 137 210 157 210 157
UF52 210 157 210 157
UF54 216 161 216 161
UFAAPG 220 164
UFAAQ8 227 169
UF60 200 149 240 179 240 179 Picture shown represents JU6H-T engine model

UF62 240 179 240 179


UFAARG 252 188 All Models are available for Export

UF84 259 193 275 205


UFAAS0 260 194 Note: Engine models with an “*” may have
elevation restrictions. Please consult factory to
UFAAT8 265 198 273 203.5 conirm application.

UFAAT0 293 218.5 295 220


UFAAT2 295 220 291* 217*
UF94 295*220* 300*224*

ITEM JU6H MODELS


D0 D2 30 32 34 M8 M0 M2 58 50 52 54 60 62 84 AAPG AAQ8 AARG AAS0 94 AAT0 AAT2 AAT8
Number of Cylinders 6
Aspiration T TRWA
Rotation* CW
Overall Dimensions - in.(mm) 59.8(1519) H X 57.4(1457) L X 36.6(930) W 59.8(1519) H X 58(1473) L X 36.6(930) W
Crankshaft Centerline Height - in.(mm) 14 (356)
Weight - lb (kg) 1657 (750) 1693 (766)
Compression Ratio 17.0:1
Displacement - cu. in. (I) 414 (6.8)
Engine Type 4 Stroke Cycle - Inline Construction
Bore & Stroke - in. (mm) 4.19 x 5.00 (106 x 127)
Installation Drawing D536 D763 D776
Wiring Diagram AC C07651
Wiring Diagram DC C072145
Engine Series John Deere 6068 Series
Speed Interpolation Optional
Abbreviations: CW - Clockwise T -Turbocharged TRWA - Turbocharged with Raw Water Aftercooling L - Length W - Width H - Height
*Rotation viewed from Heat Exchanger / Front of engine

CERTIFIED POWER RATING


• Each engine is factory tested to verify power and performance

ENGINE RATINGS BASELINES


• Engines are to be used for stationary emergency standby ire pump service only. Engines are to be tested in accordance with NFPA 25.
• Engines are rated at standard SAE conditions of 29.61 in. (752.1 mm) 77°F (25°C) inlet air temperature [approximates 300 ft. (91.4 m) above sea level] by the testing laboratory
(see SAE Standard J 1349).
• A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m)
• A deduction of 1 percent from engine horsepower rating as corrected to standard SAE conditions shall be made for diesel engines for every 10°F (5.6°C) above 77°F (25°C)
ambient temperature.
MODELS
JU6H-UFD0 JU6H-UF34 JU6H-UF58
R JU6H-UF62 JU6H-UF94
JU6H-UFD2 JU6H-UFM8 JU6H-UF50 JU6H-UFAAQ8 JU6H-UFAAS0
JU6H-UF30 JU6H-UFM0 JU6H-UF52 JU6H-UFAAPG JU6H-UFAAT0
JU6H-UF32 JU6H-UFM2 JU6H-UF54 JU6H-UFAARG JU6H-UFAAT2
UL/FM - cUL APPROVED RATINGS BHP/KW JU6H-UF60 JU6H-UF84 JU6H-UFAAT8

ENGINE EQUIPMENT
EQUIPMENT STANDARD OPTIONAL
Air Cleaner Direct Mounted, Washable, Indoor Service with Drip Shield Disposable, Drip Proof, Indoor Service Outdoor Type,
Single or Two Stage (Cyclonic)
Alarms Overspeed Alarm & Shutdown, Low Oil Pressure, Low & High Low Coolant Level, Low Oil Level, Oil FIlter Diferential
Coolant Temperature, Low Raw Water Flow, High Raw Water Pressure, Fuel Filter Diferential Pressure, Air Filter
Temperature Restriction
Alternator 12V-DC, 42 Amps with Poly-Vee Belt and Guard 24V-DC, 40 Amps with Poly-Vee Belt and Guard
Coupling Bare Flywheel Listed Driveshaft and Guard: UFD0, UFD2, UF30, UF32,
UF34, UFM8, UFM0, UFM2, UFS8, UF50, UF52, UF54,
UF60, UF62, UF84 - CDS30-S1;
UFAAPG, AAQ8, AARG, AAT0, AAT8 -CDS50-SC;
UF94 - SC61A-L at 2800 & 3000 RPM;
AAT0, AAT2 - SC81A at 2350 & 2600 RPM
Engine Heater 115V-AC, 1360 Watt 230V-AC, 1360 Watt
Exhaust Flex Connection SS Flex, 150# ANSI Flanged Connection, 5” SS Flex, 150# ANSI Flanged Connection, 6”
(AAT0, AAT2, UF94: SS Flex, 150# ANSI Flanged Connection, 6”)
Exhaust Protection Metal Guards on Manifolds and Turbocharger
Flywheel Housing SAE #3
Flywheel Power Take Of 11.5” SAE Industrial Flywheel; Connection
Fuel Connections Fire Resistant, Flexible, Supply and Return Lines SS, Braided cUL Listed, Supply and Return Lines
Fuel Filter Primary Filter and Priming Pump
Fuel Injection System Direct Injection
Fuel Solenoid 12V-DC Energized to Stop (ETS) 24V-DC Energized to Stop (ETS)
Governor, Speed Constant Speed, Mechanical
Heat Exchanger Tube and Shell, 60 PSI (4 BAR), NPT(F) Connections - Sea Water
Compatible
Instrument Panel NEMA Type 2, Powder Coated Steel Construction, English and 316 Stainless Steel NEMA 4X/IP66
Metric, Tachometer, Hourmeter, Water Temperature, Oil Pressure
and (2) Voltmeters
Junction Box Integral with Instrument Panel; For DC Wiring Interconnection to
Engine Controller
Lube Oil Cooler Engine Water Cooled, Plate Type
Lube Oil Filter Full Flow with By-Pass Valve
Lube Oil Pump Gear Driven, Gear Type
Manual Start Control On Instrument Panel with Control Position Warning Light
Overspeed Control Electronic with Reset and Test on Instrument Panel
Raw Water Cooling Loop - w/Alarms Galvanized Seawater, All 316SS, High Pressure
Raw Water Solenoid Operation Automatic from Fire Pump Controller and from Engine Instrument Not Supplied (for Vertical Turbine Fire Pump Applications)
Panel (for Horizontal Fire Pump Applications)

Run - Stop Control On Instrument Panel with Control Position Warning Light
Starters Two (2) 12V-DC Two (2) 24V-DC
Throttle Control Adjustable Speed Control, Tamper Proof
Water Pump Centrifugal Type, Poly-Vee Belt Drive with Guard

Abbreviations: DC - Direct Current, AC - Alternating Current, SAE - Society of Automotive Engineers, NPT(F) - National Pipe Tapered Thread (Female), SS - Stainless Steel

MODEL NOMENCLATURE (8 Digit Models) MODEL NOMENCLATURE (10 Digit Models)


JU6H-UF94 JU6H-UFAARG

Base Engine Power Curve Number Base Engine Power Curve Number
350 Series UL Listed and FM Approved 350 Series Non-Emissionized
6 Cylinder 6 Cylinder Built in USA
Heat Exchanger Cooled Heat Exchanger Cooled UL Listed and FM Approved

Speciications and information contained in this brochure is subject to change without notice.
R

100 Progress Place, Cincinnati, OH 45246 Grange Works, Lomand Rd, Coatbridge, ML5-2NN
United States of America United Kingdom
Tel +1-513-475-3473 Fax +1-513-771-8930 Tel +44-1236-429946 Fax +44-1236-427274

C13556 RevS www.clarkefire.com


07NOV18
FIRE PUMP MODEL: JU6H-UF52
Heat Exchanger Cooled
T urbocharged
6.8L 6 Cylinder
Brake Horsepow er - BHP (kw )

ENGINE SPEED - RPM


RESTRICTED:
Use only for Stand-By Fire Pump Applications

NAMEPLATE BHP (MAXIMUM PUMP LOAD)

ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77°F (25°C) AIR INLET TEMPERATURE
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)
THIS DRAWING AND THE INFORMATION CREA TED DA TE CREA TED
HEREIN ARE OUR PROPERTY AND MAY
BE USED BY OTHERS ONLY AS 08/23/00
AUTHORIZED BY US. UNPUBLISHED --
ALL RIGHTS RESERVED UNDER THE
COPYRIGHT LAWS.
ENGINE MODEL JU6H-UF52
DRA WING NO . REV
John W hitney 23AUG00 C13495 A
JU6H-UF52
INSTALLATION & OPERATION DATA (I&O)
USA Produced
Basic Engine Description
Engine Manufacturer ......................................................................................................................................................
John Deere C o.
Ignition Type ......................................................................................................................................................
C ompression (Diesel)
Number of C ylinders ......................................................................................................................................................
6
Bore and Stroke - in (mm) ......................................................................................................................................................
4.19 (106) X 5 (127)
Displacement - in³ (L) ......................................................................................................................................................
415 (6.8)
C ompression Ratio ......................................................................................................................................................
17.0:1
Valves per cylinder
Intake ......................................................................................................................................................
1
Exhaust ......................................................................................................................................................
1
C ombustion System ......................................................................................................................................................
Direct Injection
Engine Type ......................................................................................................................................................
In-Line, 4 Stroke C ycle
Fuel Management C ontrol ......................................................................................................................................................
Mechanical, Rotary Pump
Firing Order (C W Rotation) ......................................................................................................................................................
1-5-3-6-2-4
Aspiration ......................................................................................................................................................
Turbocharged
C harge Air C ooling Type ......................................................................................................................................................
None
Rotation, viewed from front of engine, C lockwise (C W) ......................................................................................................................................................
Standard
Engine C rankcase Vent System ......................................................................................................................................................
Open
Installation Drawing ......................................................................................................................................................
D536
Weight - lb (kg) ......................................................................................................................................................
1657 (752)

Power Rating 2350 2600


Nameplate Power - HP (kW) ¹ ......................................................................................................................................................
210 (157) 210 (157)

Cooling System - [C051127] 2350 2600


Engine C oolant Heat - Btu/sec (kW) ......................................................................................................................................................
101 (107) 96 (101)
Engine Radiated Heat - Btu/sec (kW) ......................................................................................................................................................
15.5 (16.4) 15.5 (16.4)
Heat Exchanger Minimum Flow
60°F (15°C ) Raw H2O - gal/min (L/min) ......................................................................................................................................................
21 (79.5) 23 (87.1)
100°F (37°C ) Raw H2O - gal/min (L/min) ......................................................................................................................................................
26 (98.4) 28 (106)
Heat Exchanger Maximum C ooling Raw Water
Inlet Pressure - psi (bar) ......................................................................................................................................................
60 (4.1)
Flow - gal/min (L/min) ......................................................................................................................................................
40 (151)
Typical Engine H2O Operating Temp - °F (°C ) ......................................................................................................................................................
180 (82.2) - 195 (90.6)
Thermostat
Start to Open - °F (°C ) ......................................................................................................................................................
170 (76.7)
Fully Opened - °F (°C ) ......................................................................................................................................................
190 (87.8)
Engine C oolant C apacity - qt (L) ......................................................................................................................................................
19.5 (18.5)
C oolant Pressure C ap - lb/in² (kPa) ......................................................................................................................................................
10 (68.9)
Maximum Engine C oolant Temperature - °F (°C ) ......................................................................................................................................................
200 (93.3)
Minimum Engine C oolant Temperature - °F (°C ) ......................................................................................................................................................
160 (71.1)
High C oolant Temp Alarm Switch - °F (°C ) ......................................................................................................................................................
205 (96.1)

Electric System - DC Standard Optional


System Voltage (Nominal) ......................................................................................................................................................
12 24
Battery C apacity for Ambients Above 32°F (0°C )
Voltage (Nominal) ......................................................................................................................................................
12 {C 07633} 12 {C 07633}
Qty. Per Battery Bank ......................................................................................................................................................
1 2
SAE size per J537 ......................................................................................................................................................
8D 8D
C C A @ 0°F (-18°C ) per J537 ......................................................................................................................................................
1400 1400
Reserve C apacity - Minutes per J537 ......................................................................................................................................................
430 430
Battery C able C ircuit, Max Resistance - ohm ......................................................................................................................................................
0.0012 0.0012
Battery C able Minimum Size
0-120 in. C ircuit Length ² ......................................................................................................................................................
00 00
121-160 in. C ircuit Length ² ......................................................................................................................................................
000 000
161-200 in. C ircuit Length ² ......................................................................................................................................................
0000 0000
C harging Alternator Maximum Output - Amp, ......................................................................................................................................................
40 {C 07639} 18 {C 071048}
Starter C ranking Amps, Rolling - @60°F (15°C ) ......................................................................................................................................................
440 {RE69704/RE70404} 250 {C 07819/C 07820}

Page 1 of 2
C 133697 Rev G
* All footnotes are at the bottom of Page 2 DSP 21NOV19
JU6H-UF52
INSTALLATION & OPERATION DATA (I&O)
USA Produced
Exhaust System (Single Exhaust Outlet) 2350 2600
Exhaust Flow - ft.³/min (m³/min) ......................................................................................................................................................
1359 (38.5) 1496 (42.4)
Exhaust Temperature - °F (°C ) ......................................................................................................................................................
977 (525) 953 (512)
Maximum Allowable Back Pressure - in H2O (kPa) ......................................................................................................................................................
25 (6.2) 25 (6.2)
Minimum Exhaust Pipe Dia. - in (mm) ³ ......................................................................................................................................................
5 (127) 5 (127)

Fuel System 2350 2600


Fuel C onsumption - gal/hr (L/hr) ......................................................................................................................................................
12.9 (48.8) 12.7 (48.1)
Fuel Return - gal/hr (L/hr) ......................................................................................................................................................
7.9 (29.9) 8.6 (32.6)
Fuel Supply - gal/hr (L/hr) ......................................................................................................................................................
20.8 (78.7) 21.3 (80.6)
Fuel Pressure - lb/in² (kPa) ......................................................................................................................................................
3 (20.7) - 4 (27.6)
Minimum Line Size - Supply - in. ......................................................................................................................................................
.50 Schedule 40 Steel Pipe
Pipe Outer Diameter - in (mm) ......................................................................................................................................................
0.848 (21.5)
Minimum Line Size - Return - in. ......................................................................................................................................................
.375 Schedule 40 Steel Pipe
Pipe Outer Diameter - in (mm) ......................................................................................................................................................
0.675 (17.1)
Maximum Allowable Fuel Pump Suction Lift
with clean Filter - in H2O (mH2O) ......................................................................................................................................................
31 (0.8)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft (m) ......................................................................................................................................
4.5 (1.4)
Fuel Filter Micron Size ......................................................................................................................................................
5

Heater System Standard Optional


Engine C oolant Heater
Wattage (Nominal) ......................................................................................................................................................
1360 1360
Voltage - AC , 1 Phase ......................................................................................................................................................
115 (+5% -10%) 230 (+5%, -10%)
Part Number ......................................................................................................................................................
{C 123640} {C 123644}

Air System 2350 2600


C ombustion Air Flow - ft.³/min (m³/min) ......................................................................................................................................................
508 (14.4) 568 (16.1)
Air C leaner ......................................................................................................................................................
Standard Optional
Part Number ......................................................................................................................................................
{C 03396} {C 03327}
Type ......................................................................................................................................................
Indoor Service Only, C anister,
with Shield Single-Stage
C leaning method ......................................................................................................................................................
Washable Disposable
Air Intake Restriction Maximum Limit
Dirty Air C leaner - in H2O (kPa) ......................................................................................................................................................
12 (3) 12 (3)
C lean Air C leaner - in H2O (kPa) ......................................................................................................................................................
6 (1.5) 5 (1.2)
Maximum Allowable Temperature (Air To Engine Inlet) - °F (°C ) .....................................................................................................................................................
130 (54.4)

Lubrication System
Oil Pressure - normal - lb/in² (kPa) ......................................................................................................................................................
40 (276) - 60 (414)
Low Oil Pressure Alarm Switch - lb/in² (kPa) ......................................................................................................................................................
20 (138)
In Pan Oil Temperature - °F (°C ) ......................................................................................................................................................
220 (104) - 245 (118)
Total Oil C apacity with Filter - qt (L) ......................................................................................................................................................
19.7 (18.6)

Lube Oil Heater Optional Optional


Wattage (Nominal) ......................................................................................................................................................
150 150
Voltage ......................................................................................................................................................
120V (+5%, -10%) 240V (+5%, -10%)
Part Number ......................................................................................................................................................
{C 04430} {C 04431}

Performance 2350 2600


BMEP - lb/in² (kPa) ......................................................................................................................................................
171 (1180) 154 (1060)
Piston Speed - ft/min (m/min) ......................................................................................................................................................
1958 (597) 2167 (661)
Mechanical Noise - dB(A) @ 1m ......................................................................................................................................................
C 131782
Power C urve ......................................................................................................................................................
C 13495

NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. ¹ Derate 3% per every 1000 ft. 304.8m above 300 ft. 91.4m and derate 1%
for every 10°F 5.55 °C above 77°F 25°C. ² Positive and Negative Cables Combined Length. ³ Minimum Exhaust Pipe Diameter is based on: 15 feet of pipe, one
90° elbow, and one Industrial silencer. A Back-pressure flow analysis must be performed on the actual field installed exhaust system to assure engine maximum
allowable back pressure is not exceeded. See Exhaust Sizing Calculator on www.clarkefire.com. { } indicates component reference part number.
Page 2 of 2
C 133697 Rev G
DSP 21NOV19
JU4H, JU4R & JU6H, JU6R ENGINE MODELS
ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner Cylinder Head
Type…………..………….. .. Indoor Usage Only Type…….. …………………Slab 2 Valve
Oiled Fabric Pleats Material……………………. Annealed Gray Iron
Material……..…..…….………Surgical Cotton
Aluminum Mesh Cylinder Liners
Type…….. …………………Centrifugal Cast, Wet Liner
Air Cleaner - Optional Material………………..….…Alloy Iron Plateau, Honed
Type…………………………. Canister
Material………………………Pleated Paper Fuel Pump
Housing………………..…… Enclosed Type…………………………Diaphragm
Drive…………………………Cam Lobe
Camshaft
Material………….………….. Cast Iron Heat Exchanger (USA) - JU4H & JU6H Only
Chill Hardened Type…………………………Tube & Shell
Location…………...….……. In Block Materials
Drive……………….………..… Gear, Spur Tube & Headers……………Copper
Type of Cam…………..….... Ground Shell…………………………Copper
Electrode……………………Zinc
Charge Air Cooler (JU6H-60,62,68,74,84, 94, T8, T0,
T2, ADK0, AD58, ADNG, ADN0, ADQ0, ADR0, AAQ8,
AARG, ADP8, ADP0, ADT0, AD88, ADR8, AD98,
ADS0, ADW8, ADX8, AD98 only)
Type……….. ..…………….Raw Water Cooled Heat Exchanger (UK) - JU4H & JU6H Only
Materials (in contact with raw water) Type…………………………Tube & Bundle
Tubes……… …………………… 90/10 CU/NI
Headers …………………… 36500 Muntz Materials
Covers …………………… 83600 Red Brass Tube & Headers……………Copper
Plumbing …………………… 316 Stainless Steel/ Brass Shell………..……………. Aluminum
90/10 Silicone
Injection Pump
Charge Air Cooler (JU6R-AA67, 59, 61, PF, Q7, RF, Type……………………….. Rotary
S9, 83 only) Drive…………………………Gear
Type…...……………………Air to Air Cooled
Materials Lubrication Cooler
Core…………………………Aluminum Type…………………………Plate

Coolant Pump Lubrication Pump


Type……….………………… Centrifugal Type…………………………Gear
Drive……………………………Poly Vee Belt Drive…………………………Gear

Coolant Thermostat Main Bearings


Type…………………………… Non Blocking Type…………………………Precision Half Shells
Qty……………………………1 Material………………………
Steel Backed-Aluminum
Lined
Cooling Loop (Galvanized)
Tees, Elbows, Pipe…………Galvanized Steel Piston
Ball Valves……………………Brass ASTM B 124, Type and Material…………Aluminum Alloy with
Solenoid Valve………………Brass Reinforced Top Ring Groove
Pressure Regulator…………Bronze Cooling………………………Oil Jet Spray
Strainer………………………Cast Iron (1/2" - 1" loops) or
Bronze (1.25" - 2" loops) Piston Pin
Type…………………………Full Floating - Offset

Cooling Loop (Sea Water) Piston Rings


Tees, Elbows, Pipe…………316 Stainless Steel Number/Piston…………… 3
Ball Valves……………………316 Stainless Steel Top………………………… Keystone Barrel Faced -
Solenoid Valve………………316 Stainless Steel Plasma Coated
Pressure Regulator/StrainerCast Brass ASTM B176 Second………………………Tapered Cast Iron
C87800 Third…………………………Double Rail Type
w/Expander Spring
Cooling Loop (316SS)
Tees, Elbows, Pipe…………316 Stainless Steel Radiator - JU4R & JU6R Only
Ball Valves……………………316 Stainless Steel Type……………………… Plate Fin
Solenoid Valve………………316 Stainless Steel Materials
Pressure Regulator/Strainer316 Stainless Steel Core……………………… Copper & Brass
Tank & Structure……….. Steel
Connecting Rod
Type…………………………… I-Beam Taper Optional
Material………………………Forged Steel Alloy Marine Coating…………… Baked Phenolic

Crank Pin Bearings Valves


Type…………………………… Precision Half Shell Type…….. …………………Poppet
Number………………………1 Pair Per Cylinder Arrangement………… ……Overhead Valve
Material………………………Wear-Guard Number/Cylinder…………… 1 intake
1 exhaust
Crankshaft Operating Mechanism……Mechanical Rocker Arm
Material………………………Forged Steel Type of Lifter…………….. Large Head
Type of Balance…………… Dynamic Valve Seat Insert……………Replaceable

Cylinder Block
Type…………………………… One Piece with
Non-Siamese Cylinders
Material………………………Annealed Gray Iron

C13615 14NOV18
JU6H-UF52
Stationary Fire Pump Engine Driver
EMISSION DATA
EPA 40 CFR Part 60

6 Cylinders
Four Cycle
Lean Burn
Turbocharged

500 PPM SULFUR #2 DIESEL FUEL


FUEL GRAMS / HP- HR EXHAUST
RPM BHP (3) GAL/HR (4) CFM
NMHC NOx CO PM °F (°C)
(L/HR) (m3/min)
2350 210 12.9 (49) 0.20 4.70 0.46 0.15 977 (525) 1359 (38)
2600 210 12.7 (48) 0.20 4.72 0.57 0.22 953 (512) 1496 (42)

Notes:
1) 6068TF220 Base Engine Model manufactured by John Deere Corporation.
For John Deere Emissions Conformance to EPA 40 CFR Part 60 see Page 2 of 2.
2) The Emission Warranty for this engine is provided directly to the owner
by John Deere Corporation. A copy of the John Deere Emission Warranty can
be found in the Clarke Operation and Maintenance Manual.
3) Engines are rated at standard conditions of 29.61in. (7521 mm) Hg barometer
and 77°F (25° C) inlet air temperature. (SAE J1349)
4) PM is a measure of total particulate matter, including PM 10 .

CLARK E
FIRE PROTECTION PRODUCTS
3133 EAST KEMPER ROAD
C131852 REV.C CINCINNATI, OH 45241
01NOV 07 KRW PAGE 1 OF 2
John Deere Power Systems
3801 W. Ridgeway Ave., PO Box 5100
Waterloo, Iowa USA 50704-5100

31 October 2007

Subject: Fire Pump Ratings – Conformance to EPA 40 CFR Part 60 (NSPS requirements)

All John Deere stationary fire pump engines conform to the requirements of 40 CFR Part 60. All such
engines include an emission label, stating the engine conforms to the requirements of 40 CFR Part 60. An
example of the emission label is show below:

This label applies to all of the following engine models, sold to Clarke Fire Protection, for use in stationary
fire pump applications:

All engines conforming to 40 CFR Part 60 (identified by emission label, as shown above) are covered under
the emissions warranty of 40 CFR Part 89.

Sincerely,

Kyle J. Tingle
Regional Sales Manager, JDPS
Page 2 of 2
JU6H-UF52
FIRE PUMP DRIVER

NOISE DATA
Mechanical Engine Noise *
Octave Band

RPM BHP OVERALL 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz 16k Hz


dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
2350 210 106.60 67.00 68.40 81.90 87.90 93.00 99.00 102.20 100.90 92.40 85.90
2600 210 108.60 68.30 69.40 84.80 92.30 93.70 100.50 103.70 103.50 94.60 88.50

Raw Exhaust Engine Noise **


Octave Band

RPM BHP OVERALL 31.5 Hz 63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz 16k Hz


dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
2350 - 2600 210 109.50 0.00 99.30 103.70 98.40 100.60 100.20 102.90 99.10 89.80 83.40

* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.
** Values above are provided at 23ft (7m), 90° horizontal, from a vertical exhaust outlet and does not include noise created mechanically by the engine.
The above data reflects nominal values for a typical engine of this model, speed and power in a free-field environment, tested at a no-load condition.
Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect the overall noise
levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.

C131782 Rev D 23Jan18 DSP


Controladores de motor diésel
BR081011S Vigente abril 2015 FD120

Motor diésel
Controladores de bombas contra incendios
Tipos de comunicación Relés de salida estándar Alimentación/voltaje
USB Todos los relés de salida estándar son de Suministro de voltaje universal
El puerto USB se utiliza para descargar 8 amperios, DPDT. El controlador se puede alimentar con
el historial de mensajes, estadísticas, voltajes de suministro de 0 VAC a 
diagnósticos, estado y datos de configuración t Future #1 (Futuro No. 1) 240 VAC al conectarse a tres terminales de
del controlador en una unidad de disco USB. entrada L, N, G que se encuentran en la
t Future #2 (Futuro No. 1)
El puerto USB también se puede utilizar para parte inferior izquierda del tablero del
t Low Fuel (combustible bajo) motor.
cargar mensajes personalizados, idiomas t Modo Auto (automático)
adicionales y actualizar el firmware
t Common Alarm (Alarma común)
del microprocesador.
Relés de salida opcionales
Descripción del producto Ethernet
Se puede conectar una computadora
Existe la posibilidad de agregar hasta ocho
salidas de relé adicionales, por medio de
Los Controladores de bomba contra incendios externa al controlador Diesel Plus por medio cuatro tableros de salida de relé opcionales
DIESEL Plus de Eaton están diseñados para del puerto Ethernet opcional. Una página que se montan en la configuración a presión.
controlar y supervisar los motores de bomba Web integrada muestra el estado actual Cada tablero contiene un máximo de 2 relés
contra incendios diésel de 12 o 24 voltios del controlador, así como todas las lecturas adicionales. Salida doble
y se encuentran entre los controladores actuales, puntos de ajuste e historial. La salida de 12 o 24 VDC se puede seleccionar
disponibles de motor diésel técnicamente por medio del interruptor DIP que se
más avanzados. encuentra en los cargadores de la batería.
Son una versión mejorada de la Serie FD100 Modbus Nota: Cada controlador está establecido en
basada en el microprocesador original Los controladores de bomba contra incendios fábrica para 12 VDC. Si se necesitan 24 VDC
de los controladores de motor diésel. La Diesel Plus tienen la opción de comunicarse de fábrica, se debe indicar en la información
programación es directa debido al uso del con los sistemas utilizando el nivel Regular de del pedido.
firmware principal y la estructura del menú Modbus (incluye los modos de transmisión
utilizada en la Serie LMR Plus de controladores RTU y ASCII). Los ajustes de comunicación Filtro de línea
eléctricos. los puede configurar el usuario a través del Un filtro de línea incorporado en el tablero
menú de configuración de Diésel Plus. del motor se utiliza para reducir/eliminar
El controlador se puede pedir con la opción
Relé de funcionamiento del motor los transientes de voltaje externo entrante.
para mostrar y transmitir valores y estados
de corriente, a pedido, desde varios protocolos El tablero de E/S de energía aloja un relé de
Conexiones de campo funcionamiento del motor de 10 amperios
Desconexión de alimentación de AC
de software.
que se utiliza para propósitos de alarma o para Un interruptor que se encuentra dentro del
Desde el puerto de comunicación opcional Entradas estándar energizar persianas externas. controlador en el Tablero del motor se utiliza
Ethernet se puede acceder a una página Web t Remote Start (Arranque remoto) para encender y apagar la alimentación de
integrada para recuperar los reportes de t Fuel Spill (Derrame de combustible) Relé de alarma común AC a la unidad. Se enciende cuando recibe
diagnóstico e historial. El puerto serial RS485 t Deluge Valve (Válvula de Inundación) El controlador FD120 tiene un relé de alarma energía.
opcional se puede utilizar para conexión t Low Suction (Succión baja)
t Interlock On (Interbloqueo activado)
común que se desenergiza cada vez que hay Desconexión de la alimentación
directa a una computadora para transferencia condiciones de alarma. Este relé se energiza
de datos. t Pump Start (Arranque de la bomba) de DC
bajo condiciones normales y tiene una
t Low Fuel (Combustible bajo) El tablero del motor aloja dos interruptores
indicación de estado de diodo fotoemisor.
t Entradas programables (9) automáticos en tablero que se utilizan para

Características Clasificación del relé de alarma encender o apagar la alimentación de DC de


Entradas programables las baterías.
Todos los relés de alarma están clasificados
del producto Se pueden programar hasta 9 entradas
a 8 amperios, 250 VAC, 1/3 HP solamente de Cada interruptor tiene un diodo fotoemisor
programables adicionales para indicar
Comunicación hasta 13 tipos de entradas diferentes. Se carga de resistencia. montado en el tablero del motor que se
enciende cuando el interruptor recibe energía.
pueden programar para energizar la salida Salidas programables
Página Web integrada
de alarma común, enlazar a relés y diodos
Se pueden programar hasta 10 salidas
Las páginas Web integradas permiten al
usuario ver el estado actual del controlador
fotoemisores opcionales y asegurar hasta que
programables adicionales (dos estándar; ocho
Indicación de alarma y estado
las restablezca el usuario.
así como todas las lecturas de amperaje, Todas las entradas, salidas y diodos por medio de tableros de salida opcionales) Accesibilidad
puntos de ajuste, diagnósticos, estadísticas, fotoemisores opcionales se pueden enlazar, para indicar hasta 45 condiciones de salida.
Puede acceder a todos los diodos fotoemisores
configuración e historial. Para acceder a las según sea necesario. También se pueden Se pueden programar para seguridad contra
de alarma y estado así como la pantalla LCD
páginas se usa una computadora externa programar con funciones de retardo de fallas y asegurar hasta que las restablezca
y los botones de programación desde la parte
conectada por medio del puerto opcional tiempo. el usuario. Todas las entradas, salidas y diodos
delantera del controlador.
Ethernet. Los datos específicos requeridos fotoemisores opcionales se pueden enlazar,
se pueden descargar para propósitos de según sea necesario. También se pueden
referencia. programar con funciones de retardo de
tiempo. Igualmente, se pueden programar
dos diodos fotoemisores de alarma opcionales
hasta para 28 condiciones de alarma.
BR081011S Motor diésel
Abril de 2015 Controladores de bombas contra incendios

Pantalla LCD t FUEL INJECTION MALFUNCTION t AC Failure Alarm (Alarma de falla de AC)
El tablero de la pantalla del controlador (MAL FUNCIONAMIENTO EN t AC Fail to Start (Falla de arranque
contiene una pantalla LCD de 4 líneas por de AC)
LA INYECCIÓN DE COMBUSTIBLE)
40 caracteres de ancho, con iluminación
trasera, que tiene la capacidad de generar t ECM WARNING (ADVERTENCIA
varios idiomas. La pantalla muestra la presión DEL ECM)
Cajas
actual del sistema, hora y fecha, voltaje de t ECM FAILURE (FALLA DEL ECM)
salida del cargador y cualquier mensaje Capacidades
t HIGH RAW WATER TEMP. (TEMP. ALTA Todos los controladores FD120 vienen
personalizado, alarma o valores
del temporizador. DE AGUA NO PROCESADA) estándar con cajas NEMA 2 a menos que
t LOW ENGINE TEMPERATURE se pida algo distinto.
(TEMPERATURA BAJA DEL MOTOR)
Las opciones disponibles incluyen: Estándares y certificaciones
NEMA 3R, 4, 4X, 12.
t FUEL SPILL (DERRAME COMBUSTIBLE) Los controladores de bomba contra incendios
t One Programmable LED (Un diodo Tamaño reducido del motor diésel FD120 cumplen o superan
fotoemisor programable) Un diseño interno aerodinámico ha permitido los requisitos de Underwriters Laboratories,
que el tamaño total de modelos anteriores de Factory Mutual Research (FM), la Asociación
controladores DIESEL Plus se reduzca. Consulte Canadiense de Estándares, el código de
Estadísticas los dibujos de medidas en nuestro sitio Web. construcción de la Ciudad de Nueva York,
Se registran hasta 26 puntos estáticos para la marca CE y U.B.C. /requisitos sísmicos
proporcionar una revisión rápida de cómo de C.B.C, se construyen de acuerdo con los
está operando el sistema. Las estadísticas se Especificaciones técnicas estándares NFPA 20.

Diodos fotoemisores de estado pueden ver en la pantalla principal, se pueden


El controlador se suministra con seis (6) guardar en una unidad de disco USB o se t Voltaje de suministro: 0-240Vac
diodos fotoemisores verdes de estado para pueden ver en la página Web integrada. t Voltaje de salida: 12-24Vdc
lo siguiente: t Hertz: 50/60 Hz
t Caja:
t LOW PRESSURE (PRESIÓN BAJA) Diagnósticos
Estándar NEMA 2
Se pueden registrar hasta cincuenta y tres
t ENGINE RUN (FUNC DEL MOTOR) t NEMA 3R, 4, 4X, 12 opcional
puntos de diagnóstico que se pueden usar
t Temperatura:
t REMOTE START (ARRANQUE REMOTO) para ayudar a resolver problemas con
4 a +50 grados C
el controlador. Los diagnósticos se pueden ver
t INTERLOCK ON (INTERBLOQUEO 39 a +122 grados F
en la pantalla principal, se pueden guardar en
ACTIVADO) t Relés de alarma: DPDT 8 amp
una unidad de disco USB o se pueden ver en
t Relé de funcionamiento del motor
t DELUGE VALVE (VÁLVULA DE la página Web integrada.
DPDT 10 amp
INUNDACIÓN) t Relés de parada de arranque/
Historial de mensajes combustible: SPDT
t Un diodo fotoemisor programable Se pueden almacenar hasta 10k de alarmas/ t Transductor de presión: 500 psi
estado en la memoria del controlador. Se t Cumplimiento de inmunidad:
pueden ver en la pantalla principal, se pueden Ambiente A
Diodo fotoemisor de alarma guardar en una unidad de disco USB o se t Cumplimiento de emisión:
El controlador se suministra con veinte (20) pueden ver en la página Web integrada. Ambiente B
diodos fotoemisores rojos de estado para
lo siguiente:
Falla de DC
t BATTERY # 1 FAILURE Se proporciona una indicación visual y una Cargadores de la batería
(FALLA DE BATERÍA N.° 1) alarma audible para indicar una pérdida
t CHARGER # 1 FAILURE de alimentación de DC debido a que una t Modo: Interruptores
o ambas baterías se están desconectando t Doble de 10 amperios
(FALLA DEL CARGADOR No. 1)
del controlador. Esta indicación también se t Comunicación a alimentación
t BATTERY # 2 FAILURE proporcionará en caso de que el controlador Tablero de E/S
(FALLA DE BATERÍA N.° 1) no esté funcionando debido a una falla t Registro de diagnósticos
del tablero electrónico. t Ácido de plomo o carga en tres pasos
t CHARGER # 2 FAILURE
NiCad
(FALLA DEL CARGADOR No. 1) t Supervisión de temperatura interna
Características programables
t LOW PRESSURE (PRESIÓN BAJA) t Entrada de voltaje universal
t Languages (Idiomas)
t SYSTEM OVER PRESSURE t (Inglés, francés, español estándar. Hay t Salida de voltaje doble seleccionable
(SOBREPRESIÓN DEL SISTEMA) otros idiomas disponibles. Consulte
a la fábrica).
t LOW SUCTION PRESSURE
t Date and Time (Fecha y hora)
(BAJA PRESIÓN DE SUCCIÓN) t Pressure Start and Stop Points (Puntos
t LOW FUEL (COMBUSTIBLE BAJO) de arranque y parada de presión)
t FAIL TO START (FALLA DE ARRANQUE) t Low and High Pressure Alarms
(Alarmas de presión baja y alta)
t HIGH ENGINE TEMP t Stop Mode (Parada)
(TEMP ALTA DEL MOTOR) t Low Suction Shutdown (Desconexión
t LOW OIL PRESSURE por baja succión)
t Pressure Recording Parameters
(PRESIÓN ACEITE BAJA) (Parámetros de registro de presión)
t ENGINE OVER SPEED t Run Period Timer (Temporizador
(SOBREVELOCIDAD DEL MOTOR) del período de funcionamiento)
t Weekly Test Timer (Temporizador
t ECM SELECTOR IN ALT POSITION
de prueba semanal)
(SELECTOR DE ECM EN POSICIÓN ALT) t Sequential Start Timer (Temporizador
de arranque en secuencia)

© 2015 Eaton Eaton Industries Canada Company


Todos los derechos reservados 10725 - 25th Street NE, # 124
Impreso en Canadá Calgary, AB T3N0A4
Publicación N.º BR081011S Canada
Abril de 2015 www.chfire.com
®
FAIRBANKS NIJHUIS

PVM(X) SERIES VERTICAL MULTISTAGE


Certified to
NSF/ANSI 61 & 372

PVMX1
through
PVMX33
Only
Ft. H[m]
1312 400
✤ ✁ ✂✄☎
984 300 60 Hz

656 200

PVM150
PVMX150
PVM120
328 100 PVMX120

262 80
PVM3 PVM10 PVM20 PVM45 PVM90
197 60 PVMX3 PVMX10 PVMX20 PVMX45 PVMX90

131 40
PVM1 PVM5 PVM15 PVM33 PVM64
98 30 PVMX1 PVMX5 PVMX15 PVMX33 PVMX64

66 20

PVM and PVMX pumps have different size


33 10
and various numbers of stages to provide 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 Q[m3h]
the flow and pressure required. 4 9 13 18 22 26 35 44 88 132 176 220 264 350 440 880 GPM

VERTICAL MULTISTAGE PUMPS


ADDED VALUES: MADE TO SUPPLY WATER
The PVM and PVMX are vertical in-line multistage
TEFC Motors pumps with stainless steel stage construction. PVM
Increased protection against models are available with flanged/NPT or grooved
weather, dirt and moisture connections. PVMX models are available in flanged,
grooved or NPT connections.
Premium efficiency motors are standard for 230/460V,
EPACT efficiency for all other voltages.
Pump shafts are directly coupled to NEMA
standard motors.

PENTAIR PVM - TECHNICAL DATA


▶▶ Flow: up to 800 GPM ▶▶ Motor: 50/60 Hz
Cartridge mechanical seal ▶▶ Heads: up to 960 ft ▶▶ EPACT and premium
It can be replaced easily without efficient motors available
▶▶ Liquid temp: 5°F to 248°F
dismantling the pump
▶▶ 200 to 575 Volts
▶▶ Flanges connection: ANSI
Class 150 & Class 250 ▶▶ TEFC enclosures
standard for
▶▶ Cartridge mechanical
Stainless Steel construction PVM(X)1 – PVM(X)33
seal: SiC/SiC/EPDM
Impellers and diffusers in
or Viton® ▶▶ Up to 100 hp
AISI 304 (PVM) or AISI 316 (PVMX)

APPLICATION
Multiple Connection Options
Flanged, grooved or
▶▶ Water supply ▶▶ Irrigation
NPT connections ▶▶ Pressure ▶▶ High pressure washes
boosting systems ▶▶ Liquid transfer
▶▶ Water treatment/ ▶▶ Boiler feed
filtration ▶▶ Jockey pumps

Fairbanks Nijhuis®
3501 Fairbanks Avenue, Kansas City, Kansas 66106 · Tel. 913-371-5000
www.FairbanksNijhuis.com FM-02-1544 (01/23/15)
Customer : Engie Services Perú Jockey Pump Curve
S.A. Encompass 2.0 - 20.3.5
Project name : 750 190 SC D H.
INDIGO
Curve efficiencies are typical. For guaranteed values, contact factory
250

225

200 PVM(I/X)1-17

175

150
Head - psi

125

100

75

50

25

30
NPSH3 - ft

NPSH3
15

2.4

Power
1.8
Power - hp

1.2

0.6

0.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Flow - USgpm

Item number : 001 Size : PVM(X)1-17


Service : Stages : 17
Quantity :1 Speed, rated : 3500 rpm
Quote number : 1251003 Based on curve number : PVM(X)1-17
Date last saved : 08 Oct 2020 11:52 AM Efficiency : 39.85 %
Flow, rated : 5.00 USgpm Power, rated : 1.49 hp
Differential head / : 195.0 psi NPSH required : 14.35 ft
pressure, rated Viscosity : 1.00 cP
Fluid density, rated / max : 0.999 / 0.999 SG Cq/Ch/Ce/Cn [ANSI/HI 1.1-1.5-1994] : 1.00 / 1.00 / 1.00 / 1.00

BEST SECURITY DEL PERU SAC PHONE: · FAX:


JR. ROFOLFO BELTRAN NRO. 134 · URBANIZACION ·
SANTA CATALINA, LA VICTORIA, LIMA
Encompass 2.0 - 20.3.5

General Arrangement
Pump Data
Model PVM1-17
Stages 17
Flow 5.00 USgpm
Head 195.0 psi
Rotation Right Hand
Suc/Disch Size 0.00 in
Connection Suc/Disch 1.25'' ANSI 250# flg w/ 1.25'' NPT female

Motor Data
Power 2.00 hp
Phase 3
Frequency 60 Hz
Voltage 380
Speed 3500
Frame Size 56CZ
Efficiency EPAct
Enclosure TEFC

Pump Materials of Construction


Pump Material Cast Iron
Elastomer -

Estimated Weights
Pump 106.0 lb
Motor 0.00 lb

Additional Options

A B C D E F
21.80 12.10 7.20 2.10 35.90 7.20

NOTES: Quote Information


All dimensions are in inches. Customer Engie Services Perú S.A.
Dimensions may vary ± 1/4" (6mm) due to normal manufacturing tolerances Customer Quote 1251003
- Job Name 750 190 SC D H. INDIGO
- Market -
Quote Item 001
Quote Date 08 Oct 2020
BR081001S Fecha de vigencia junio de 2015 Controladores de la bomba compensadora

Controladores de la bomba compensadora


Basado en microprocesador con pantalla táctil a color

Mecanismo de la manija Visualización de pantalla


giratoria sellada táctil a color
El mecanismo de manija giratoria Los controladores de la bomba
se puede bloquear en la posición
compensadora JOCKEY se
OFF (apagado).
suministran con una pantalla
Controles de alimentación XT táctil a color basada en
Los controladores de la bomba microprocesador. La visualización
compensadora JOCKEY de pantalla táctil le permite al
Touch incorporan controles de usuario supervisar y programar
alimentación XT de Eaton que funciones y valores.
están diseñados para el mercado La entrada de presión se
Descripción del global. Los controles XT cuentan
con clasificaciones globales, son
proporciona por medio de un
producto pequeños y están disponibles en sensor de presión de 4-20 mA.
EN TODA LA LÍNEA una amplia variedad de voltajes
de funcionamiento. Son fáciles de
CONTROLADORES DE LA instalar y dar mantenimiento debido
BOMBA COMPENSADORA a su diseño modular y enchufable. Datos técnicos
Los controladores de la bomba Voltaje de suministro universal EN TODA LA LÍNEA (directo en la línea)
compensadora JOCKEY Touch
funcionan en toda la línea. El voltaje Los controladores detectarán CONTROLADORES DE LA BOMBA COMPENSADORA
completo que se aplica al motor para automáticamente suministro de
voltaje trifásico desde 200 VCA Voltaje de línea
que arranque es mediante el uso
de un motor de arranque individual. hasta 600 VCA, 50/60 Hz 200-208V 220-240V 380-415V 440-480V 550-600V 120 V-monofásico 240 V-monofásico
La corriente de irrupción de arranque y monofásico desde 110 VCA
hasta 240 VCA, 50/60 Hz, sin
Caballos de fuerza del motor
es aproximadamente el 600% de
los amperios de carga completa el uso de un transformador de 1/3-20 Hp 1/3-20 Hp 1/3-40 Hp 1/3-50 Hp 1/3-50 Hp 1/3-2 Hp 1/3-5 Hp
especificados. control.
Y-DELTA (estrella-Delta) Cajas NEMA 2
CONTROLADORES DE LA Las cajas tienen un acabado de
pintura pulverizada al horno y se
Y-DELTA (estrella-Delta)
BOMBA COMPENSADORA CONTROLADORES DE LA BOMBA COMPENSADORA
suministran con la clasificación
Cuando los motores de la bomba NEMA 2, a menos que se solicite
compensadora conectados a seis o Voltaje de línea
otra cosa. Las opciones disponibles
12 conductores delta están conectados incluyen: NEMA 3R, 4, 4X, 12. 200-208V 220-240V 380-415V 440-480V 550-600V
en Y (estrella), aproximadamente 58%
de la línea de voltaje se aplica a cada Funciones programables Caballos de fuerza del motor
bobinado. El motor desarrolla 33% de 1/3-40 Hp 1/3-40 Hp 1/3-50 Hp 1/3-50 Hp 1/3-50 Hp
torque de arranque de voltaje completo
Las entradas, las salidas, los
(0.74-29.42 Kw) (0.74-29.42 Kw) (0.74-36.78 Kw) (0.74-36.78 Kw) (0.74-36.78 Kw)
y consume 33% de la corriente normal temporizadores y los diodos
bloqueada por el rotor de la línea. fotoemisores virtuales son
Después de un retardo de tiempo programables por medio de
ajustable (durante el cual acelera el la visualización de la pantalla
motor), se vuelve a conectar para el
funcionamiento normal.
táctil. Estándares
Métodos de arranque y certificaciones
Características del Hay cuatro métodos de arranque
del controlador: Auto, Manual,
producto Arranque remoto y Arranque de Los Controladores de la bomba
Combinación de controladores la bomba. compensadora JOCKEY Touch
del motor cumplen los requerimientos
Diagnósticos/estadísticas
Todos los controla- de la más reciente edición de
Se pueden supervisar ocho
dores JOCKEY Touch NFPA 20 así como los requisitos
parámetros de diagnóstico
vienen suministrados de los estándares europeos
con combinación de
y siete de estadísticas.
de cumplimiento (marca CE).
controladores de motor Valores de referencia de la
EATON, que combinan Cumplen o exceden los requisitos
el interruptor de circuito alarma de UL 508 [Underwriters
y la sobrecarga en un Se pueden programar cuatro Laboratories (UL)] y están
solo dispositivo. valores de referencia de la aprobados por [Canadian
alarma desde el submenú Standards Association (CSA)].
Alarm Setpoints (Valores de
referencia de la alarma).