Split Case Fire Pumps: Fairbanks Nijhuis
Split Case Fire Pumps: Fairbanks Nijhuis
Horizontal split case pumps are the most common type of fire
pump. These pumps are specifically designed and tested for
fire service applications where reliability of performance is of
vital importance. Split case pumps are characterized by:
• Rugged construction;
• Efficient operation.
Split case fire pumps are specified when the source of water
is located above the surface of the ground and provides a
positive suction pressure to the pump at any performance point.
Single-stage or multistage pumps are available dependent upon
discharge pressure requirements.
In addition to horizontal split case pumps, Fairbanks Nijhuis
Fairbanks Nijhuis split case fire pumps are built per the also offers split case performance in a vertical format. Vertical
rigid standards of NFPA 20 and are listed by Underwriters fire pumps provide distinct advantages over horizontal pump
Laboratories (UL) and approved by Factory Mutual (FM). constructions.
2
SPLIT CASE FIRE PUMPS
1
Pump Features
7
2
8 15 16
14
17
3 9 13
10
5 11 12
6 18
VERTICAL HORIZONTAL
SPLIT CASE SPLIT CASE
1. Computer Machined 8. Internal Water Seal Passages 14. Split Case Design
major components with 360 degree registered between volute and stuffing box cannot simplifies disassembly. The suction and
fits to assure concentricity of parts. be damaged. discharge piping and shaft alignment are
not disturbed.
2. Integral Bearing Arms 9. Interwoven, Graphite
eliminate bearing misalignment and Impregnated T.F.E. 15. O-Ring Sealed Shaft Sleeves
simplify maintenance. prevent corrosion of the shaft. This eliminates
diagonally cut packing rings seal
the need for stainless steel shafts.
the pump shaft.
3. Enclosed Impeller Design
provides high efficiency and performance. 10. Stuffing Boxes 16. Case Wearing Rings
and throttle bushings protect the
are extra deep for proper sealing. Split packing
casing from wear and are easily and
4. Dynamically Balanced Impeller glands simplify packing maintenance.
inexpensively replaced.
is keyed to the shaft and secured by adjustable
shaft sleeves. 11. Double Row Thrust 17. Bronze Shaft Sleeve
ball bearing.
prevents shaft wear, is slip fit over the shaft,
5. Double Suction Impeller keylocked, and extends the entire length
balances hydraulic thrust loads. 12. Grease Seals of the seal box.
and nonsparking neoprene rotating slingers
6. Cast Iron Drip Rim Base protect both bearings during pump operation
18. Certified Performance Test
directs condensation and any stuffing box and washdown.
leakage to drain. with Positive Suction Pressure
is provided for each fire pump for customer
13. Bearings approval. Pumps are also hydrostatically tested
7. Short Bearing Span selected for 50,000 hour minimum life
per NFPA 20 at no less than 250 psi.
holds shaft deflection to .002" at face of at maximum load. Average bearing life
stuffing box at maximum load. 5 x minimum.
www.FairbanksNijhuis.com 3
Fire Pump Feature Selector
Standard Optional
• Bronze fitted pump construction • Ductile iron casings (available in selected 1800 and 1900 models)
• Bronze shaft sleeves • Some models available in 316 SST, duplex and super duplex
• Corrosion-resistant lantern rings* • External bypass line from casing to stuffing boxes
(optional on Model 1800s and 1900s, standard on Model 2800s and 5800s)
• Bronze stuffing box bushings
• Formed steel drip-rim base (horizontal electric driven units only)
• Bronze or stainless steel glands
• 15' Suction lift test to verify performance at 150% of rated flow
• Interwoven graphite-impregnated T.F.E. packing rings
• Available accessories include valves, headers, main relief valves, increasers and
• Cast integral bearing arms (most models) reducers, waste cones, and more.
• Regreaseable ball bearings
• Coupling guard
VERTICAL PUMPS PROVIDE
SUCTION IN-LINE PIPING IN ANY DIRECTION SUCTION
• Suction and discharge gauges with shutoff cocks STANDARD
(ALSO AVAILABLE RIGHT- OR LEFT-HAND)
OPTIONAL
RIGHT-HAND ROTATION LEFT-HAND ROTATION
(TOP VIEW HORIZONTAL PUMP) (TOP VIEW HORIZONTAL PUMP)
ST
IT
DR
UT
HY
19 17
www.FairbanksNijhuis.com
Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
FMF-02-1048 04/01/16 © 2016 Pentair Ltd. All Rights Reserved.
Customer : Engie Services Perú Pump Performance Curve
S.A. Encompass 2.0 - 20.3.5
Project name : 750 195 SC D H.
INDIGO
300
270
240
210
14.94 in
180
Head - psi
150
120
90
60
30
240
180
Power - hp
Power
120
60
0
0 200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400
Flow - USgpm
Max Shutoff per NFPA : 273.0 psi Power driver, minimum : 164 hp
General Arrangement
Pump Data
Series Horizontal Splitcase
Model 5" 1823AF
Size 5x6x15
Flow 750.0 USgpm
Rated Pressure 195.0 psi.g
RPM 2600 rpm
Rotation Right handed
Liquid Type Water
Discharge Size 5.00 in
Suction Size 6.00 in
Impeller Diameter 15.00 in
Connection Type Flanged
Base Type Structural steel base
- -
Pump Materials of Construction
Pump Bronze fitted with Ductile Iron casing
Shaft Carbon Steel AISI C1046
Engine Data
Engine Model JU6H-UF52
Power Rated 210 hp
Power Available 210 hp
Speed 2600 rpm
Tier T1
Manufacturer Clarke
Cooling Type Heat exchanger
Heater Voltage 230 Volt
Muffler Type Commercial Grade, 5" (Qty 1)
Exhaust Connection Flanged
Battery Type Lead acid
Battery Voltage 12 Volt DC
Site Information
EY EL EX DSL CP W EW EW1 EW2 EZ YY X
Elevation 300.0 ft
45.40 48.00 25.60 15.60 28.50 16.00 37.10 16.40 20.70 4.90 15.00 13.25
Temperature 77.00 deg F
S Z HD HG HP HF1 HY HB HP1 HE HA Estimated Weights
6.25 6.25 20.00 6.00 5.00 39.00 14.00 88.00 1.00 30.00 32.00 Pump 1,000.0 lb
Driver 2,050.0 lb
NOTES: Quote Information
Not for construction, installation, or application purposes unless certified. Customer Engie Services Perú S.A.
All dimensions are in inches Customer Quote 1251003
Dimensions may vary ± .38" (10mm) due to normal manufacturing tolerances. Job Name 750 190 SC D H. INDIGO
Bases are designed to be completely filled with grout. Market -
See configuration for estimated total weight. Quote Item 001
For additional dimensions, refer to engine manufacturer's website. Quote Date 08 Oct 2020
MODELS
JU6H-UFD0 JU6H-UF34 JU6H-UF58
R JU6H-UF62 JU6H-UF94
JU6H-UFD2 JU6H-UFM8 JU6H-UF50 JU6H-UFAAQ8 JU6H-UFAAS0
JU6H-UF30 JU6H-UFM0 JU6H-UF52 JU6H-UFAAPG JU6H-UFAAT0
JU6H-UF32 JU6H-UFM2 JU6H-UF54 JU6H-UFAARG JU6H-UFAAT2
UL/FM - cUL APPROVED RATINGS BHP/KW JU6H-UF60 JU6H-UF84 JU6H-UFAAT8
ENGINE EQUIPMENT
EQUIPMENT STANDARD OPTIONAL
Air Cleaner Direct Mounted, Washable, Indoor Service with Drip Shield Disposable, Drip Proof, Indoor Service Outdoor Type,
Single or Two Stage (Cyclonic)
Alarms Overspeed Alarm & Shutdown, Low Oil Pressure, Low & High Low Coolant Level, Low Oil Level, Oil FIlter Diferential
Coolant Temperature, Low Raw Water Flow, High Raw Water Pressure, Fuel Filter Diferential Pressure, Air Filter
Temperature Restriction
Alternator 12V-DC, 42 Amps with Poly-Vee Belt and Guard 24V-DC, 40 Amps with Poly-Vee Belt and Guard
Coupling Bare Flywheel Listed Driveshaft and Guard: UFD0, UFD2, UF30, UF32,
UF34, UFM8, UFM0, UFM2, UFS8, UF50, UF52, UF54,
UF60, UF62, UF84 - CDS30-S1;
UFAAPG, AAQ8, AARG, AAT0, AAT8 -CDS50-SC;
UF94 - SC61A-L at 2800 & 3000 RPM;
AAT0, AAT2 - SC81A at 2350 & 2600 RPM
Engine Heater 115V-AC, 1360 Watt 230V-AC, 1360 Watt
Exhaust Flex Connection SS Flex, 150# ANSI Flanged Connection, 5” SS Flex, 150# ANSI Flanged Connection, 6”
(AAT0, AAT2, UF94: SS Flex, 150# ANSI Flanged Connection, 6”)
Exhaust Protection Metal Guards on Manifolds and Turbocharger
Flywheel Housing SAE #3
Flywheel Power Take Of 11.5” SAE Industrial Flywheel; Connection
Fuel Connections Fire Resistant, Flexible, Supply and Return Lines SS, Braided cUL Listed, Supply and Return Lines
Fuel Filter Primary Filter and Priming Pump
Fuel Injection System Direct Injection
Fuel Solenoid 12V-DC Energized to Stop (ETS) 24V-DC Energized to Stop (ETS)
Governor, Speed Constant Speed, Mechanical
Heat Exchanger Tube and Shell, 60 PSI (4 BAR), NPT(F) Connections - Sea Water
Compatible
Instrument Panel NEMA Type 2, Powder Coated Steel Construction, English and 316 Stainless Steel NEMA 4X/IP66
Metric, Tachometer, Hourmeter, Water Temperature, Oil Pressure
and (2) Voltmeters
Junction Box Integral with Instrument Panel; For DC Wiring Interconnection to
Engine Controller
Lube Oil Cooler Engine Water Cooled, Plate Type
Lube Oil Filter Full Flow with By-Pass Valve
Lube Oil Pump Gear Driven, Gear Type
Manual Start Control On Instrument Panel with Control Position Warning Light
Overspeed Control Electronic with Reset and Test on Instrument Panel
Raw Water Cooling Loop - w/Alarms Galvanized Seawater, All 316SS, High Pressure
Raw Water Solenoid Operation Automatic from Fire Pump Controller and from Engine Instrument Not Supplied (for Vertical Turbine Fire Pump Applications)
Panel (for Horizontal Fire Pump Applications)
Run - Stop Control On Instrument Panel with Control Position Warning Light
Starters Two (2) 12V-DC Two (2) 24V-DC
Throttle Control Adjustable Speed Control, Tamper Proof
Water Pump Centrifugal Type, Poly-Vee Belt Drive with Guard
Abbreviations: DC - Direct Current, AC - Alternating Current, SAE - Society of Automotive Engineers, NPT(F) - National Pipe Tapered Thread (Female), SS - Stainless Steel
Base Engine Power Curve Number Base Engine Power Curve Number
350 Series UL Listed and FM Approved 350 Series Non-Emissionized
6 Cylinder 6 Cylinder Built in USA
Heat Exchanger Cooled Heat Exchanger Cooled UL Listed and FM Approved
Speciications and information contained in this brochure is subject to change without notice.
R
100 Progress Place, Cincinnati, OH 45246 Grange Works, Lomand Rd, Coatbridge, ML5-2NN
United States of America United Kingdom
Tel +1-513-475-3473 Fax +1-513-771-8930 Tel +44-1236-429946 Fax +44-1236-427274
ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77°F (25°C) AIR INLET TEMPERATURE
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)
THIS DRAWING AND THE INFORMATION CREA TED DA TE CREA TED
HEREIN ARE OUR PROPERTY AND MAY
BE USED BY OTHERS ONLY AS 08/23/00
AUTHORIZED BY US. UNPUBLISHED --
ALL RIGHTS RESERVED UNDER THE
COPYRIGHT LAWS.
ENGINE MODEL JU6H-UF52
DRA WING NO . REV
John W hitney 23AUG00 C13495 A
JU6H-UF52
INSTALLATION & OPERATION DATA (I&O)
USA Produced
Basic Engine Description
Engine Manufacturer ......................................................................................................................................................
John Deere C o.
Ignition Type ......................................................................................................................................................
C ompression (Diesel)
Number of C ylinders ......................................................................................................................................................
6
Bore and Stroke - in (mm) ......................................................................................................................................................
4.19 (106) X 5 (127)
Displacement - in³ (L) ......................................................................................................................................................
415 (6.8)
C ompression Ratio ......................................................................................................................................................
17.0:1
Valves per cylinder
Intake ......................................................................................................................................................
1
Exhaust ......................................................................................................................................................
1
C ombustion System ......................................................................................................................................................
Direct Injection
Engine Type ......................................................................................................................................................
In-Line, 4 Stroke C ycle
Fuel Management C ontrol ......................................................................................................................................................
Mechanical, Rotary Pump
Firing Order (C W Rotation) ......................................................................................................................................................
1-5-3-6-2-4
Aspiration ......................................................................................................................................................
Turbocharged
C harge Air C ooling Type ......................................................................................................................................................
None
Rotation, viewed from front of engine, C lockwise (C W) ......................................................................................................................................................
Standard
Engine C rankcase Vent System ......................................................................................................................................................
Open
Installation Drawing ......................................................................................................................................................
D536
Weight - lb (kg) ......................................................................................................................................................
1657 (752)
Page 1 of 2
C 133697 Rev G
* All footnotes are at the bottom of Page 2 DSP 21NOV19
JU6H-UF52
INSTALLATION & OPERATION DATA (I&O)
USA Produced
Exhaust System (Single Exhaust Outlet) 2350 2600
Exhaust Flow - ft.³/min (m³/min) ......................................................................................................................................................
1359 (38.5) 1496 (42.4)
Exhaust Temperature - °F (°C ) ......................................................................................................................................................
977 (525) 953 (512)
Maximum Allowable Back Pressure - in H2O (kPa) ......................................................................................................................................................
25 (6.2) 25 (6.2)
Minimum Exhaust Pipe Dia. - in (mm) ³ ......................................................................................................................................................
5 (127) 5 (127)
Lubrication System
Oil Pressure - normal - lb/in² (kPa) ......................................................................................................................................................
40 (276) - 60 (414)
Low Oil Pressure Alarm Switch - lb/in² (kPa) ......................................................................................................................................................
20 (138)
In Pan Oil Temperature - °F (°C ) ......................................................................................................................................................
220 (104) - 245 (118)
Total Oil C apacity with Filter - qt (L) ......................................................................................................................................................
19.7 (18.6)
NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. ¹ Derate 3% per every 1000 ft. 304.8m above 300 ft. 91.4m and derate 1%
for every 10°F 5.55 °C above 77°F 25°C. ² Positive and Negative Cables Combined Length. ³ Minimum Exhaust Pipe Diameter is based on: 15 feet of pipe, one
90° elbow, and one Industrial silencer. A Back-pressure flow analysis must be performed on the actual field installed exhaust system to assure engine maximum
allowable back pressure is not exceeded. See Exhaust Sizing Calculator on www.clarkefire.com. { } indicates component reference part number.
Page 2 of 2
C 133697 Rev G
DSP 21NOV19
JU4H, JU4R & JU6H, JU6R ENGINE MODELS
ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner Cylinder Head
Type…………..………….. .. Indoor Usage Only Type…….. …………………Slab 2 Valve
Oiled Fabric Pleats Material……………………. Annealed Gray Iron
Material……..…..…….………Surgical Cotton
Aluminum Mesh Cylinder Liners
Type…….. …………………Centrifugal Cast, Wet Liner
Air Cleaner - Optional Material………………..….…Alloy Iron Plateau, Honed
Type…………………………. Canister
Material………………………Pleated Paper Fuel Pump
Housing………………..…… Enclosed Type…………………………Diaphragm
Drive…………………………Cam Lobe
Camshaft
Material………….………….. Cast Iron Heat Exchanger (USA) - JU4H & JU6H Only
Chill Hardened Type…………………………Tube & Shell
Location…………...….……. In Block Materials
Drive……………….………..… Gear, Spur Tube & Headers……………Copper
Type of Cam…………..….... Ground Shell…………………………Copper
Electrode……………………Zinc
Charge Air Cooler (JU6H-60,62,68,74,84, 94, T8, T0,
T2, ADK0, AD58, ADNG, ADN0, ADQ0, ADR0, AAQ8,
AARG, ADP8, ADP0, ADT0, AD88, ADR8, AD98,
ADS0, ADW8, ADX8, AD98 only)
Type……….. ..…………….Raw Water Cooled Heat Exchanger (UK) - JU4H & JU6H Only
Materials (in contact with raw water) Type…………………………Tube & Bundle
Tubes……… …………………… 90/10 CU/NI
Headers …………………… 36500 Muntz Materials
Covers …………………… 83600 Red Brass Tube & Headers……………Copper
Plumbing …………………… 316 Stainless Steel/ Brass Shell………..……………. Aluminum
90/10 Silicone
Injection Pump
Charge Air Cooler (JU6R-AA67, 59, 61, PF, Q7, RF, Type……………………….. Rotary
S9, 83 only) Drive…………………………Gear
Type…...……………………Air to Air Cooled
Materials Lubrication Cooler
Core…………………………Aluminum Type…………………………Plate
Cylinder Block
Type…………………………… One Piece with
Non-Siamese Cylinders
Material………………………Annealed Gray Iron
C13615 14NOV18
JU6H-UF52
Stationary Fire Pump Engine Driver
EMISSION DATA
EPA 40 CFR Part 60
6 Cylinders
Four Cycle
Lean Burn
Turbocharged
Notes:
1) 6068TF220 Base Engine Model manufactured by John Deere Corporation.
For John Deere Emissions Conformance to EPA 40 CFR Part 60 see Page 2 of 2.
2) The Emission Warranty for this engine is provided directly to the owner
by John Deere Corporation. A copy of the John Deere Emission Warranty can
be found in the Clarke Operation and Maintenance Manual.
3) Engines are rated at standard conditions of 29.61in. (7521 mm) Hg barometer
and 77°F (25° C) inlet air temperature. (SAE J1349)
4) PM is a measure of total particulate matter, including PM 10 .
CLARK E
FIRE PROTECTION PRODUCTS
3133 EAST KEMPER ROAD
C131852 REV.C CINCINNATI, OH 45241
01NOV 07 KRW PAGE 1 OF 2
John Deere Power Systems
3801 W. Ridgeway Ave., PO Box 5100
Waterloo, Iowa USA 50704-5100
31 October 2007
Subject: Fire Pump Ratings – Conformance to EPA 40 CFR Part 60 (NSPS requirements)
All John Deere stationary fire pump engines conform to the requirements of 40 CFR Part 60. All such
engines include an emission label, stating the engine conforms to the requirements of 40 CFR Part 60. An
example of the emission label is show below:
This label applies to all of the following engine models, sold to Clarke Fire Protection, for use in stationary
fire pump applications:
All engines conforming to 40 CFR Part 60 (identified by emission label, as shown above) are covered under
the emissions warranty of 40 CFR Part 89.
Sincerely,
Kyle J. Tingle
Regional Sales Manager, JDPS
Page 2 of 2
JU6H-UF52
FIRE PUMP DRIVER
NOISE DATA
Mechanical Engine Noise *
Octave Band
* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.
** Values above are provided at 23ft (7m), 90° horizontal, from a vertical exhaust outlet and does not include noise created mechanically by the engine.
The above data reflects nominal values for a typical engine of this model, speed and power in a free-field environment, tested at a no-load condition.
Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect the overall noise
levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.
Motor diésel
Controladores de bombas contra incendios
Tipos de comunicación Relés de salida estándar Alimentación/voltaje
USB Todos los relés de salida estándar son de Suministro de voltaje universal
El puerto USB se utiliza para descargar 8 amperios, DPDT. El controlador se puede alimentar con
el historial de mensajes, estadísticas, voltajes de suministro de 0 VAC a
diagnósticos, estado y datos de configuración t Future #1 (Futuro No. 1) 240 VAC al conectarse a tres terminales de
del controlador en una unidad de disco USB. entrada L, N, G que se encuentran en la
t Future #2 (Futuro No. 1)
El puerto USB también se puede utilizar para parte inferior izquierda del tablero del
t Low Fuel (combustible bajo) motor.
cargar mensajes personalizados, idiomas t Modo Auto (automático)
adicionales y actualizar el firmware
t Common Alarm (Alarma común)
del microprocesador.
Relés de salida opcionales
Descripción del producto Ethernet
Se puede conectar una computadora
Existe la posibilidad de agregar hasta ocho
salidas de relé adicionales, por medio de
Los Controladores de bomba contra incendios externa al controlador Diesel Plus por medio cuatro tableros de salida de relé opcionales
DIESEL Plus de Eaton están diseñados para del puerto Ethernet opcional. Una página que se montan en la configuración a presión.
controlar y supervisar los motores de bomba Web integrada muestra el estado actual Cada tablero contiene un máximo de 2 relés
contra incendios diésel de 12 o 24 voltios del controlador, así como todas las lecturas adicionales. Salida doble
y se encuentran entre los controladores actuales, puntos de ajuste e historial. La salida de 12 o 24 VDC se puede seleccionar
disponibles de motor diésel técnicamente por medio del interruptor DIP que se
más avanzados. encuentra en los cargadores de la batería.
Son una versión mejorada de la Serie FD100 Modbus Nota: Cada controlador está establecido en
basada en el microprocesador original Los controladores de bomba contra incendios fábrica para 12 VDC. Si se necesitan 24 VDC
de los controladores de motor diésel. La Diesel Plus tienen la opción de comunicarse de fábrica, se debe indicar en la información
programación es directa debido al uso del con los sistemas utilizando el nivel Regular de del pedido.
firmware principal y la estructura del menú Modbus (incluye los modos de transmisión
utilizada en la Serie LMR Plus de controladores RTU y ASCII). Los ajustes de comunicación Filtro de línea
eléctricos. los puede configurar el usuario a través del Un filtro de línea incorporado en el tablero
menú de configuración de Diésel Plus. del motor se utiliza para reducir/eliminar
El controlador se puede pedir con la opción
Relé de funcionamiento del motor los transientes de voltaje externo entrante.
para mostrar y transmitir valores y estados
de corriente, a pedido, desde varios protocolos El tablero de E/S de energía aloja un relé de
Conexiones de campo funcionamiento del motor de 10 amperios
Desconexión de alimentación de AC
de software.
que se utiliza para propósitos de alarma o para Un interruptor que se encuentra dentro del
Desde el puerto de comunicación opcional Entradas estándar energizar persianas externas. controlador en el Tablero del motor se utiliza
Ethernet se puede acceder a una página Web t Remote Start (Arranque remoto) para encender y apagar la alimentación de
integrada para recuperar los reportes de t Fuel Spill (Derrame de combustible) Relé de alarma común AC a la unidad. Se enciende cuando recibe
diagnóstico e historial. El puerto serial RS485 t Deluge Valve (Válvula de Inundación) El controlador FD120 tiene un relé de alarma energía.
opcional se puede utilizar para conexión t Low Suction (Succión baja)
t Interlock On (Interbloqueo activado)
común que se desenergiza cada vez que hay Desconexión de la alimentación
directa a una computadora para transferencia condiciones de alarma. Este relé se energiza
de datos. t Pump Start (Arranque de la bomba) de DC
bajo condiciones normales y tiene una
t Low Fuel (Combustible bajo) El tablero del motor aloja dos interruptores
indicación de estado de diodo fotoemisor.
t Entradas programables (9) automáticos en tablero que se utilizan para
Pantalla LCD t FUEL INJECTION MALFUNCTION t AC Failure Alarm (Alarma de falla de AC)
El tablero de la pantalla del controlador (MAL FUNCIONAMIENTO EN t AC Fail to Start (Falla de arranque
contiene una pantalla LCD de 4 líneas por de AC)
LA INYECCIÓN DE COMBUSTIBLE)
40 caracteres de ancho, con iluminación
trasera, que tiene la capacidad de generar t ECM WARNING (ADVERTENCIA
varios idiomas. La pantalla muestra la presión DEL ECM)
Cajas
actual del sistema, hora y fecha, voltaje de t ECM FAILURE (FALLA DEL ECM)
salida del cargador y cualquier mensaje Capacidades
t HIGH RAW WATER TEMP. (TEMP. ALTA Todos los controladores FD120 vienen
personalizado, alarma o valores
del temporizador. DE AGUA NO PROCESADA) estándar con cajas NEMA 2 a menos que
t LOW ENGINE TEMPERATURE se pida algo distinto.
(TEMPERATURA BAJA DEL MOTOR)
Las opciones disponibles incluyen: Estándares y certificaciones
NEMA 3R, 4, 4X, 12.
t FUEL SPILL (DERRAME COMBUSTIBLE) Los controladores de bomba contra incendios
t One Programmable LED (Un diodo Tamaño reducido del motor diésel FD120 cumplen o superan
fotoemisor programable) Un diseño interno aerodinámico ha permitido los requisitos de Underwriters Laboratories,
que el tamaño total de modelos anteriores de Factory Mutual Research (FM), la Asociación
controladores DIESEL Plus se reduzca. Consulte Canadiense de Estándares, el código de
Estadísticas los dibujos de medidas en nuestro sitio Web. construcción de la Ciudad de Nueva York,
Se registran hasta 26 puntos estáticos para la marca CE y U.B.C. /requisitos sísmicos
proporcionar una revisión rápida de cómo de C.B.C, se construyen de acuerdo con los
está operando el sistema. Las estadísticas se Especificaciones técnicas estándares NFPA 20.
PVMX1
through
PVMX33
Only
Ft. H[m]
1312 400
✤ ✁ ✂✄☎
984 300 60 Hz
656 200
PVM150
PVMX150
PVM120
328 100 PVMX120
262 80
PVM3 PVM10 PVM20 PVM45 PVM90
197 60 PVMX3 PVMX10 PVMX20 PVMX45 PVMX90
131 40
PVM1 PVM5 PVM15 PVM33 PVM64
98 30 PVMX1 PVMX5 PVMX15 PVMX33 PVMX64
66 20
APPLICATION
Multiple Connection Options
Flanged, grooved or
▶▶ Water supply ▶▶ Irrigation
NPT connections ▶▶ Pressure ▶▶ High pressure washes
boosting systems ▶▶ Liquid transfer
▶▶ Water treatment/ ▶▶ Boiler feed
filtration ▶▶ Jockey pumps
Fairbanks Nijhuis®
3501 Fairbanks Avenue, Kansas City, Kansas 66106 · Tel. 913-371-5000
www.FairbanksNijhuis.com FM-02-1544 (01/23/15)
Customer : Engie Services Perú Jockey Pump Curve
S.A. Encompass 2.0 - 20.3.5
Project name : 750 190 SC D H.
INDIGO
Curve efficiencies are typical. For guaranteed values, contact factory
250
225
200 PVM(I/X)1-17
175
150
Head - psi
125
100
75
50
25
30
NPSH3 - ft
NPSH3
15
2.4
Power
1.8
Power - hp
1.2
0.6
0.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Flow - USgpm
General Arrangement
Pump Data
Model PVM1-17
Stages 17
Flow 5.00 USgpm
Head 195.0 psi
Rotation Right Hand
Suc/Disch Size 0.00 in
Connection Suc/Disch 1.25'' ANSI 250# flg w/ 1.25'' NPT female
Motor Data
Power 2.00 hp
Phase 3
Frequency 60 Hz
Voltage 380
Speed 3500
Frame Size 56CZ
Efficiency EPAct
Enclosure TEFC
Estimated Weights
Pump 106.0 lb
Motor 0.00 lb
Additional Options
A B C D E F
21.80 12.10 7.20 2.10 35.90 7.20