Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

ÜNTEL KABLOLARI SANAYİ VE TİCARET A.Ş.

DEMİRCİLER KÖYÜ MAKİNE OSB. 97 PARSEL


41455 DİLOVASI / KOCAELİ

DATE : 20.01.2021

TYPE OF CABLE : M2XCH flex [FI] 5G25 mm² (Black)


RELATED STANDARD : IEC 60092-353, IEC 60754
LENGTH OF CABLE : 199 m.
DRUM NUMBER : 941206161
CUSTOMER ORDER NO : N5523/2020/1202
ORDER NO : E201272
QUALITY CONTROL REPORT
STANDARD ÜNTEL
A. ELECTRICAL TESTS

A.1. Conductor resistance 20oC DC. Ohm/km max. 0,780 0,775


A.2. High voltage Test 5 minutes A.C. kV 3,5 OK
A.3. Insulation Resistance Mohm.km (20 ºC) 350 ≥350

B. PHYSICAL TESTS

B.1. Conductor Control - OK


B.2. Wall Thickness of Insulation nom. mm 0,90 0,98
B.3. Wall Thickness of Inner Sheath nom. mm 0,80 0,90
B.4. Copper Wire Braiding Diameter nom. mm 0,30 0,30
B.5. Wall Thickness of Outer Sheath nom. mm 1,90 1,95
B.6. Outer Diameter nom. mm - 30,00

C MECHANICAL TESTS

C.1. Tensile Strength ( before ageing )(insulation) min. N/mm² 12,5 14,6
C.2. Elongation ( before ageing )(insulation) min % 200 315
C.3. Tensile Strength ( after ageing )(insulation) max variation % ±25 -5
C.4. Elongation ( after ageing )(insulation) max variation % ±25 -4
C.5. Tensile Strength ( before ageing )(outer sheath) min. N/mm² 9 11
C.6. Elongation ( before ageing ) (outer sheath) min % 120 185
C.7. Tensile Strength ( after ageing ) (outer sheath) Max. Variation. % ±30 -4
C.8. Elongation ( after ageing ) (outer sheath) Max Variation. % ±30 -9
C.9. HOT-SET Test <%(175,15)max OK
RESULT OK
QUALITY CONT.MANAGER

OK
KODU: FR 32 REV: O REV.TAR. 01.10.2003 SAYFA NO: 1/1