Professional Documents
Culture Documents
(Water Treatment & Cleaning System)
(Water Treatment & Cleaning System)
SECTION 15997
PAGE
PART 1 GENERAL 2
PART 2 PRODUCTS 3
PART 3 EXECUTION 5
3.1 Installation 5
3.2 Systems Cleaning 5
PART 1 GENERAL
The chemicals used and methods of feeding shall comply with all code
requirements and local health codes or other standards and sound practice.
1.4 SUBMITTALS
Supply one set of test kits to run following analysis on site, these kits
shall be handed to the owner:
- PH
- T.D.S.
- Chloride
- Ca H
- Cu
- Fe
- Chemical residuals
PART 2 PRODUCTS
The chemicals shall not have any effect on non-metallic materials such as
rubber, etc.
Chilled water system shall be equipped with single shot chemical feeder
with internal lining to prevent corrosion.
2.2.1 Closed System: Water treatment for the chilled water system shall be
carried out manually using a chemical pot feeder, of the bypass type
designed for feeding chemical inhibitor solution to system.
Unit shall be complete with strainer, hose bib, isolating valves, air relief
valve, throttling valve. Unit and accessories shall be made of suitable
materials for the chemicals used.
The amount of corrosion inhibitor required shall depend on the system water
content and the concentration level of the chemical as recommended by the
manufacturer. Water analysis and addition of inhibitors required, shall be
carried out once a week.
For each system corrosion and sitting rates shall be measured by using
suitable corrosion test coupons representing the metal in the circuit,
according to ASTM corrosion test procedure D 935-49 and A 224-46.
Closed System:
pH 10 min
3.1 INSTALLATION
All water systems shall be thoroughly flushed-out first with water and then
with the approved cleaning chemicals to remove dope, flushing compounds,
cutting oils and other loose extraneous materials. All valves shall be
blocked open and circulation shall be with external pump during application
of cleaning chemicals and with the system pump in the final flush.
- Chillers.
- Air handling units.