Professional Documents
Culture Documents
Emerson Discharge Temperature Control Valve Installation: March 2020
Emerson Discharge Temperature Control Valve Installation: March 2020
As the busy season approaches, contractors and technicians need quick access to
product information. That’s why we have prepared the attached instructions on how to
easily install a discharge temperature control (DTC) valve on Copeland™ scroll
compressors.
In addition to the instructions attached, please note the following when installing DTC
valves on Copeland digital scroll models. The thermistor sensing bulb is in a different
location when compared to a standard model - see Image 1. There are three steps to
remember when installing a DTC valve on ZFD**KVE models.
1. Remove remote bulb cap and replace it with the DTC bulb.
2. Use either the 1/2” or 5/8” thermostat provided in Kit 998-1000-52 in the control circuit.
3. Use the 5K ohm resistor on the IDCM T1 and T2 terminals.
DOWNLOAD INSTRUCTIONS
The table below is a cross reference showing demand cooling kits transitioning to DTC
Valve Kits.
*Digital Model