EXTRANA
CABLE

NYAF 450/750 V
SNI 04-6629.3; SNI 0225; IEC 60227-3
(Flexible Copper Conductor, PVC Insulated)

NYAF is used fixed internal wiring with low mechanical stress for electrical equipments, machineries,
distribution panels, luminaires and other electrical appliances used in dry indoor premises. Also used
as substitute for NYA.

CONSTRUCTION DATA
Nominal Overall Net
Diameter Weight Bending Standard
Size Insulation
Diameter delivery length
Thickness Approximate

mm² mm mm kg/km mm mtr


1.5 0.7 3.12 22 19 100/coil
2.5 0.8 3.76 34 23 100/coil
4 0.8 4.28 49 26 100/coil
6 0.8 4.84 68 29 100/coil
10 1.0 6.25 118 38 100/coil
16 1.0 8.05 179 48 100/coil
25 1.2 9.90 275 59 1000/drum
35 1.2 11.24 371 67 1000/drum
50 1.4 13.32 526 80 1000/drum
70 1.4 15.24 717 91 1000/drum
95 1.6 17.35 930 104 1000/drum
120 1.6 19.56 1213 117 1000/drum
150 1.8 21.86 1517 131 1000/drum
185 2.0 23.99 1822 144 1000/drum
240 2.2 27.21 2364 163 1000/drum
300 2.4 30.97 3089 186 1000/drum
400 2.6 35.23 4045 211 1000/drum

ELECTRICAL DATA
Min. DC Ins ulation Max. Current Carrying Max. Short
Max . Co nductor Resistance
Size Resistance Capacity at 30ºC Inductance circuit current
DC at 20ºC AC at 70 ºC at 20ºC at 70ºC in air In pipe at 1 sec.

mm² Ω/km Ω/km M.Ω.km M.Ω.km A A mH/km kA

1.5 13.3 15.914 50 0.0100 24 15 0.320 0.17


2.5 7.98 9.548 50 0.0090 32 20 0.309 0.29
4 4.95 5.923 50 0.0077 42 25 0.290 0.46
6 3.30 3.948 40 0.0065 54 33 0.276 0.69
10 1.91 2.286 30 0.0065 73 45 0.274 1.15
16 1.210 1.448 30 0.0050 98 61 0.260 1.84
25 0.780 0.933 30 0.0050 129 83 0.257 2.88
35 0.554 0.663 20 0.0045 158 103 0.249 4.03
50 0.386 0.463 20 0.0040 198 132 0.248 5.75
70 0.272 0.326 20 0.0035 245 165 0.240 8.05
95 0.206 0.248 20 0.0035 292 197 0.239 10.93
120 0.161 0.194 20 0.0032 344 235 0.235 13.80
150 0.129 0.156 20 0.0032 391 - 0.235 17.25
185 0.106 0.129 20 0.0032 448 - 0.235 21.28
240 0.0801 0.0988 20 0.0032 525 - 0.233 27.60
300 0.0641 0.0800 20 0.0030 608 - 0.232 34.50
400 0.0486 0.0620 20 0.0028 726 - 0.231 41.20

www.extranacable.com
®
EXTRANA
CABLE
NYMHY 300/500 V
SNI 04-6629.5; IEC 60277-5; SNI 0255
(Flexible Copper Conductor, PVC Insulated, PVC
Sheathed)

NYMHY is used for power cord or internal wiring with low mechanical stress for
electrical equipments, machineries, luminaires and other portable appliances used in
dry indoor premises.
It is suitable for installation where the cable is permanently exposed in humid
environment, which installation can be in tray or under plaster. Suitable for industrial
three phase 380 - 415 VAC or single phase 220 - 240 VAC multipurpose applications,
EXTRANA CABLE

inherently flame retardant in compliance with IEC 60332-1

CONSTRUCTION DATA
Nominal Thickness Overall Net
Diameter Weight Bending
Core Size
Diameter
Insulation Sheath Approximate

- mm² mm mm mm kg/km mm
0.75 0.6 0.8 6.5 65 39
1 0.6 0.8 6.8 74 41
2
1.5 0.7 0.8 7.7 98 46
2.5 0.8 1.0 9.4 152 56
0.75 0.6 0.8 6.8 76 41
1 0.6 0.8 7.2 88 43
3
1.5 0.7 0.9 8.4 121 50
2.5 0.8 1.1 10.2 188 61
0.75 0.6 0.8 7.5 90 45
1 0.6 0.9 8.1 110 49
4
1.5 0.7 1.0 9.4 151 56
2.5 0.8 1.1 11.1 229 67
Core Identification: 0.75 0.6 0.9 8.3 110 50
2 cores : Black, Blue
1 0.6 0.9 8.8 129 53
3 cores : Green-yellow, Brown, Blue 5
4 cores : Green-yellow, Brown, Black, Grey 1.5 0.7 1.1 10.4 183 63
5 cores : Green-yellow, Brown, Black, Grey, Blue
2.5 0.8 1.2 12.4 278 74

ELECTRICAL DATA

Size Max. Conductor Resistance Max. Current Carrying Max. Short circuit
Min. DC Insulation
Core
Resistance at 20ºC Capacity at 30ºC current at 1 sec.
DC at 20ºC AC at 70ºC

- mm² Ω/km Ω/km M.Ω.km A kA


0.75 26.00 31.110 50 18 0.10
1 19.50 23.332 50 26 0.13
2
1.5 13.3 15.914 50 61 0.19
2.5 7.98 9.548 50 82 0.32
0.75 26.00 31.110 50 18 0.10
1 19.50 23.332 50 44 0.13
3
1.5 13.3 15.914 50 61 0.19
2.5 7.98 9.548 50 82 0.32
0.75 26.00 31.110 50 18 0.10
1 19.50 23.332 50 44 0.13
4
1.5 13.3 15.914 50 61 0.19
2.5 7.98 9.548 50 82 0.32
0.75 26.00 31.110 50 18 0.10
1 19.50 23.332 50 44 0.13
5
1.5 13.3 15.914 50 61 0.19
2.5 7.98 9.548 50 82 0.32

www.extranacable.com
®
EXTRANA
CABLE
NYYHY 300/500 V
2 CORE SNI 04-6629.5; SNI 0255; Manufacturing Specification
(Flexible Copper Conductor, PVC Insulated, PVC Sheathed)

NYYHY is used for power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, luminaires and other portable appliances used in dry
indoor/outdoor premises.
It is suitable for installation where the cable is permanently exposed in humid
environment, which installation can be in tray or under plaster. Suitable for industrial
three phase 380 - 415 VAC or single phase 220 - 240 VAC multipurpose applications,
inherently flame retardant in compliance with IEC 60332-1.

CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight
Diameter. Bending
Size diameter
Insulation Sheath Approximate

mm² mm mm mm kg/km mm

0.75 0.6 0.8 6.5 65 39

1 0.6 0.8 6.8 74 41

1.5 0.7 0.8 12.2 98 46

2.5 0.8 1.0 13.5 152 56

4 0.8 1.0 14.9 202 63

6 0.8 1.1 16.2 270 71

10 1.0 1.3 17.9 452 90

16 1.0 1.8 20.0 679 109

25 1.2 1.8 23.4 990 129

35 1.2 1.8 25.6 1,285 143

50 1.4 1.8 29.1 1,769 165

ELECTRICAL DATA
Max. Conductor Resistance Min. DC Insulation Resistance Max. Current
Max. Short circuit
Carrying Capacity
Size current at 1 sec..
DC at 20ºC AC at 70 ºC at 20ºC at 70ºC at 30ºC

mm² Ω/km Ω/km M.Ω.km M.Ω.km A kA


0.75 26.00 31.110 50 0.0110 10 0.09

1 19.50 23.332 50 0.0100 14 0.12

1.5 13.3 15.914 50 0.0100 18 0.17

2.5 7.98 9.548 50 0.0090 26 0.29

4 4.95 5.923 50 0.0077 34 0.46

6 3.30 3.948 40 0.0065 44 0.69

10 1.91 2.286 30 0.0065 61 1.15

16 1.210 1.448 30 0.0050 82 1.84

25 0.780 0.933 30 0.0050 108 2.88

35 0.554 0.663 20 0.0045 135 4.03

50 0.386 0.463 20 0.0040 168 5.75

www.extranacable.com
®
EXTRANA
CABLE

NYYHY 300/500 V
3 CORE SNI 04-6629.5; SNI 0255; Manufacturing Specification
(Flexible Copper Conductor, PVC Insulated, PVC Sheathed)

NYYHY is used for power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, luminaires and other portable appliances used in dry
indoor/outdoor premises.
It is suitable for installation where the cable is permanently exposed in humid
environment, which installation can be in tray or under plaster. Suitable for industrial
three phase 380 - 415 VAC or single phase 220 - 240 VAC multipurpose applications,
inherently flame retardant in compliance with IEC 60332-1.

CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight
Diameter. Bending
Size diameter
Insulation Sheath Approximate

mm² mm mm mm kg/km mm

0.75 0.6 0.8 6.6 76 41


1 0.6 0.8 6.9 88 43

1.5 0.7 0.9 8.1 121 50

2.5 0.8 1.1 10.0 188 61

4 0.8 1.1 11.1 253 68

6 0.8 1.2 12.4 342 76

10 1.0 1.4 16.0 574 97

16 1.0 1.8 20.8 854 115

25 1.2 1.8 25.4 1,257 137

35 1.2 1.8 27.7 1,648 152

50 1.4 1.8 32.9 2,284 176

ELECTRICAL DATA
Max. Conductor Resistance Min. DC Insulation Resistance Max. Current
Max. Short circuit
Carrying Capacity
Size current at 1 sec..
DC at 20ºC AC at 70 ºC at 0ºC at 70ºC at 30ºC

mm² Ω/km Ω/km M.Ω.km M.Ω.km A kA


0.75 26.00 31.110 50 0.0110 6 0.09

1 19.50 23.332 50 0.0100 10 0.12

1.5 13.3 15.914 50 0.0100 15 0.17

2.5 7.98 9.548 50 0.0090 20 0.29

4 4.95 5.923 50 0.0077 26 0.46

6 3.30 3.948 40 0.0065 33 0.69

10 1.91 2.286 30 0.0065 45 1.15

16 1.210 1.448 30 0.0050 61 1.84

25 0.780 0.933 30 0.0050 83 2.88

35 0.554 0.663 20 0.0045 103 4.03

50 0.386 0.463 20 0.0040 132 5.75

www.extranacable.com
®
EXTRANA
CABLE

NYYHY 300/500 V
4 CORE SNI 04-6629.5; SNI 0255; Manufacturing Specification
(Flexible Copper Conductor, PVC Insulated, PVC Sheathed)

NYYHY is used for power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, luminaires and other portable appliances used in dry
indoor/outdoor premises.
It is suitable for installation where the cable is permanently exposed in humid
environment, which installation can be in tray or under plaster. Suitable for industrial
three phase 380 - 415 VAC or single phase 220 - 240 VAC multipurpose applications,
inherently flame retardant in compliance with IEC 60332-1.

CONSTRUCTION DATA
Overall
Nominal Thickness Net Weight
Diameter. Bending
Size diameter
Insulation Sheath Approximate

mm² mm mm mm kg/km mm

0.75 0.6 0.8 7.3 90 45


1 0.6 0.9 7.8 110 49

1.5 0.7 1.0 9.1 151 56

2.5 0.8 1.1 10.9 229 67

4 0.8 1.2 12.3 311 74

6 0.8 1.3 13.8 415 82

10 1.0 1.5 17.7 684 103

16 1.0 1.8 22.9 986 118

25 1.2 1.8 28.0 1,482 142

35 1.2 1.8 30.5 1,971 159

50 1.4 1.8 36.6 2,762 186

ELECTRICAL DATA
Max. Conductor Resistance Min. DC Insulation Resistance Max. Current
Max. Short circuit
Carrying Capacity
Size current at 1 sec..
DC at 20ºC AC at 70 ºC at 20ºC at 70ºC at 30ºC

mm² Ω/km Ω/km M.Ω.km M.Ω.km A kA


0.75 26.00 31.110 50 0.0110 6 0.09

1 19.50 23.332 50 0.0100 10 0.12

1.5 13.3 15.914 50 0.0100 15 0.17

2.5 7.98 9.548 50 0.0090 20 0.29

4 4.95 5.923 50 0.0077 26 0.46

6 3.30 3.948 40 0.0065 33 0.69

10 1.91 2.286 30 0.0065 45 1.15

16 1.210 1.448 30 0.0050 61 1.84

25 0.780 0.933 30 0.0050 83 2.88

35 0.554 0.663 20 0.0045 103 4.03

50 0.386 0.463 20 0.0040 132 5.75

www.extranacable.com
EXTRANA
CABLE

CONTROL CABLE
NYYHY 300/500 V
SNI 04-6629.7; SNI 0255
(Flexible Copper Conductor, PVC Insulated, PVC Sheathed)

NYYHY is used for power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, luminaires and other portable appliances used in dry
indoor/outdoor premises.
It is suitable for installation where the cable is permanently exposed in humid
environment, which installation can be in tray or under plaster. Suitable for industrial
three phase 380 - 415 VAC or single phase 220 - 240 VAC multipurpose applications,
inherently flame retardant in compliance with IEC 60332-1.

CONSTRUCTION DATA

Nominal Thickness Overall Net


Diameter Weight Bending
Core Size
Diameter
Insulation Sheath Approximate

- mm² mm mm mm kg/km mm
0.75 0.6 0.9 8.1 98 49
1 0.6 0.9 8.5 112 51
1.5 0.7 1.1 10.1 164 61
5 2.5 0.8 1.2 12.2 246 73
4 0.8 1.2 13.5 334 81
6 0.8 1.4 15.4 460 92
10 1.0 1.6 19.7 767 118
0.75 0.6 1.0 9.1 125 55
1 0.6 1.0 9.5 144 57
7
1.5 0.7 1.2 11.3 203 68
2.5 0.8 1.3 13.6 314 82
0.75 0.6 1.1 11.7 183 70
1 0.6 1.1 12.2 211 73
10
1.5 0.7 1.3 14.5 305 87
2.5 0.8 1.5 17.6 465 106
0.75 0.6 1.1 12.0 208 72
1 0.6 1.2 12.8 247 77
12
1.5 0.7 1.3 14.9 349 89
2.5 0.8 1.5 18.1 535 109

ELECTRICAL DATA
Max. Conductor Resistance
Min. DC Insulation Max. Current Carrying Max. Short circuit
Core Size
Resistance at 20ºC Capacity at 30ºC current at 1 sec.
DC at 20ºC AC at 70ºC

- mm² Ω/km Ω/km M.Ω.km A kA


0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 10 0.12
1.5 13.30 15.914 50 15 0.17
5 2.5 7.98 9.548 50 20 0.29
4 4.95 5.923 50 26 0.46
6 3.30 3.948 50 33 0.69
10 1.91 2.286 50 45 1.16
0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 9 0.12
7
1.5 13.30 15.914 50 15 0.17
2.5 7.98 9.548 50 18 0.29
0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 9 0.12
10
1.5 13.3 15.914 50 14 0.17
2.5 7.98 9.548 50 18 0.29
0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 9 0.12
12
1.5 13.3 15.914 50 14 0.17
2.5 7.98 9.548 50 18 0.29

www.extranacable.com
EXTRANA
CABLE

CONTROL CABLE
NYYHY 300/500 V
SNI 04-6629.7; SNI 0255
(Flexible Copper Conductor, PVC Insulated, PVC Sheathed)

NYYHY is used for power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, luminaires and other portable appliances used in dry
indoor/outdoor premises.
It is suitable for installation where the cable is permanently exposed in humid
environment, which installation can be in tray or under plaster. Suitable for industrial
three phase 380 - 415 VAC or single phase 220 - 240 VAC multipurpose applications,
inherently flame retardant in compliance with IEC 60332-1.

CONSTRUCTION DATA

Nominal Thickness Overall Net


Diameter Weight Bending
Core Size
Diameter
Insulation Sheath Approximate

- mm² mm mm mm kg/km mm
0.75 0.6 1.3 14.5 297 87
1 0.6 1.4 15.5 358 93
16
1.5 0.7 1.6 18.0 497 108
2.5 0.8 1.8 21.5 753 129
0.75 0.6 1.4 15.4 340 92
1 0.6 1.5 16.5 411 99
19
1.5 0.7 1.6 19.1 571 114
2.5 0.8 1.9 22.8 867 137
0.75 0.6 1.6 18.3 420 110
1 0.6 1.7 19.5 506 117
21
1.5 0.7 1.9 22.7 701 136
2.5 0.8 2.2 27.2 1,061 163
0.75 0.6 1.6 18.3 437 110
1 0.6 1.7 19.5 528 117
24
1.5 0.7 1.9 22.7 733 136
2.5 0.8 2.2 27.2 1,114 163

ELECTRICAL DATA
Max. Conductor Resistance
Min. DC Insulation Max. Current Carrying Max. Short circuit
Core Size
Resistance at 20ºC Capacity at 30ºC current at 1 sec.
DC at 20ºC AC at 70ºC

- mm² Ω/km Ω/km M.Ω.km A kA


0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 9 0.12
16
1.5 13.30 15.914 50 13 0.17
2.5 7.98 9.548 50 17 0.29
0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 8 0.12
19
1.5 13.30 15.914 50 13 0.17
2.5 7.98 9.548 50 17 0.29
0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 8 0.12
21
1.5 13.3 15.914 50 13 0.17
2.5 7.98 9.548 50 17 0.29
0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 8 0.12
24
1.5 13.3 15.914 50 13 0.17
2.5 7.98 9.548 50 16 0.29

www.extranacable.com
EXTRANA
CABLE
NYYHY 300/500 V
CONTROL CABLE SNI 04-6629.7; SNI 0255
(Flexible Copper Conductor, PVC Insulated, PVC Sheathed)

NYYHY is used for power cord or internal wiring with low mechanical stress for electrical
equipments, machineries, luminaires and other portable appliances used in dry
indoor/outdoor premises.
It is suitable for installation where the cable is permanently exposed in humid
environment, which installation can be in tray or under plaster. Suitable for industrial
three phase 380 - 415 VAC or single phase 220 - 240 VAC multipurpose applications,
inherently flame retardant in compliance with IEC 60332-1.

CONSTRUCTION DATA

Nominal Thickness Overall Net


Diameter Weight Bending
Core Size
Diameter
Insulation Sheath Approximate

- mm² mm mm mm kg/km mm
0.75 0.6 1.7 19.5 526 117
1 0.6 1.8 20.8 637 125
30
1.5 0.7 2.0 24.2 888 145
2.5 0.8 2.3 28.9 1,354 174
0.75 0.6 1.9 22.1 631 133
1 0.6 2.0 23.7 762 142
34
1.5 0.7 2.2 27.5 1,060 165
2.5 0.8 2.4 32.5 1,578 195
0.75 0.6 2.0 24.0 745 144
1 0.6 2.1 25.7 900 154
40
1.5 0.7 2.4 29.9 1,253 180
2.5 0.8 2.4 35.1 1,832 210
0.75 0.6 2.2 26.9 1,024 162
1 0.6 2.3 28.8 1,245 173
61
1.5 0.7 2.4 33.1 1,697 198
2.5 0.8 2.4 38.8 2,517 233

ELECTRICAL DATA
Max. Conductor Resistance
Min. DC Insulation Max. Current Carrying Max. Short circuit
Core Size
Resistance at 20ºC Capacity at 30ºC current at 1 sec.
DC at 20ºC AC at 70ºC

- mm² Ω/km Ω/km M.Ω.km A kA


0.75 26.00 31.110 50 6 0.09
1 19.50 23.332 50 8 0.12
30
1.5 13.30 15.914 50 13 0.17
2.5 7.98 9.548 50 16 0.29
0.75 26.00 31.110 50 5 0.09
1 19.50 23.332 50 8 0.12
34
1.5 13.30 15.914 50 13 0.17
2.5 7.98 9.548 50 15 0.29
0.75 26.00 31.110 50 5 0.09
1 19.50 23.332 50 8 0.12
40
1.5 13.3 15.914 50 13 0.17
2.5 7.98 9.548 50 15 0.29
0.75 26.00 31.110 50 5 0.09
1 19.50 23.332 50 8 0.12
61
1.5 13.3 15.914 50 12 0.17
2.5 7.98 9.548 50 14 0.29

www.extranacable.com