CV01.0001

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
10'-0", MATCH EXISTING
3000 PSI CONCRETE CONTROL JT. AS APPLICABLE
W/ 6x6x
W2.9xW2.9 WWF

4" MATCH EXISTING

GRANULAR FILL
VDOT 21A MATCH EXISTING

TOP OF UTILITY VAULT


SEE VAULT SECTION ON ST03.0002

NOTES:
1. CONTRACTOR TO REPLACE EXISTING JOINTS WITH NEW JOINTS IN SAME KIND ACCORDING TO DETAILS THIS SHEET.
2. PROVIDE CONTROL JOINTS AT 5'-0" ON CENTERS (MAX).
3. REMOVAL AND REPLACEMENT SHALL BE TO THE NEAREST JOINT.
4. WHERE SIDEWALK WIDTH EXCEEDS 6'-0" PROVIDE LONGITUDINAL CONTROL JOINT AT MIDDLE OF THE SIDEWALK.
5. CONTRACTOR SHALL VERIFY EXISTING SIDEWALK PAVEMENT SECTION AND MATCH EXISTING.

MATCH
EXISTING

MATCH
EXISTING
MATCH
EXISTING
3/4" 1 1/2"
SLOT

3/4" 1 1/2"
SLOT

TOP BOTTOM

NOTES:
1) MANHOLE LID TO BE IN ACCORDANCE WITH MWAA DESIGN MANUAL AND THE
NOTES BELOW
2) MATERIAL: STEEL
3) THE LETTERS ARE TO BE WELDED INTO THE DEPRESSION IN THE TOP OF THE
COVER, 3-INCH LETTER HEIGHT & WELD RAISED 1/4 INCH
4) SEE STRUCTURAL VAULT SECTION ON SHEET ST03.0002 FOR FRAME AND
MANHOLE LOCATIONS.

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
ABBREVIATIONS SYMBOLS

GENERAL NOTES

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
1 DEMOLITION FLOOR PLAN - FIRST FLOOR

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
1 DEMOLITION REFLECTED CEILING PLAN - FIRST FLOOR

DEMOLITION REFLECTED CEILING PLAN


ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
1 DEMOLITION FLOOR PLAN - SECOND FLOOR

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
1 DEMOLITION REFLECTED CEILING PLAN - SECOND FLOOR

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
1 DEMOLITION - ROOF PLAN

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
2 KEY PLAN - SECOND FLOOR

1 KEY PLAN - FIRST FLOOR

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
1 DETAILED FLOOR PLAN - FIRST FLOOR

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
1 DETAILED REFLECTED CEILING PLAN - FIRST FLOOR

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
D1 F1

4 DOOR ELEVATION

DH1 / DJ1

5 DOOR DETAIL 6 WINDOW ELEVATION

1 DETAILED FLOOR PLAN - SECOND FLOOR


2 WINDOW ELEVATION 3 WINDOW SECTION 7 WINDOW SECTION

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
2 TYPICAL CEILING/ROOF DETAIL

1 DETAILED REFLECTED CEILING PLAN - SECOND FLOOR

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
1 ROOF PLAN

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
HEAD-OF-PARTITION PARALLEL HEAD-OF-PARTITION PERPENDICULAR
TO FLUTED DECK TO FLUTED DECK HEAD-OF-PARTITION @ BEAM

INSIDE LOFT OPEN BAY INSIDE LOFT OPEN BAY

A1 PARTITION A1 PARTITION
TYPICAL @ MID BEAM LOCATIONS
R-11 VALUE R-11 VALUE

1 PARTITION DETAILS 2 TYP. MECHANICAL UNIT ROOF CURB DETAIL

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SUITE 200
DULLES, VIRGINIA 20166
ABBREVIATIONS MECHANICAL SYMBOLS MECHANICAL SYMBOLS MECHANICAL SYMBOLS GENERAL NOTES
FPM FEET PER MINUTE G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
FT. FEET UNION COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
PERFORATED CEILING PANEL, 24x24 FACE DUCT WITH ACOUSTICAL SOUND LINING
F.V. FACE VELOCITY PRESSURE REDUCING VALVE AREA, SUITABLE FOR 2'x4' TILE CEILING. G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
GAL. GALLON
GPM GALLONS PER MINUTE SAFETY RELIEF VALVE ROUND DUCT UP UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
H.C. HEATING COIL CENTRIFUGAL FAN OR
HP HORSEPOWER O.S.&Y VALVE PUMP BY APPLICATION G7 SEE GN01.0001 FOR PHASING DEFINITIONS AND OUTLINE PROJECT
HW DOMESTIC HOT WATER ROUND DUCT DOWN SEQUENCES.
M
HWR HEATING WATER RETURN MOTORIZED O.S.&Y VALVE VANE AXIAL FAN
HWS HEATING WATER SUPPLY DUCT WITH FIRE DAMPER AND
Hz HERTZ FLOW MEASURING VALVE MINIMUM 16x16 ACCESS DOOR
IN. INCHES F.D.&A.D.
COMBINATION FLOW MEASURING
JB JUNCTION BOX AND BALANCING VALVE 350 RETURN AIR SYMBOL DUCT WITH ACCESS DOOR,
NUMBER INDICATES CFM MINIMUM 16x16
JC JANITORS CLOSET BALANCING VALVE A.D.
L.A.T. LEAVING AIR TEMPERATURE
BALL VALVE 350 SUPPLY AIR SYMBOL
DUCT WITH MANUAL BALANCING DAMPER
GENERAL SYMBOLS
LBS. POUNDS NUMBER INDICATES CFM
LBS./HR. POUNDS PER HOUR BUTTERFLY VALVE AND MINIMUM 16x16 ACCESS DOOR
M.B.D. SECTION IDENTIFICATION
L.D.B. LEAVING DRY BULB T THERMOSTAT
BACKFLOW PREVENTOR DUCT WITH MOTOR OPERATED DAMPER INDICATES DIRECTION
L.W.T. LEAVING WATER TEMPERATURE H HUMIDITY SENSOR OF CUTTING PLANE
MAX. MAXIMUM M.A.V. MANUAL AIR VENT 3/8" BALL VALVE M.O.D.
M.B.D. MANUAL BALANCING DAMPER A COMPRESSED AIR PIPING 1
DUCT WITH FLEXIBLE CONNECTION NUMBER INDICATES
MER MECHANICAL EQUIPMENT ROOM CW DOMESTIC COLD WATER SECTION
M-101 M-401
MIN. MINIMUM CWR CHILLED WATER RETURN SHEET NUMBER WHERE
M.O.D. MOTOR OPERATED DAMPER THERMOMETER AND WELL CWS CHILLED WATER SUPPLY DUCT WITH SOUND ATTENUATOR SECTION IS DRAWN
NC NOISE CRITERIA D CONDENSATE DRAIN SHEET NUMBER WHERE
N.C. NORMALLY CLOSED HTWR HIGH TEMP. HOT WATER RETURN SECTION IS TAKEN
N.I.C. NOT IN CONTRACT UP DUCT TRANSITION UP
HTWS HIGH TEMP. HOT WATER SUPPLY DETAIL IDENTIFICATION
N.O. NORMALLY OPEN PRESSURE GAUGE NUMBER INDICATES
HW DOMESTIC HOT WATER
O.A. OUTSIDE AIR DETAIL
HWR HEATING WATER RETURN DUCT TRANSITION DOWN 1
O.C. ON CENTER DN.
PIPE TURN UP HWS HEATING WATER SUPPLY
O.S.D. OPEN SITE DRAIN MU MAKE-UP WATER M-101 M-501
PIPE TURN DOWN RISE DUCT RISE
P.D. PRESSURE DROP SHEET NUMBER WHERE
ST STORM WATER DETAIL IS DRAWN
PH PHASE
V VENT SHEET NUMBER WHERE
PRV PRESSURE RELIEF VALVE RECTANGULAR DUCT DETAIL IS TAKEN
PSI
PSIG
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH GAUGE
ABBREVIATIONS SINGLE LINE PIPE REPRESENTING A
4-PIPE SYSTEM; CWS, CWR, HWS & HWR.
SIZE TRANSITION
A.D. ACCESS DOOR NORTH ARROW
PVC POLYVINYL CHLORIDE RIGID ROUND DUCT ARROW INDICATES
A.F.F. ABOVE FINISHED FLOOR SINGLE LINE PIPE REPRESENTING A
R.A. RETURN AIR SIZE TRANSITION TRUE NORTH AND/OR
AHU AIR HANDLING UNIT 2-PIPE SYSTEM; HWS & HWR.
R.G. RETURN GRILLE PROJECT NORTH
RHG REFRIGERANT HOT GAS ARCH. ARCHITECTURAL DUCT TRANSITION FROM N
WYE STRAINER WITH CAPPED SQUARE TO ROUND
RL REFRIGERANT LIQUID A.P. ACCESS PANEL
BLOWDOWN VALVE
RLA RUNNING LOAD AMPS APPROX. APPROXIMATELY
BHP BRAKE HORSEPOWER FL.D. FLOOR DRAIN DUCT WITH 1/2"x1/2" WOVEN WIRE
RPM REVOLUTIONS PER MINUTE MESH SCREEN WITH HEMMED EDGES. COLUMN BUBBLE
S.A. SUPPLY AIR BTU BRITISH THERMAL UNITS R.D. ROOF DRAIN A DESIGNATION
SD SMOKE DETECTOR BTUH BRITISH THERMAL UNITS PER HOUR
C COMMON SD DUCT WITH SMOKE DETECTOR
S.P. STATIC PRESSURE DOUBLE LINE PIPE TURN UP 1
C.C. COOLING COIL REVISION CLOUD WITH
S.S. STAINLESS STEEL REVISION NUMBER DESIGNATION
ST STORM C.D. CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE DOUBLE LINE PIPE TURN DOWN DUCT ELBOW WITH
T.G. TOP GRILLE TURNING VANES
T.O.C. TOP OF CONCRETE C.G. CEILING GRILLE
T.O.G. TOP OF GRADE C.O. CLEANOUT BREAKLINE
T.O.S. TOP OF STEEL C.R. CEILING REGISTER FORGED BRANCH PIPE FITTING FLEXIBLE DUCTWORK. 5 FEET MAXIMUM
T.R. TOP REGISTER CW DOMESTIC COLD WATER LENGTH, SIZE AS INDICATED OR SCHEDULED M A T C H L I N E A-A MATCHLINE DESIGNATION
TYP. TYPICAL D.B. DRY BULB
UH UNIT HEATER db DECIBEL DEMOLITION LINETYPE
V VOLTS DDC DIRECT DIGITAL CONTROL DUCT MOUNTED REGISTER, SIZE PER SCHEDULE
PROVIDE FULL LUG CENTERLINE
VAV VARIABLE AIR VOLUME DESIG. DESIGNATION UNLESS OTHERWISE NOTED. NUMBER INDICATES
BUTTERFLY ISOLATION VALVES 135 R BALANCING AIRFLOW CFM. R INDICATES REGISTER. CL CENTERLINE SYMBOL
VOL. VOLUME DIA. DIAMETER
DN. DOWN M (E) EXISTING
VTR VENT THRU ROOF PROVIDE MOTORIZED, FULL LUG
W.B. WET BULB (E) EXISTING POINT OF CONNECTION TO EXISTING
E.A.T. ENTERING AIR TEMPERATURE BUTTERFLY ISOLATION VALVES
W.C. WATER COLUMN
W.G. WATER GAUGE E.D.B. ENTERING DRY BULB SQUARE CEILING DIFFUSER WITH FLEXIBLE POINT OF TERMINATION OF REMOVAL
PIPE CAP
EFF. EFFICIENCY
135 DUCT(5' MAXIMUM LENGTH) SAME SIZE AS # NOTE NUMBER
E.G. EXHAUST GRILLE DIFFUSER NECK SIZE. DIFFUSER SIZE PER
ELEV. ELEVATION/ELEVATOR SCHEDULE UNLESS OTHERWISE NOTED.
ENT. ENTERING
E.S.P. EXTERNAL STATIC PRESSURE PROVIDE OS&Y
PROVIDE CONICAL SPIN-IN TAP WITH
BALANCING DAMPER AT CIRCULAR DUCT.
MECHANICAL SYMBOLS
E.V. EXHAUST VENT ISOLATION VALVES NUMBER INDICATES BALANCING AIRFLOW CFM.
E.W.B. ENTERING WET BULB EXHAUST OR RETURN DUCT UP
E.W.T. ENTERING WATER TEMPERATURE 135
GATE VALVE CEILING REGISTER, SIZE PER SCHEDULE UNLESS
EXIST. EXISTING GLOBE VALVE EXHAUST OR RETURN DUCT DOWN
OTHERWISE NOTED. NUMBER INDICATES
DEGREES FAHRENHEIT SWING CHECK VALVE BALANCING AIRFLOW CFM.
F.D. FIRE DAMPER CR
FLA FULL LOAD AMPS TWO-WAY CONTROL VALVE SUPPLY DUCT UP
SUPPLY AIR DIFFUSER, 24x24 FACE
FL.D. FLOOR DRAIN
THREE-WAY CONTROL VALVE AREA, SUITABLE FOR 2'x4' TILE CEILING.
FLR. FLOOR SUPPLY DUCT DOWN
STRAINER
FILE NAME: IF1402ME000001.DWG

PLOT DATE: 5/21/2015 9:33:32 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SYMBOLS AND ABBREVIATIONS
SUITE 200
DULLES, VIRGINIA 20166
ASBESTOS SUMMARY NOTES GENERAL NOTES
ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS THAT ARE TO 9 DEMOLISH PIPE, HANGERS, SUPPORTS, AND APPURTENANCES G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
BE DEMOLISHED OR DAMAGED DURING THE COURSE OF THE WORK COMPLETE TO POINTS INDICATED. COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

LIMITED TO ALL ORIGINAL PIPE INSULATION, OTHER ITEMS AS NOTED 16 DEMOLISH DOWN TO BELOW METAL PLATE AT FLOOR AND CAP. G4 ALL WORK IS TO BE PROVIDED UNDER PHASE II UNLESS
IN THE DRAWINGS AND ANY MATERIALS SUSPECTED BY THE ABANDON PIPES BELOW IN TRENCH.. OTHERWISE INDICATED.
CONTRACTOR DURING THE COURSE OF THE WORK. THE TESTING
AGENCY SHALL BE LICENSED TO TEST ASBESTOS IN THE STATE OF 34 DEMOLISH THERMOSTAT. CONTROL WIRING, CONDUIT, AND
VIRGINIA AND MEET THE REQUIREMENTS OUTLINED IN THE SWITCHES TO REMAIN FOR REUSE BY UNIT HEATERS. SEE DRAWING NOTES
ME030001. 1 PERFORM WORK DURING PHASE I.
ABATED BY AN ASBESTOS ABATEMENT CONTRACTOR LICENSED AND
4 PERFORM WORK DURING PHASE IV.
WORK TO REMOVE AND PROPERLY DISPOSE OF THE ASBESTOS
CONTAINING MATERIAL IS THE RESPONSIBILITY OF THE 5 DEMOLISH DUCT, HANGERS, SUPPORTS, AND APPURTENANCES
COMPLETE TO POINTS INDICATED.
ACCORDANCE WITH THE SPECIFICATIONS, MWAA DESIGN MANUAL
2014 AND THE LAWS OF THE STATE OF VIRGINIA. 6 DEMOLISH EQUIPMENT, ASSOCIATED SUPPORTS, CONTROLS WIRING,
INSULATION, AND APPURTENANCES COMPLETE.
EXISTING HTHW LINES, ROOF DRAIN ELBOWS, DOMESTIC HOT WATER
LINES, AND THE HTHW TO HW HEAT EXCHANGER TO BE DEMOLISHED 7 PATCH AND REPAIR WALL AS INDICATED ON ARCHITECTURAL
CONTAIN ASBESTOS INSULATION AND/OR JOINT FILLERS. DRAWINGS.

8 CAREFULLY REMOVE EQUIPMENT AND RETURN TO OWNER.


D4 D3 D2 1 A.C. UNIT 7 8
2 3 4 5
(E)24x8 E.A. UP
10x30 5
6 7
(E)14x8 5 8x6
A.C. UNIT 7 8
1 5 8x6 UP
D
(E)8x5
18x24 R.G. 5
(E)JB (E)12x8 RM 104 BTU METER 4 6
(E)15x8
(E)11x8 12x14 UP 5 1
8x7 5 5 12x8
(E)10x8 2"HTWS&R UP & DN. 4 16
RM 108 13x8 5 RM 100 25x8
(E)8x5
RM 103 5

2"CWS&R UP&DN. 1 16 4" V UP&DN.


(E)13x8
5 29x12 5 7 9x6
(E)13x8
32x10 5 8x6 5
(E)8x5 T 4 34
5 7x15 RM 114
C
5 34x12 24x12 5 16x6 R.G. 5 7
5 30x12
28x10 5
5 8x7
5 8x8
8x7 5 RM 112

A.C. UNIT 7 8
8x8 5
5 8x7

RM 110
1 20x10 5

B 1 34 T T 1 34 1 34 T T 4 34
12x8 1 5 1 7 10x8 1 5 4 34 T
12x8 1 5

T 1 34 (E)36x24 TRANSFER GRILLE


1 5 22x8
UH 6 1
(E)6"ST UP&DN.
RM 111 4 34 T

(E)36x24 TRANSFER GRILLE


HTWS&R 9 1

(E)CONDUIT UP&DN.

T
A
1 9 HTWS&R UP HTWS&R 9 1
(E)8"ST
1 6 ABANDONED THERMOSTAT
GRAPHIC SCALE
FIRST FLOOR PLAN - DEMOLITION N 1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME020001.DWG

PLOT DATE: 5/21/2015 9:33:50 AM


OUR REF: 112.09

ALPHA CORPORATION
FIRST FLOOR MECHANICAL PLAN -
21351 RIDGETOP CIRCLE,
SUITE 200
DEMOLITION
DULLES, VIRGINIA 20166
ASBESTOS SUMMARY NOTES GENERAL NOTES
ANY SUSPECTED ASBESTOS-CONTAINING MATERIALS THAT ARE TO 7 PATCH AND REPAIR WALL AS INDICATED ON ARCHITECTURAL G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
BE DEMOLISHED OR DAMAGED DURING THE COURSE OF THE WORK DRAWINGS. COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

LIMITED TO ALL ORIGINAL PIPE INSULATION, OTHER ITEMS AS NOTED 9 DEMOLISH PIPE, HANGERS, SUPPORTS, AND APPURTENANCES G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS
IN THE DRAWINGS AND ANY MATERIALS SUSPECTED BY THE COMPLETE TO POINTS INDICATED. OTHERWISE INDICATED.
CONTRACTOR DURING THE COURSE OF THE WORK. THE TESTING
AGENCY SHALL BE LICENSED TO TEST ASBESTOS IN THE STATE OF
VIRGINIA AND MEET THE REQUIREMENTS OUTLINED IN THE
15 PATCH AND REPAIR FLOOR PENETRATION PER STRUCTURAL DETAILS.
NOTES
36 DEMOLISH RACK OF PNEUMATIC CONTROL TUBING. 2 PERFORM WORK DURING PHASE II.
ABATED BY AN ASBESTOS ABATEMENT CONTRACTOR LICENSED AND
3 PERFORM WORK DURING PHASE III.
WORK TO REMOVE AND PROPERLY DISPOSE OF THE ASBESTOS
CONTAINING MATERIAL IS THE RESPONSIBILITY OF THE 4 PERFORM WORK DURING PHASE IV.

ACCORDANCE WITH THE SPECIFICATIONS, MWAA DESIGN MANUAL 5 DEMOLISH DUCT, HANGERS, SUPPORTS AND APPURTENANCES
2014 AND THE LAWS OF THE STATE OF VIRGINIA. COMPLETE TO POINTS INDICATED.

EXISTING HTHW LINES, ROOF DRAIN ELBOWS, DOMESTIC HOT WATER 6 DEMOLISH EQUIPMENT, ASSOCIATED SUPPORTS, CONTROLS WIRING,
LINES, AND THE HTHW TO HW HEAT EXCHANGER TO BE DEMOLISHED 6 HVC-2 INSULATION, AND APPURTENANCES COMPLETE.
CONTAIN ASBESTOS INSULATION AND/OR JOINT FILLERS. STARTER
6 HTHW HEAT
EXCHANGER PNEUMATIC CONTROL
D4 D3 D2 1 2 PANEL 6
3 4 5 6 7
(E)EXHAUST 5 8x6 DN. OA LOUVER 5 7
LOUVER (E)VTR
36 OA LOUVER 5 7
HVC-2 6 18x18 5

D (E)EMCS CONTROL PANEL


15
6 FAN 36 (E)1"CONDUIT (E)PATCHED FRAMED ROOF PENETRATION
(E)CONDUIT
(E)HW
9 1-1/2"HTWS&R 9 1-1/4"HTWS&R 14x12 DN. 5
6 DWH 2"HTWS&R 9 4
(E)4"ST
1/2" 9 1-1/4" 9 (E)V DN. TO FL.D.
UP TO R.D. CWS&R
HTWS&R 3/4"HTWS&R 9
CHILLED WATER CIRCULATING PUMP 6
6
HTWS&R 9 4

9 2"CWS&R (E)4"ST
(E)4"ST SPILL TO LOW 34x15 DN. 2"HTWS&R 9 (E)4"ST
UP TO R.D.
ROOF. SEE ME020003 UP TO R.D.
(E)4"ST 5 20x18 (E)4"ST CEILING FAN 6 (E)4"ST RM 200 (E)E.V. UP TO ROOF (E)4"ST
FOR CONTINUATION. UP TO RD (E)E.V. UP UP TO R.D. UP TO R.D. UH 6 UP TO R.D.
6 4"ST 9
C (E)E.V. UP TO ROOF (E)E.V. UP TO ROOF TO ROOF
6
(E)4"ST
(E)E.V. UP
6 TO ROOF
(E)E.V. UP TO ROOF (E)1"CONDUIT 1"HTWS&R 9 (E)E.V. UP TO ROOF (E)E.V. UP TO ROOF
HV-1 (E)JB (E)4"ST 6
(E)1"CONDUIT (E)1"CONDUIT UH 6 4
UH 6 UH 6 18x30 5 4 6 UH UH 6 4
6 UH (E)3"CONDUIT HTWS&R 9 4
(E)1"CONDUIT

CAPPED (E)2"CONDUIT
(E)4"ST (E)CONDUIT
6 (E)JB (E)E.V. UP (E)E.V. UP (E)4"ST UP TO R.D.
(E)E.V. UP TO ROOF 4 9 HTWS&R TO ROOF
(E)6"ST (E)CONDUIT HTWS&R 9 4
TO ROOF
9 HTWS&R (E)4"ST UP 6 6
TO (E)R.D. (E)3"CONDUIT (E)4"ST (E)E.V. UP
FAN 6 (E)8-1"PIPES 1-1/2" (E)4"ST
24x18 S.R. 5 HTWS&R 9 4 TO ROOF
GREASE,OIL,TRANS. HTWS&R 9 (E)6"ST
B 5 24x6 FLUID, CMPA UH 6 4
30x18
THROUGH WALL TO 36x18 LOUVER (E)4"ST (E)4"ST
5 30x18 5 3 5 (E)6"ST
ABOVE LOW ROOF. UP TO R.D. RM 204 UP TO R.D.
SEE ME020003 FOR CONTINUATION. (E)4"ST
UP (E)4"ST
UP TO R.D.
UP TO R.D.
(E)4"ST 6 3 5
(E)2"CONDUIT 6
FAN
6
PV-1 3 5
(E)4"ST (E)JB
(E)30x30
UP TO R.D. 30x18 AHU 3 6
OA INTAKE
3 5
(E)JB 5

TO ROOF
A
(E)OA (E)8"ST
LOUVER 6 FAN PV-1 ELECTRICAL EQUIPMENT
STARTER AREA 3 5
9 HTWS&R DN. 3 5 GRAPHIC SCALE
(E)EXHAUST
FAN SECOND FLOOR PLAN - DEMOLITION N
1/8"=1'-0"
8' 4' 0 8' 16'
(E)EXHAUST
CAUTION: IF THIS DRAWING IS A REDUCTION,
LOUVER
FILE NAME: IF1402ME020002.DWG

PLOT DATE: 5/21/2015 9:34:01 AM


OUR REF: 112.09

ALPHA CORPORATION
SECOND FLOOR MECHANICAL PLAN -
21351 RIDGETOP CIRCLE,
SUITE 200
DEMOLITION
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G5 ALL WORK IS TO BE PROVIDED UNDER PHASE III UNLESS


OTHERWISE INDICATED.

NOTES
4 PERFORM WORK DURING PHASE IV.

5 DEMOLISH DUCT, HANGERS, SUPPORTS AND APPURTENANCES


COMPLETE TO POINTS INDICATED.

6 DEMOLISH EQUIPMENT, ASSOCIATED SUPPORTS, CONTROLS WIRING,


INSULATION, AND APPURTENANCES COMPLETE

17 DEMOLISH LOUVER. PATCH WALL TO MATCH EXISTING PER


ARCHITECTURAL DRAWINGS.

D4 D3 D2 1 2 3 4 5 6 7

(E)ROOF ACCESS
HATCH
D
(E)V

(E)4"R.D.

(E)E.V. DN.
(E)E.V. DN.
(E)4"R.D.
(E)E.V. DN. (E)4"R.D. (E)E.V. DN. (E)4"R.D. (E)E.V. DN.
(E)4"ST SPILL ON ROOF. (E)4"R.D.
(E)4"R.D. (E)ANTENNA (E)E.V. DN. (E)E.V. DN.
SEE ME0301 FOR CONTINUATION.
C
(E)E.V. DN.
(E)FAN (E)FAN

(E)FAN (E)FAN (E)FAN (E)FAN (E)FAN

(E)V (E)4"R.D.

36x18 LOUVER SEE ME020002


FOR CONTINUATION. 4 17 (E)E.V. DN. (E)E.V. DN.
B (E)E.V. DN.
(E)4"R.D. (E)4"R.D. (E)4"R.D.
(E)E.V. DN. (E)4"R.D.

CONDENSING UNIT 6

(E)30x30 OA

(E)4"R.D.

(E)V

GRAPHIC SCALE
ROOF PLAN - DEMOLITION N 1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME020003.DWG

PLOT DATE: 5/21/2015 9:34:14 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
ROOF MECHANICAL PLAN - DEMOLITION
SUITE 200
DULLES, VIRGINIA 20166
26
20x8 OPENING C 2
SHUTOFF VALVE (E)8x6
(E)10x30 NOTES GENERAL NOTES
(E)6"CWR 1 34x10 UP
19 PROVIDE TRANSFER PER DETAIL 9/ME030001/040001. G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND

10" 27 (E)6"CWS WELD 1/2" PIPE TO CAP D COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
21 PROVIDE OUTSIDE AIR TEMPERATURE SENSOR TS-OA.
BLANK OFF UNUSED (E)18x24 R.G. G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
5.75" 4.25" PORTION OF DUCT
2"HTWS 23 PROVIDE EMERGENCY HVAC OFF SWITCH. COORDINATE LOCATION UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
2-1/2"HTWS (E)6"HTWS 6" OPENING WITH OWNER.
16"
G4 ALL WORK IS TO BE PROVIDED UNDER PHASE II UNLESS
14" 1/2" PIPE
27 (E)6"HTWR (E)25x8 26 SEE STRUCTURAL DRAWINGS FOR VAULT DETAILS. COORDINATE OTHERWISE NOTED.
5" (E)12x8 MANHOLE LOCATIONS WITH VALVE LOCATIONS.
38 2-1/2"HTWR
2"HTWR 27 PROVIDE AIR VENT AT TAP PER DETAIL 2/ME030001/ME030001.
NOTES
8"
D4 (E)8x6
1 PERFORM WORK DURING PHASE I.
6" 38 31 PROVIDE NETWORK CONNECTION USING CAT-6 CABLES TO CONNECT
BTU METER PANEL AND HEAT EXCHANGER CONTROL PANEL TO AHU 4 PERFORM WORK DURING PHASE IV.
CONTROL PANEL ON SECOND FLOOR.
56x38 UP THROUGH FLOOR. SEE STRUCTURAL DRAWINGS. 2 3 10 REUSE EXISTING WALL PENETRATION.
4"CWS&R UP 9" DETAIL ME030001 ME030001 1 DETAIL ME030001 ME030001 35 CONNECT THERMOSTAT TO REUSE CONTROL WIRING, CONDUIT AND
SWITCHES. 11 PROVIDE WALL PENETRATIONS PER ARCHITECTURAL DETAILS.
2"HTWS&R UP
AIR VENT PHASE 1 DUCT CONNECTION
38 SUPPORT PIPE ON SLIDE PLATE ASSEMBLY TO ALLOW PIPE 18 PROVIDE TRANSFER PER DETAIL 1/ME030001/ME040002.
1 MOVEMENT DUE TO EXPANSION IN ALL DIRECTIONS PER DETAIL
1 DETAIL ME030001 ME030001 3/ME030001/ME040003.

TRENCH PLAN N 1 2 3
(E)24x8 E.A. UP 3
D4 D3 D2 (E)14x8
1"HWS&R 4 5 6 7
ME030001 ME030001
(E)JB 1 34x10 UP
D 26x10 8x6
(E)8x5
(E)JB VAV-2
RM 104 230 230
(E)12x8
(E)11x8
(E)JB 140
10x8 8x6
(E)10x8 VAV-5
RM 108 RM 103 (E)4" V UP&DN.
RM 100
21 (E)13x8
(E)8x5 14x12 230 EF-2, SF-3, AND SF-4 STARTERS 4
140 230
19 11 TRANSFER VAV-1 T 11
HX-1 CONTROL PANEL 1 31 1 TO EF-1 T
T 16x8
30" 10 18 11 TRANSFER T
10
16x10 UP 65 RM 114 TO UH-5 4 35
C REMOVABLE 2x2 SQUARE T & UH-7
24x16 R.G UP 10
1 HX-1 TUBE RAIL(TYP.). SEE STRUCTURAL DRAWINGS. 1 VAV-3 TRANSFER 8x4
45 R 45 R
12x6 T 11 18
HX TUBE PULL AREA 19'8"
11 EF-3
56x38 OPEN TO TRENCH BELOW 45 45 105 110
2"HTWS&R UP 1 R R RM 112

4"CWS&R UP 1 1 8x6 4 TO T
EF-2
ME030001,ME030002 ME060002 12x8
50 R RM 110 45 R 50 R 45 R 45 R 50 R
BTU METER PANEL 1 31
12x6 12x6
EF-1, SF-1, AND SF-2 STARTERS STACKED VERTICALLY 4
TO
B 1 UH-1
T T
TO UH-2 1 35 TO UH-4
T T
1 T
& UH-3 1 35 TO
ME030001 ME030001 1 35 TO 4 35 35 4
35 1 UH-8
UH-6
23 T (E)36x24 TRANSFER GRILLE TO
35 4
UH-10 1 UH-9
(E)6"ST UP&DN.
RM 111 T

(E)36x24 TRANSFER GRILLE


1"HWS&R 1

(E)CONDUIT UP&DN.
EF-5
A GRAPHIC SCALE
1 1 24x30 LOUVER 11 1/4"=1'-0"
1"HWS&R UP 1 (E)8"ST
4' 2' 0 4' 8'
ME030001,ME030002 ME060001 ME030001,ME030002 ME060003
1/8"=1'-0"
FIRST FLOOR PLAN N 8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME030001.DWG

PLOT DATE: 5/21/2015 9:34:27 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
FIRST FLOOR MECHANICAL PLAN
SUITE 200
DULLES, VIRGINIA 20166
NOTES NOTES GENERAL NOTES
37 PROVIDE NETWORK CONNECTION USING CAT-6 CABLES FROM 13 PROVIDE FLOOR PENETRATION PER STRUCTURAL DETAIL. PROVIDE G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
SWITCH TO EXISTING EMCS CONTROL PANEL. FIRE STOPPING. COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

39 PROVIDE NETWORK CONNECTION USING CAT-6 CABLES FROM 18 PROVIDE TRANSFER PER DETAIL 1/ME030002/ME040002. G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
SWITCH TO AHU CONTROL PANEL. UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
20 PROVIDE DIFFERENTIAL PRESSURE TRANSMITTER DPT-1.
40 DEMOLISH MEDIA CONVERTOR WITHIN EXISTING EMCS CONTROL G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS
PANEL. 22 PROVIDE DIFFERENTIAL PRESSURE TRANSMITTER DPT-3. OTHERWISE INDICATED.

41 DEMOLISH EMCS CONTROL PANEL UPON COMPLETION OF PHASE IV 24 ROUTE 1/2"CW MAKE UP WATER TO EXPANSION TANK. PROVIDE NOTES
WORK. PRESSURE REGULATING VALVE AND BACKFLOW PREVENTER PER 2 PERFORM WORK DURING PHASE II.
DETAIL 1/ME030002/ME040003. SEE DETAIL 6/ME030002/ME040002 FOR
42 PROVIDE MINIMUM 24" W x 30" L x 6" D NEMA 3R ENCLOSURE WITH POINTS OF CONNECTION. 3 PERFORM WORK DURING PHASE III.
HINGED DOOR AND QUARTER TURN LATCH FOR SWITCH AND
28 PROVIDE MANUAL AIR VENT OFF TOP OF PIPE AND DRAIN VALVE WITH 4 PERFORM WORK DURING PHASE IV.
HOSE CONNECTION OFF BOTTOM OF PIPE.
11 PROVIDE WALL PENETRATION PER ARCHITECTURAL DETAIL. SEAL ALL
ENCLOSURE ON WALL ADJACENT TO EXISTING EMCS CONTROL 29 PROVIDE WELDED LINKED EYE ROD HANGERS FOR HEATING WATER PENETRATIONS AIR TIGHT.
PANEL. PIPING PER DETAIL 2/ME030002/ME040003.
12 REUSE/MODIFY EXISTING FLOOR PENETRATION. PROVIDE FIRE
30 EXTEND FIBER CONNECTION TO CONNECT TO NEW MEDIA STOPPING.
CONVERTOR.

D4 D3 D2 1 2 3 33 SEE STRUCTURAL DRAWINGS FOR FRAMING DETAILS.


2 13 1"HWS&R DN. (E)VTR 5-PORT GIGABIT GREENNET SWITCH AND 100BASE-TX TO 100BASE-FX MULTI MODE SC FIBER CONVERTOR 30 37 39 42
1 (E)EXHAUST LOUVER
34x10 DN. 12 (E)V DN.
ME030001,ME030002 ME060001 12 24x8 DN. EF-4 TO FL.D. 4 5 6 7
3 (E)EMCS CONTROL PANEL 40 41
24
D 24
4
(E)ROOF ACCESS 2 GALLON CHEMICAL FEED TANK
(E)CONDUIT ME030002 ME040002
DWH-1 20
(E)PATCHED FRAMED ROOF PENETRATION
(E)4"ST 2"HWS&R VAV-6 VAV-4 195 R
2 (E)HW

18x4
UP TO R.D. 3 ET-1 1-1/2"HWS&R 4
11

26x18
1-1/2"HWS&R 4
2"HWS&R 18x4
(E)4"ST

16x10 3
(E)4"ST SPILL TO LOW 12x10
ROOF. SEE ME030003 UP TO RD 3 (E)4"ST
190 R (E)4"ST

24x12
190 R
FOR CONTINUATION. 18x4
RM 200 UH-5 4 UP TO R.D. UP TO R.D.
12x10
(E)E.V. UP TO ROOF (E)E.V. UP 4250 R
C (E)LIGHT TO ROOF 30x30 UP (E)E.V. UP TO ROOF (E)E.V. UP TO ROOF (E)E.V. UP TO ROOF
(E)4"ST 18x4
(E)1"CONDUIT TO SF-3 4 33
(E)E.V. UP TO ROOF UP TO R.D.
4250 R
190 R
UH-2 1-1/2"HWS&R (E)4"ST
2"HWS&R UH-8 4 1"HWS&R 4
UH-1 2"HWR (E)1"CONDUIT (E)3"CONDUIT (E)1"CONDUIT UH-9 4
29 2-1/2"HWR 29 2"HWS UH-4
(E)1"CONDUIT 1-1/4"HWS&R 4 1"HWS&R 4
1
2-1/2"HWS&R 29 (E)2"CONDUIT
28 UH-7 4 4250 R
ME030001,ME030002 ME060002 (E)CONDUIT
UH-3 4"CWS&R (E)4"ST (E)6"ST (E)JB 33 4 30x30 UP TO SF-4
29 2-1/2"HWS 4250 R (E)3"CONDUIT 11 (E)E.V. UP TO ROOF
18x4 (E)6"ST (E)CONDUIT
4250 R
4"CWS&R 33 4 30x30 UP TO SF-2 (E)4"ST (E)4"ST (E)E.V. UP TO ROOF 46x46 UP TO EF-2 4250 R (E)4"ST UP TO R.D.
4 33 46x46 UP TO EF-1 190 R
30x30 UP TO SF-1 4 33 (E)LIGHT 190 R 1"HWS&R 4 4 33
(E)4"ST (E)E.V. UP TO ROOF
B 4250 R (E)E.V. UP 4250 R UP TO R.D.
TO ROOF TRANSFER 3 11 18 (E)4"ST
(E)4"ST 18x4 UP TO R.D.
195 200 (E)6"ST
UP TO R.D.
4"ST UH-6 4 (E)4"ST
1 UP TO R.D.
195 R 3 11 3
ME030002 ME030004
DN.
(E)4"ST 195 R
18x4 18x4 3 (E)JB
UP TO R.D. (E)2"CONDUIT 190 R
200 200
(E)JB AHU-1 D-3 3 11 18 TRANSFER
12 3 RM 204
22
(E)LOUVER
A
1
1"HWS&R DN. ELECTRICAL EQUIPMENT
ME030001,ME030002 ME060003 (E)EXHAUST
LOUVER AREA
(E)EXHAUST GRAPHIC SCALE
FAN
SECOND FLOOR PLAN N 1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME030002.DWG

PLOT DATE: 5/21/2015 9:58:29 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SECOND FLOOR MECHANICAL PLAN
SUITE 200
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT


UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".

G6 ALL WORK IS TO BE PROVIDED UNDER PHASE IV UNLESS


OTHERWISE INDICATED.

NOTES
14 PROVIDE ROOF CURB AND PENETRATION PER ARCHITECTURAL
DETAIL.

D4 D3 D2 1 2 3 4 5 6 7

ROOF ACCESS
HATCH
D

(E)4"R.D.

(E)E.V. DN. (E)4"R.D.


(E)4"R.D. (E)4"R.D. (E)4"R.D. (E)E.V. DN. (E)4"R.D.
(E)E.V. DN. (E)E.V. DN. (E)FAN (E)E.V. DN. (E)E.V. DN.
(E)E.V. DN.
C (E)FAN (E)FAN

14 EF-1 (E)E.V. DN. (E)FAN SF-3 14

(E)FAN (E)FAN (E)FAN

14 SF-4

(E)4"R.D.
SF-1 14
(E)4"ST SPILL ON ROOF.
SEE ME0301 FOR CONTINUATION.
14 EF-2 (E)E.V. DN.
(E)E.V. DN.
14 SF-2
B (E)E.V. DN. (E)E.V. DN.
(E)4"R.D. (E)4"R.D.
(E)4"R.D. (E)4"R.D.

(E)30x30 OA

(E)4"R.D.

GRAPHIC SCALE
ROOF PLAN N 1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME030003.DWG

PLOT DATE: 5/21/2015 9:35:49 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
ROOF MECHANICAL PLAN
SUITE 200
DULLES, VIRGINIA 20166
NOTES GENERAL NOTES
13 PROVIDE FLOOR PENETRATION PER STRUCTURAL DETAIL. G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
1 COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
16x10 DN. 12 24 ROUTE 1/2"CW MAKE UP WATER TO EXPANSION TANK. PROVIDE
PRESSURE REGULATING VALVE AND BACKFLOW PREVENTER PER G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
39 AHU-1 CONTROL PANEL DETAIL 2/ME030002/ME040002. SEE DETAIL 6/ME030002/ME040002 FOR UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
32 AHU-1 VFD 2 POINTS OF CONNECTION.
G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS
13 24x16 DN. ME030003 ME030003 28 PROVIDE MANUAL AIR VENT OFF TOP OF PIPE AND 3/4"DRAIN VALVE OTHERWISE INDICATED.
WITH THREADED HOSE CONNECTION OFF BOTTOM OF PIPE.
(E)4"ST UP
TO (E)R.D. 32 CONTROL VFD BY AHU CONTROL PANEL THROUGH SIEMENS NOTES
C COMPATIBLE P1 INTERFACE.
32x18 12 REUSE/MODIFY EXISTING FLOOR PENETRATION. PROVIDE FIRE
AHU-1 D2 STOPPING.
24x6 R.G. 39 PROVIDE NETWORK CONNECTION USING CAT-6 CABLE FROM SWITCH
4"CWS&R TO NEW AHU CONTROL PANEL.

28 4"CWS&R
2"HWS&R

4"ST

AHU-1
66"Wx40"Hx12"D PLENUM
1"HWS&R

1"HWS&R

1"HWS&R
TO (E)30x30 OA B C
4"ST INTAKE ABOVE
AHU-1 D-1A AHU-1 AMS-1

4"CWS&R
18x30 2"HWS&R

40x10 24x6 R.G.


4"ST
18x32 18x26
B
(E)4"ST UP 24x6
TO (E)R.D.
30x18
ELEVATOR ELEVATOR MACHINE ROOM
30x12
AHU-1 VFD
16x16
AHU-1
16x24 DN. 13
AHU-1 AMS-1 AHU-1 D2
16x18 12 16x10 DN.
4
AHU-1 D-1A 4" CONCRETE PAD
AHU-1 D-1B ME030004 ME040003
(E)2"CONDUIT
22x18
SPLIT
16&6
(E)30x30 OA
INTAKE ABOVE 2
SECTION ME030004 ME030004
NORTH NEAR COLUMN LINE 4
SCALE: 1/4" = 1'-0"

AHU AREA FLOOR PLAN 1 N


ME030002 ME030004

KEY PLAN
NOT TO SCALE

GRAPHIC SCALE
1/4"=1'-0"
4' 2' 0 4' 8'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME030004.DWG

PLOT DATE: 5/21/2015 9:36:08 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
AHU-1 DETAILS AND SECTIONS
SUITE 200
DULLES, VIRGINIA 20166
GENERAL NOTES
SEE SCHEDULE
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
FOR PIPE SIZE
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
POWER ROOF SEE SCHEDULE
FOR DUCT SIZE
VENTILATOR G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
THERMOMETER VAV BOX UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
"D"
EXTENSION NECK TO MATCH
BOLT FAN BASE INSULATION THICKNESS
TO CURB
3 1/2" MIN
BOLT FLANGE TO
CURB AND SEAL REHEAT COIL
C
NC
PLENUM ACCESS DOOR NO

ELECTRIC CONDUIT AND SEPARABLE


THERMOMETER WELL SEE DETAILS
WIRE TO FAN. SEE MOTORIZED DAMPER WITH FOR PIPE SIZES
ELECTRICAL DRAWINGS. ACCESSIBLE LINKAGE AND ACTUATOR FROM 2x2 REDUCING TEE
BELOW CEILING AUTOMATIC
8 CONTROL VALVE
TRANSITION TEMPERATURE 1
DETAIL ME090001 ME040001 6
& PRESSURE DETAIL ME030002 ME040001
DETAIL ME040001 ME040001 SEE FLOOR PLAN TEST PLUG
POWER ROOF VENTILATOR FOR DUCT SIZE
CONDENSATE DRAIN TRAP
NO SCALE THERMOMETER INSTALLATION
SEE FLOOR PLAN
PIPING 2" AND SMALLER FOR PIPE SIZE
NO SCALE COMBINATION BALANCING AND N
4 TUR PL
Y
FLOW MEASURING DEVICE RE SUP
DETAIL ME090001 ME040001
VAV BOX HEATING COIL CONNECTION AUTOMATIC
CONTROL VALVE NC
3/4" VALVE WITH
HOSE CONNECTION
SEAL DUCT TO NO SCALE
C
WALL AIRTIGHT
PROVIDE STRUCTURAL NO
3/8" BALL HWCP-1
FRAMING ALL SIDES VALVE
0-20
12"x12" GRILL PSIG
12"x12" GRILL WITH PROVIDE EXHAUST LOUVER WITH A MAXIMUM
12"x12" NECK 0.14"W.G. P.D. AND <0.01 OZ/SF WATER
PENETRATION AT A 950 FPM FREE AREA VELOCITY. IN.
"M
BASIS OF DESIGN: RUSKIN L375D AND GREENHECK EDD-401. 1-1/2" 6D
OSHA SCREEN GUARD W

HTWS
LO

HTWR
EMERGENCY SHUTOFF F
1-1/2" AIR
N.C. CONTROL VALVE 6 THERMOMETER & WELL
1" 3 LB DENSITY SOUND LINING 2-1/2"HWS 0-20
WALL 5 ME040001 ME040001 PSIG 3/4" DRAIN VALVE
0-150 WITH HOSE CONN.
PSIG ME040001 ME040003
MOTORIZED DAMPER
PROVIDE PIPING SIZED
THERMOMETER IN WELL,
PLAN 0-150 EQUAL TO MAINS
PSIG
2
N.C. 0-450
2-1/2"HWR ASME RELIEF, SET 150 PSIG
MOUNTING SADDLES
PSIG DETAIL ME090001 ME040001
SEAL DUCT TO WALL
WALL AIRTIGHT
GALVANIZED STEEL HOUSING ASSEMBLY
BOLT TO CHANNELS
CONTROL VALVE HEATING COIL PIPING
MOUNT AT 6' AFF. 0-450 NO SCALE
TURN RELIEF VALVE N
MOUNT FAN TO WALL 4x5.4 CHANNEL
PSIG TUR
DISCHARGE PIPING DOWN WELD TO PIPE STAND AUTOMATIC RE
AND TERMINATE 4" AFF. CONTROL VALVE
3/8" BALL VALVE NC
12" MIN. Y
1" 3 LB DENSITY 6 THERMOMETER & WELL P PL
SOUND LINING SU
7 3" PIPE STAND
THERMOMETER IN WELL, (TYP) ME040001 ME040001
DETAIL ME090001 ME040001 6
0-20
WALL MOUNTED PROPELLER 3/4" DRAIN VALVE WITH
1" DIA. PIPE
WELD TO PIPE STANDS
ME040001 ME040001 PSIG
3/4" VALVE WITH
HOSE CONNECTION 6"x6"x1/4" PLATE WELDED
CEILING FAN INSTALLATION TO PIPE STAND. BOLT TO
W
HOSE CONNECTION
NO SCALE CONC. PAD WITH 2 - 1/4" F LO
BOLTS EACH PLATE AIR SEE FLOOR PLAN FOR
ELEVATION 0-20 FOR PIPE SIZES
5 4 PSIG
9 DETAIL ME090001 ME040001 4" CONC. PAD DOWEL TO FLOOR SLAB
ME040001 ME040003
DETAIL ME030001 ME040001 WATER TO WATER HEAT EXCHANGER 3/4" DRAIN VALVE
TRANSFER DUCT NO SCALE WITH HOSE CONN.
3
NO SCALE
DETAIL ME090001 ME040001
COOLING COIL PIPING
NO SCALE
FILE NAME: IF1402ME040001.DWG

PLOT DATE: 5/21/2015 9:36:41 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
MECHANICAL DETAILS
SUITE 200
DULLES, VIRGINIA 20166
RETURN MAIN
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
SUPPLY MAIN
G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
MANUAL AIR VENT C PROVIDE WALL BRACKET AND CONICAL TAP, UNLESS
N.C.
SHORT HANGER ON EITHER OTHERWISE NOTED
N.O. SHEETMETAL DUCT
SIDE OF PUMP
0-60 PSI 0-60 PSI SEAL DUCT TO
* 3/8" BALL WALL AIRTIGHT
VALVE (TYP.)
GATE VALVE (TYP)

12"x12" GRILL

SUPPORT FROM JOIST 2-1/2" M.B.D.


STRUCTURE UNLESS PROVIDE SILENT
5 PRESSURE AND
OTHERWISE INDICATED CHECK VALVE STAINLESS STEEL DRAW BAND
TEMPERATURE
DETAIL ME090001 ME040002 TEST PLUG (TYP.)
FLEXIBLE DUCT SIZE
VERTICAL IN-LINE PUMP SAME AS DIFFUSER
NECK, MAXIMUM 6' IN
1" 3 LB DENSITY SOUND LINING
DIRT LEG NO SCALE WALL
LENGTH.

* THE FLOW CONTROL VALVES SHALL BE


INSTALLED BY THE CONTRACTOR DUCT COLLAR PLAN
IN CONFORMANCE WITH VALVE MFGR'S OPPOSED BLADE DAMPER
RECOMMENDED SPACING UP/DOWNSTREAM STAINLESS STEEL DRAW BAND
FROM PIPE CHANGES IN DIRECTION AND/OR EQUALIZING GRID
SEAL DUCT TO WALL
OTHER VALVES/COMPONENTS IN THE PROVIDE MANUFACTURER INSULATED
WALL AIRTIGHT
PIPING. BACKPAN. PROVIDE 1/2" FIBERGLASS
7
INSULATION WITH VAPOR BARRIER.
DETAIL ME090001 ME040002 PROVIDE 24"x24" SQUARE FACE, ROUND NECK, 12"x12" GRILL
T-BAR CEILING GRID
HORIZONTAL HOT WATER CEILING DIFFUSER WITH FRAME SUITABLE FOR
CEILING IN WHICH DEVICE IS INSTALLED. NECK
12" MIN.
UNIT HEATER PIPING THERMOMETER SIZE PER DIFFUSER SCHEDULE. SEE PLANS
FOR CFM.
NO SCALE
3
DETAIL ME090002 ME040002 1" 3 LB DENSITY
HWS SOUND LINING
HWR
MAKE ALL TAKE-OFFS CEILING DIFFUSER CEILING
WITH SWING JOINTS NO SCALE
MANUAL AIR
VENT P & T RELIEF VALVE
SUSPENDED FROM STRUCTURE
(E)HW SIZED BY MANUFACTURER
ELEVATION
(TYP 4 PLACES) C SUCTION 1
N.C. HEADER
DISCHARGE
DETAIL ME030001,ME030002 ME040002
DWH-1
GATE VALVE
(TYP) 3/4"CW MAKE UP
HEADER TRANSFER DUCT
NO SCALE
TO ET-1. SEE ME03.0002
FOR CONTINUATION.
1/2" GAGE GLASS 1/4"
PIPE FULL SIZE CAST IRON 3/4"
GUARD RODS &
TO FLOOR (TYP.) FILL CAP BALL CHECKS
(E)HW 3/4" DRAIN VALVE
UNION DIRT LEG
WITH HOSE
VERTICAL PROPELLER CONNECTION SAMPLE
UNIT HEATER OUTLET
TO DEMOLISHED 5 GAL. TANK
* THE FLOW CONTROL VALVES HTHW WATER HEATER SUSPEND FROM
SHALL BE INSTALLED BY THE CONTRACTOR (E)CW 3/4"
FLOOR STRUCTURE ABOVE
IN CONFORMANCE WITH VALVE MFGR'S WITH 3/8" DIA. RODS
RECOMMENDED SPACING UP/DOWNSTREAM 6
FROM PIPE CHANGES IN DIRECTION AND/
OR OTHER VALVES/COMPONENTS IN THE DETAIL ME030002,ME090001 ME040002 SEE FLOOR PLAN
PIPING
8 ELECTRIC WATER HEATER DRAIN VALVE FOR SIZE & CONTINUATION
NO SCALE
DETAIL ME090001 ME040002 5 GALLON BYPASS FEEDER
3/4" GATE VALVE & NIPPLE
VERTICAL HOT WATER SUPPORT LEGS (TYP. OF 3)
AIR SEPARATOR
SEE FLOOR PLAN
FOR SIZE & CONTINUATION
UNIT HEATER PIPING 4 2 MANUAL VENT
LOCATED AT 4'AFF.
NO SCALE
DETAIL ME030002 ME040002 DETAIL ME090001 ME040002
CHEMICAL FEEDER AIR SEPARATOR
NO SCALE NO SCALE
FILE NAME: IF1402ME040002.DWG

PLOT DATE: 5/21/2015 9:36:56 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
MECHANICAL DETAILS
SUITE 200
DULLES, VIRGINIA 20166
PROVIDE 4" THICK 3000PSI CONCRETE PAD
WITH #3 BARS AT 12" O.C. EACH WAY IN UPPER
THIRD OF SLAB THICKNESS.
GENERAL NOTES
EXISTING SLAB
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT


UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
APPLY BONDING COMPOUND PER
THE STRUCTURAL NOTES
BETWEEN PAD AND EXISTING SLAB.
FIELD WELD PIPE TO TEE (TYP.)
4 ASME RELIEF VALVE
DETAIL ME030004,ME040001 ME040003 2-1/2" (TYP.) SET @ 80 PSIG

10-5/8"
TYPE 304 SS FACING PLATE ON TEE (TYP.) REDUCED PRESSURE
CONCRETE PAD STEEL BASE PLATE WITH MIN. 1/16" THICK
TO PUMP SUCTION
BACKFLOW PREVENTER
NO SCALE 21"x12", 5/8" THICK PTFE SLIDE PAD FIELD WELDED TO STEEL 0-100 PSI
9-1/2" 9-1/2" 9-1/2" EMBED (TYP.) 3/4" CW
STEEL EMBED. 4" 9-1/2"
STRUCTURAL NOTES SEE STRUCTURAL 1-1/4" 1/2" 1/4" 4-1/4" 4-1/2" 3-1/4" 31"x12", 5/8" THICK STEEL EMBED. SEE MAKE-UP
STRUCTURAL DRAWINGS.
CAST IN PLACE CONCRETE CONSTRUCTION: PROVIDE CONCRETE CONFORMING DRAWINGS.
TO ALL REQUIREMENTS OF ACI 301-99, ACI 318-02 AND THE ACI DETAILING 75 PSIG
24 PSIG INDIRECT WASTE
MANUAL. PROVIDE CONCRETE CONSTRUCTION CONFORMING TO THE CONNECTION
FOLLOWING CRITERIA:
*PROVIDE MSS SP-69 & SP-58 TYPE 35 COMPLIANT SLIDE PLATE ASSEMBLY TO FLOOR DRAIN
MINIMUM ULTIMATE
TO ALLOW MINIMUM 2-1/2" MOVEMENT IN ALL DIRECTIONS
STRUCTURE COMPRESSIVE STRENGTH MAXIMUM ENTRAINED
TYPE @ 28 DAYS F'c (PSI) WATER/CEMENT RATIO AIR RANGE (%) FULL SIZE OF
PIPE OUTLET
EQUIPMENT 3,000 0.55 2-4% TO FLOOR DRAIN
PAD DIAPHRAGM
TYPE
PROVIDE CEMENT CONFORMING WITH ASTM C 150, TYPE 1. USE DRINKABLE EXPANSION
WATER. PROVIDE AGGREGATE CONFORMING WITH ASTM C 33. PROVIDE TANK
CONCRETE ADMIXTURES CONTAINING NO MORE THAN 0.1 PERCENT CHLORIDE
IONS. PROVIDE AIR ENTRAINING ADMIXTURE CONFORMING TO ASTM C 260. USE 1"
3 INCH MAXIMUM SLUMP. PROVIDE A WATER BASED EPOXY RESIN/PORTLAND
CEMENT BONDING AGENT SUCH AS SIKA ARMATEC 110 OR EQUIVALENT.
PROVIDE SURFACE PREPARATION AND PRODUCT APPLICATION IN ACCORDANCE FIELD WELD PIPE
WITH MANUFACTURER'S RECOMMENDATIONS. APPLY A SMOOTH TROWEL FINISH TO TEE (TYP.)
TO THE TOP OF THE EQUIPMENT PAD. 38"
3/4" DRAIN W/
TYPE 304 SS FACING HOSE CONN.
CONCRETE REINFORCEMENT: PROVIDE HIGH STRENGTH NEW BILLET STEEL BASE PLATE WITH MIN. 1/16" PLATE ON TEE (TYP.)
DEFORMED STEEL REINFORCEMENT CONFORMING TO ASTM A615, GRADE 60. THICK PTFE SLIDE PAD (TYP.)
PROVIDE DETAILS OF STEEL REINFORCEMENT CONFORMING TO ACI 318-89 AND WELDED TO STEEL EMBED.
CRSI STANDARDS. PROVIDE A MINIMUM OF 1 INCH CONCRETE PROTECTION FOR
STEEL REINFORCEMENT OF CAST-IN-PLACE CONCRETE.
STEEL EMBED. SEE 1
CONTRACTOR: FIELD VERIFY ALL DIMENSIONS OF EXISTING CONSTRUCTION. IF
DEVIATIONS ARE FOUND, PROVIDE A WRITTEN REPORT TO THE CONTRACTING
STRUCTURAL DRAWINGS (TYP.)
DETAIL ME030002,ME090001 ME040003
OFFICER. 2-1/4" (TYP.)
2-1/4" (TYP.) 5" (TYP.) EXPANSION TANK
NO SCALE
*PROVIDE MSS SP-69 & SP-58 TYPE 35 COMPLIANT SLIDE PLATE ASSEMBLY
TO ALLOW MINIMUM 2-1/2" MOVEMENT IN ALL DIRECTIONS

ATTACH TO ANCHOR DEVICE


3
DETAIL ME030002 ME040003
4 1/2" PRESSURE GAUGE
0-600 PSIG SCALE FOR HTHW
PIPE SLIDE ASSEMBLY
1/4" NPT CONNECTION NO SCALE
WELDED LINKED EYE RODS

COUPLING
1/4" NPT SCHEDULE 80 SIPHON LOCK NUT WELDLESS EYE NUT
1/2" x 1/4" THREADED BUSHING
1/2" CLASS 800 FORGED STEEL
THREADED, ANGLE GLOBE VALVE MSS SP-58 TYPE 3 PIPE
1/2" x 6"LG SCH 80 STEEL NIPPLE CLAMP. REFER TO FLOOR
WELD NIPPLE PLANS FOR PIPE SIZES.

PIPE
5
DETAIL ME040001 ME040003 2
H.P. GAUGE DETAIL ME030002 ME040003
NO SCALE
HEATING WATER PIPE HANGER
NO SCALE
FILE NAME: IF1402ME040003.DWG

PLOT DATE: 5/21/2015 9:37:25 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
MECHANICAL DETAILS
SUITE 200
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT
AND COORDINATE ALL WORK PRIOR TO THE START OF
CONSTRUCTION.

G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS


CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.",
OR "(E)".

G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS


OTHERWISE INDICATED.
B
4 14 SF-1 NOTES
A (E)E.V. C D 4 PERFORM WORK DURING PHASE IV.

14 PROVIDE ROOF CURB AND PENETRATION PER ARCHITECTURAL


DETAILS.

25 PROVIDE GE SENSING DF868 ULTRASONIC BTU METER.


4 30x30 2-1/2"HWS&R

SEE STRUCTURAL DRAWINGS FOR CONNECTION DETAILS (TYP.)

4 42x30 REGISTER 4 42x30 REGISTER


12 GAUGE STEEL GALVANIZED PIPE CLAMP
3/4"HWS&R WELDED TO SQUARE TUB ALONG ALL EDGES (TYP.)

5/16" SLOTTED HEX HEAD MACHINE SCREW (TYP.)


4"CWS&R UH-1

WELD RISER PIPE CLAMP TO BEAM (TYP.)


SEE STRUCTURAL DRAWINGS FOR CONNECTION DETAILS (TYP.) (E)JB (E)LIGHT
2 (E)JB
(E)JB WELD 4"x4" SQUARE TUBE TO BEAM.
ME060001 ME060001

4"x4" SQUARE TUBE HWP-1


AS-1

25 BTU METER

BTU METER PANEL UNION TO ALLOW FOR REMOVAL OF HX-1 TUBES


8'9" (E)JB
EF-1 STARTER
SF-1 STARTER HX-1 SEE STRUCTURAL DRAWINGS FOR CONNECTION DETAILS (TYP.)
SF-2 STARTER HX-1 CONTROL PANEL

SEE STRUCTURAL DRAWINGS FOR CONNECTION DETAILS (TYP.)

HX TUBE PULL AREA


1-1/2" PIPE STAND
2"HTWS&R. SEE ME03.0001 FOR
4"CWS&R. SEE ME03.0001 FOR CONTINUATION
CONTINUATION
(E)JB
1 2
SECTION ME030001,ME030002 ME060001 DETAIL ME060001 ME060001
NORTH NEAR COLUMN LINE 4 TYPICAL PIPING SUPPORT ALONG WALL
SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0"

GRAPHIC SCALE
1/4"=1'-0"
4' 2' 0 4' 8'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME060001.DWG

PLOT DATE: 5/21/2015 9:37:43 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
MECHANICAL SECTIONS
SUITE 200
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT
AND COORDINATE ALL WORK PRIOR TO THE START OF
CONSTRUCTION.

G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS


CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.",
OR "(E)".

G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS


OTHERWISE INDICATED.

D4 D3 D2 1 NOTES
4"CWS&R
2-1/2"HWS&R BEHIND 4 PERFORM WORK DURING PHASE IV.

4 14 EF-1 14 PROVIDE ROOF CURB AND PENETRATION PER ARCHITECTURAL


DETAILS.
3/4"M.A.V. (E)4"ST SPILL TO LOW ROOF.
SEE ME0303 FOR CONTINUATION.
3/4"M.A.V.
3/4"M.A.V. 3/4"M.A.V.
30x18
4"CWR 46x46
4"ST
(E)4"ST

2-1/2"HWS 2"HWS 18x30


10x40
3/4"DRAIN VALVE WITH HOSE CONNECTION 3/4"DRAIN VALVE WITH HOSE CONNECTION
3/4"DRAIN VALVE WITH HOSE CONNECTION

UH-1 UH-3 UH-4 AHU-1

12x30 RETURN DUCT BEYOND


SUPPLY FAN SECTION

66"Wx40"Hx12"D PLENUM

3
COOLING COIL SECTION
4" CONCRETE PAD
ACCESS SECTION ME060001 ME040001
2
HEATING COIL SECTION
FILTER SECTION ME060001 ME040001
3/4"DRAIN VALVE WITH HOSE CONNECTION

1
SECTION ME030001,ME030002 ME060002
EAST NEAR COLUMN LINE B
SCALE: 1/4" = 1'-0"

GRAPHIC SCALE
1/4"=1'-0"
4' 2' 0 4' 8'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME060002.DWG

PLOT DATE: 5/21/2015 9:39:58 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
MECHANICAL SECTIONS
SUITE 200
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT
AND COORDINATE ALL WORK PRIOR TO THE START OF
CONSTRUCTION.

G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS


CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.",
OR "(E)".

G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS


OTHERWISE NOTED.

D C (E)FAN B A NOTES
4 14 SF-2
4 PERFORM WORK DURING PHASE IV.
(E)JB
(E)CONDUIT 14 PROVIDE ROOF CURB AND PENETRATION PER ARCHITECTURAL
DETAILS.

30x30 4

(E)E.V. UP 4"ST
TO ROOF
2"HWS&R

4"CWS&R
UH-4
42x30 REGISTER 4
4 42x30 REGISTER

1
SECTION ME030001,ME030002 ME060003
SOUTH NEAR COLUMN LINE 1
SCALE: 1/4" = 1'-0"

GRAPHIC SCALE
1/4"=1'-0"
4' 2' 0 4' 8'
CAUTION: IF THIS DRAWING IS A REDUCTION,
FILE NAME: IF1402ME060003.DWG

PLOT DATE: 5/21/2015 9:40:10 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
MECHANICAL SECTIONS
SUITE 200
DULLES, VIRGINIA 20166
NOTES GENERAL NOTES
2 PERFORM WORK DURING PHASE II.
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT
AND COORDINATE ALL WORK PRIOR TO THE START OF
3 PERFORM WORK DURING PHASE III.
CONSTRUCTION.
4 PERFORM WORK DURING PHASE IV.
G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.",
25 PROVIDE GE SENSING DF868 ULTRASONIC BTU METER.
OR "(E)".

G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS


OTHERWISE INDICATED.

D4 D3 D2 1 2 3 4 5 6 7

3/4" M.A.V.

3/4" M.A.V. 3/4" M.A.V.


4"CWS
4"CWR 4"CWS&R CAPPED WITH BLIND FLANGE FOR FUTURE USE
2-1/2"HWS
3/4" M.A.V.
2-1/2"HWR
2"HWS
2"HWR 3/4" DRAIN VALVE WITH HOSE CONNECTION 1"HWR 4
(E)HW 4 1-1/4"HWS 1"HWS 4
1"HWS&R 2
4 1-1/4"HWR

(E)3/4" VENT TO (E) FL.D.

2"HWR 1-1/2"HWR 4
UH-1 UH-2 UH-3 UH-4 2"HWS 1-1/2"HWS 4
VAV-6 VAV-4 3
3/4" DRAIN VALVE WITH 3/4" DRAIN VALVE WITH
3/4"CW
HOSE CONNECTION HOSE CONNECTION
UH-5 4 UH-6 4 UH-7 4 UH-8 4 UH-9 4
(E)
HWCP-1 REDUCED PRESSURE
PRINCIPLE BACKFLOW 3/4"MU
PREVENTER
DWH-1 (E) 3/4" DRAIN VALVE WITH
AHU-1 (E)
(E) TO FLOOR DRAIN HOSE CONNECTION
2 GALLON CHEMICAL FEED TANK
SECOND FLOOR
HWP-1
(E)CW
AS-1 UH-10 ET-1
TT

VAV-1 2 VAV-3 2 2 3/4"HWS&R 2 VAV-2 VAV-5 2


TT ULTRASONIC FLOW METER 25
TT

TT
TT

1-1/4" TT

TT

HX-1
TT

3/4" DRAIN VALVE WITH HOSE CONNECTION FIRST FLOOR

2"HTWS
2"HTWR
HIGH TEMPERATURE HEATING WATER,
HEATING WATER, AND CHILLED WATER RISER
NO SCALE
FILE NAME: IF1402ME070001.DWG

PLOT DATE: 5/21/2015 9:40:28 AM

HIGH TEMPERATURE HOT WATER,


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
HEATING WATER, AND CHILLED WATER
SUITE 200
DULLES, VIRGINIA 20166 RISER DIAGRAM
VAV BOX SCHEDULE 2 4
SOUND REQUIREMENTS GENERAL NOTES
VAV BOX INFORMATION
SCHEDULE UNIT HEATER SCHEDULE G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
TYPE MOTOR ENTERING HEATING COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
HEATING COIL 3 UNIT WATER LOCATION
1 CFM RPM AIR TEMP. CAPACITY GPM 3
BALANCE MINIMUM SCHEDULE ALL SOUND DATA SHALL BE MEASURED IN ACCORDANCE WITH ARI NO. 1 HP 2 P.D. FT. AREA SERVED
BTUH G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
VAV BOX CONTROL SOUND AREA STANDARD 880 WITH AN INLET PRESSURE OF 1.0" W.G., UNLESS OTHERWISE
AIR FLOW AIR FLOW MAX UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
IDENTIFIER NAME REQ. SERVICE L.A.T. SERVED
(CFM) (CFM) E.A.T. NOTED. UH-1 THRU UH-9 VERT 5 6 2500 1075 1/4 14 100,000 3.3 5 MAINTENANCE BAYS
HEATING AIR GPM
FLOW (CFM) G7 PROVIDE ALL IDENTIFYING TAGS, NAMEPLATES, AND CONTROL
MAXIMUM SOUND POWER LEVELS: UH-10 HORIZ 4 2500 1075 1/4 14 90,300 3.0 5 FIRST FLOOR STORAGE POINTS TO MATCH CONTROL NAME. CONTROL NAME IS IDENTIFIER
VAV-1 2 VAV-C1 A 280 56 SUPPLY 139 55 82.0 1.0 OFFICE 111
DESIGNATION dB re 10 -12
WATTS TO BE USED BY BMS. CONTROL NAME AND CONTROL GRAPHICS
VAV-2 2 VAV-D3 A 280 63 SUPPLY 144 55 80.9 1.0 106 & 114 IN VAV BOX
NOTES: 1 HORIZ - HORIZONTAL DISCHARGE PROPELLER WITH INDIVIDUALLY ADJUSTABLE DISCHARGE LOUVERS. MUST BE APPROVED BY OWNER.
VAV-3 2 VAV-C2 NA 465 93 SUPPLY 232 55 88.3 1.0 LOCKER RM. SCHEDULE
OCTAVE BAND 2 3 4 5 6 7 VERT - VERTICAL DISCHARGE PROPELLER WITH INDIVIDUALLY ADJUSTABLE DISCHARGE LOUVERS.
VAV-4 3 VAV-D2A B 795 159 SUPPLY 397 55 79.0 1.0 OFFICE 202
Hz 125 250 500 1000 2000 4000
VAV-5 2 VAV-D2B B 920 218 SUPPLY 459 55 75.1 1.0 BREAK RM. 2 115V/1PH/60HZ. NOTES
VAV-6 1 VAV-D2C NA 1725 344 SUPPLY 862 55 86.6 1.5 STORAGE RADIATED L 62 59 48 42 41 35 3
A 1 PERFORM WORK DURING PHASE I.
NOTES: DISCHARGE L 74 69 59 57 53 53 4 PROVIDE PER DETAIL 7/ME090001/ME040002
1 ALL PIPING RUNOUTS ARE 3/4" 2 PERFORM WORK DURING PHASE II.
RADIATED L 64 58 54 51 49 38 5 PROVIDE PER DETAIL 8/ME090001/ME040002
B
DISCHARGE L 72 67 64 61 56 53 3 PERFORM WORK DURING PHASE III.
2 INSTALL PER DETAIL 4/ME090001/ME040001. 6 MOUNT AT 21 FT AFF.

3 4 PERFORM WORK DURING PHASE IV.

4 BOXES WITH HEATING COILS: MAXIMUM AIR PRESSURE DROP THROUGH BOX, INCLUDING REHEAT
COIL, OF 0.45" W.G. AT SCHEDULED MAX. AIRFLOW.
CONTROL VALVE SCHEDULE
VALVE CLOSE
UNIT NO.
NO.
SERVICE TYPE GPM Cv
OFF (PSI) CONTROL DAMPER SCHEDULE
FAN SCHEDULE DAMPER BALANCE
FAN MAX WEIGHT AHU-1 V-1 HEATING WATER 3-WAY 2 1.3 60 UNIT NO. SERVICE VOLUME SIZE
NO.
WHEEL T.S.P. BHP MOTOR ELECTRICAL DATA FOOTPRINT TOTAL SERVICE
UNIT NO. TYPE CFM RPM AHU-1 V-2 CHILLED WATER 2-WAY 21 14.3 100 AHU-1 D-1A MIN. OUTSIDE AIR 1,265 6x18
DIA. IN. IN W.G. MAX. H.P. V/PH/Hz LBS/SF LBS
EF-1 4 PRV 3 44 17,000 1.0 562 6.1 7.5 460/3/60 47 700 NORTH BAY EXHAUST HX-1 V-1 HTHW 2-WAY 16.5 10.9 450 AHU-1 D-1B MAX. OUTSIDE AIR 2,935 16x18
EF-2 4 PRV 3 44 17,000 1.0 562 6.1 7.5 460/3/60 47 700 SOUTH BAY EXHAUST AHU-1 D-2 RETURN AIR 2,935 16x16
HX-1 V-2 HTHW 2-WAY 16.5 10.9 450
EF-3 2 PROP 2 14 465 0.25 1125 0.09 0.25 115/1/60 9 30 LOCKER ROOM EXHAUST AHU-1 D-3 RELIEF AIR 2,935 30x18
UH-# V-1 HEATING WATER 3-WAY 3.3 2.2 60
EF-4 1 SWSI 13.25 800 0.7 1825 0.19 0.25 115/1/60 24 106 TOILET AND JANITOR EXHAUST
NOTES: TERMINAL EQUIPMENT: FOR FLOW RATES LESS THAN EQUAL TO 1.5 NOTES: ALL DAMPERS SHALL BE OPPOSED BLADE
EF-5 2 PROP 2 14 1935 0.25 1633 0.24 0.33 115/1/60 9 40 FIRST FLOOR SHOP VENTILATION CONFIGURATION AND MODULATING.
GPM, SELECT CONTROL VALVE WITH A Cv OF 1.0.
SF-1 4 PRV 3 30 8500 1.0 1488 3.41 5.0 460/3/60 90 900 NORTH BAY SUPPLY
SF-2 4 PRV 3 30 8500 1.0 1488 3.41 5.0 460/3/60 90 900 NORTH BAY SUPPLY
SF-3 4 PRV 3 30 8500 1.0 1488 3.41 5.0 460/3/60 90 900 SOUTH BAY SUPPLY
1 PUMP SCHEDULE 1 2

30 8500 1.0 1488 3.41 5.0 460/3/60 90 900 SOUTH BAY SUPPLY UNIT CONTROL HEAD BHP MOTOR ELECTRICAL DATA
SF-4 4 PRV 3 TYPE FLUID GPM RPM EFF. SERVICE
NOTES:
NO. NAME FT. MAX. HP V/PH/Hz 1 AIR SEPARATOR SCHEDULE 1

1 SWSI = SINGLE WIDTH, SINGLE INLET CENTRIFUGAL, BELT DRIVEN. 2 INSTALL PER DETAIL 7/ME090001/ME040001. HWP-1 HWP-C04 IC WATER 42 42 3600 37 0.7 1.5 460/3/60 HEATING WATER UNIT MAX. P.D.
SIZE GPM SERVICE
PROP = DIRECT DRIVE, PROPELLER WALL FAN WITH OSHA MOTOR GUARD
NO. FT. OF WATER
3 INSTALL PER DETAIL 8/ME090001/ME040001.
PRV = POWER ROOF VENTILATOR, DIRECT DRIVE, WITH DISCONNECT SWITCH, BIRDSCREEN, HWCP-1 HWCP-C1 IC WATER 5 15 3600 37 0.3 0.5 115/1/60 HEATING WATER AS-1 2" 42 0.5 HEATING WATER
MOTORIZED DAMPER, AND FAN MOUNTED SPEED CONTROLLER.
NOTES: 1 IC = INLINE CIRCULATOR, CLOSE COUPLED 2 INSTALL PER DETAIL 5/ME090001/ME040002. NOTES: 1 INSTALL PER DETAIL 4/ME090001/ME040002.

1 WATER TO WATER CONVERTOR SCHEDULE 1 DOMESTIC WATER HEATER 1

TUBE SIDE 2 SHELL SIDE 2 PHYSICAL


1 EXPANSION TANK SCHEDULE 1 2
UNIT ENT. FLUID LVG. FLUID TANK VOLUME ELECTRICAL
UNIT CONTROL FLUID
ENT. FLUID LVG. FLUID MAX P.D. FOULING MAX TUBE ENT. FLUID LVG. FLUID MAX P.D. FOULING MAX TUBE MAX. SHELL MIN. SHELL UNIT TANK VOL. ACCEPT. VOL. INITIAL CHARGE NO. GALLONS kW 2 3
NO. NAME GPM FLUID GPM FLUID SERVICE NO. TANK SIZE SERVICE
LENGTH, FT (GALLONS) (GALLONS) (PSIG)
FT. WTR FACTOR VELOCITY FT. WTR FACTOR VELOCITY DIA. INCHES
DWH-1 WATER 40 140 80 27
SHOP 1 ET-1 18 6 12 HEATING WATER
HX-1 HX-C04 16.5 WATER 380 240 5 0.0005 6.5 42 WATER 147 200 5 0.0005 6.5 5 4
HEATING NOTES: 1 SELF CONTAINED CONTROLS AND DISCONNECT
NOTES: 1 PROVIDE 3/4" DRAIN, VALVE, HOSE CONNECTION AND CAP.
NOTES: 1 INSTALL PER DETAIL 5/ME090001/ME040001. 2 2 3 6 HEATING ELEMENTS
2 INSTALL PER DETAIL 1/ME090001/ME040003.

1 AIR HANDLING UNIT SCHEDULE 4


TOTAL MIN. SUPPLY FAN 9 COOLING COIL 6 8 HEATING COIL 1 3 FILTERS MAX WEIGHT
UNIT CONTROL
SUPPLY O.A. WHEEL EXT. S.P. T.S.P. BHP MOTOR AIR MAX. F.V. MAX. P.D. CAPACITY MBH ENT. LVG. WATER WATER AIR MAX. F.V. MAX. P.D. CAPACITY E.A.T. L.A.T. WATER WATER MAX. P.D. IN W.G. ASHRAE FOOTPRINT TOTAL AREA SERVED NOTES
No. NAME TYPE CFM RPM VOLTAGE
CFM CFM DIA. IN. IN W.G. IN W.G. MAX. H.P. CFM FPM IN W.G. TOTAL SENSIBLE D.B. W.B. D.B. W.B. GPM P.D. CFM FPM IN W.G. MBH GPM P.D. INITIAL FINAL % EFF. LBS/SF LBS
AHU-1 AHU-C1 4,465 1,265 AIRFOIL 7 15 4,465 2.1 5.0 3420 6.9 7.5 460/3 5 4,200 500 1.0 205.34 142.0 81.7 67.1 51.0 50.5 36 56 21 10 FT 1,265 550 0.2 51.5 14 51 5 6 FT 0.95 1.75 2 44.1 2,500 CENTER BAY 4
NOTES:
1 3 INSTALL PER DETAIL 3/ME090001/ME040001. 5 PROVIDE PREMIUM EFFICIENCY MOTOR AND VFD. 7 CLASS 1 FAN SHALL OPERATE WITHOUT SURGE BETWEEN 900 9 PROVIDE FAN WITH INTEGRAL PIEZOMETRIC FLOW
CFM, 0.3"W.G. AND 4,465 CFM, 5"W.G. MEASURING RING ON INLET.
PROVIDE 2" MERV-8 PRE-FILTER. PROVIDE 12" CARTRIDGE MERV-13A FINAL FILTER. 6 PROVIDE CONDENSATE DRAIN PER DETAIL 1/ME090001/ME040001.
2 4 PROVIDE AHU PER DETAIL 1/ME090001/ME030004. 8 INSTALL PER DETAIL 2/ME090001/ME040001.
BALANCE FAN BY FALSELY LOADING FILTER BANK TO 1.75"W.G.

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
MECHANICAL SCHEDULES
SUITE 200
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT


UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".

AIR DEVICE SCHEDULE


OVERALL MAX. S.P.
AIR VOLUME NECK SIZE SIZE DROP MAX. HORIZONTAL
SYMBOL THROW @ 100 FACE REMARKS
(CFM) (INCHES) (INCHES) (IN. W.G.) N.C. FPM
0 DEGREE
R 0-75 NA 6x6 0.06 25 3 3/4"SPACING, STEEL REGISTER
DEFLECTION
0 DEGREE
R 80-200 NA 8x6 0.06 30 19 3/4"SPACING, STEEL REGISTER
DEFLECTION
0 DEGREE
R 4250 NA 42x30 0.06 35 92 3/4"SPACING, STEEL REGISTER
DEFLECTION
2 CONE
50-120 6 1 24x24 0.06 30 FACE 4-WAY BLOW

4 CONE
125-225 8 1 24x24 0.06 30 FACE 4-WAY BLOW

5 CONE
230-330 10 1 24x24 0.06 30 FACE 4-WAY BLOW

50-1000 22x22 2 24x24 0.04 30 - PERFORATED


NOTES: 1 INSTALL PER DETAIL 3/ME090002/ME040002. 2 ALL UNDUCTED RETURN DIFFUSERS.

DUCTWORK CLASSIFICATION SCHEDULE


DUCT TYPE AND LOCATION PRESSURE IN. W.G. SEAL CLASS

SUPPLY AIR DUCT FROM DISCHARGE OF AIR HANDLING UNIT


4 A
TO VARIABLE AIR VOLUME BOX

SUPPLY AIR DUCT FROM VARIABLE AIR VOLUME BOX DISCHARGE


2 A
TO SUPPLY AIR OUTLETS.

RETURN AIR AND GENERAL EXHAUST TO AIR HANDLING UNIT -1 B


& EXHAUST DUCTWORK.
FILE NAME: IF1402ME090002.DWG

PLOT DATE: 5/21/2015 9:48:02 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
MECHANICAL SCHEDULES
SUITE 200
DULLES, VIRGINIA 20166
EXISTING INSULATION
FAN, FILTER OR
OTHER DEVICE SYMBOLS & ABBREVIATIONS GENERAL REQUIREMENTS
AIR FLOW PROVIDE
BRACKET M CONTROL AIR MAIN CONNECTION 1. PROVIDE THE FOLLOWING AUTOMATIC ALARM AT OWS EVERY MARCH 1ST AND
UPSTREAM PITOT TUBE DOWNSTREAM PITOT TUBE PER SEPTEMBER 1ST: "IN CONFORMANCE WITH THE LOCAL BUILDING CODES,
INSTALL IN ACCORDANCE INSTALL IN ACCORDANCE D-# EXECUTIVE ORDERS, AND IN ORDER TO SAVE ENERGY, BUILDING SENSORS MUST
5 AUTOMATIC TEMPERATURE CONTROL MODULATING DAMPER.
BE CALIBRATED AND CLEANED AT REGULAR INTERVALS. OUTSIDE AIR, DUCT, AND
3 3 UNIT-MOUNTED TEMPERATURE, HUMIDITY, AND ENTHALPY SENSORS SHOULD BE
WITH DETAIL WITH DETAIL ME100001 ME100001 D-#
ME100001 ME100001 AUTOMATIC TEMPERATURE CONTROL TWO POSITION DAMPER. CALIBRATED ANNUALLY. AIR-FLOW MEASURING STATIONS SHOULD BE CLEANED
ME100001 ME100001
EVERY SIX MONTHS."
A-#
PROVIDE 0.25"
DAMPER ACTUATOR.
0.25" TYPE M
RIGID COPPER TUBE
RIGID COPPER
SUPPORT TUBE
SYMBOLS & ABREVIATIONS
DIFFERENTIAL PRESSURE SWITCH
OR TRANSMITTER. PROVIDE 2 WAY AUTOMATIC TEMPERATURE CONTROL VALVE. AI ANALOG INPUT
WIRE AND BRACKET IN ACCORDANCE V-#
CONDUIT TO SCREW TO AO ANALOG OUTPUT
FIELD PANEL 5 DUCT/CASING 3 WAY AUTOMATIC TEMPERATURE CONTROL VALVE.
WITH DETAIL BI BINARY INPUT
ME100001 ME100001 WITH SELF DRILLING/ #12 BARE COPPER WIRE V-#
4 TAPPING SCREWS ARRANGE IN UNIFORM MANNER THRU SPACE BO BINARY OUTPUT
DETAIL ME100001 ME100001 TEST TEE WITH PLUG
1
HYDRONIC PIPING
CLG COOLING
AIR DIFFERENTIAL PRESSURE DEVICE DETAIL ME100001 ME100001 AIR OR WATER FLOW PATH
NO SCALE COV CHANGE OF VALUE
SENSING ELEMENT Cx COMMISSIONING
INSTALLATION FILTER OR COIL (AS LABELED)
HTG HEATING
NO SCALE
AIR OR WATER DIFFERENTIAL PRESSURE SWITCH, BY APPLICATION. I/O INPUT/OUTPUT
18 GAUGE GALVANIZED SHEET METAL JUNCTION BOX AND COVER DP-# PROVIDE AIR SWITCH PER DETAIL 4/ME10.0001/ME10.0001.
BRACKET ATTACHED TO DUCT WITH PROVIDE WATER SWITCH PER DETAIL 6/ME10.0001/ME10.0001. NVI NETWORK VARIABLE INPUT
FOUR #8 x 0.75" SHEET METAL SCREWS CONDUIT TO
FIELD PANEL G DIFFERENTIAL PRESSURE GAUGE, CONNECT TO STATIC NVO NETWORK VARIABLE OUTPUT
PRESSURE TAPS IN ACCORDANCE WITH DETAIL 3/ME10.0001/ME10.0001.
PROVIDE RIGID FIBERGLASS INSULATION SP SETPOINT
WITH VAPOR BARRIER, THICKNESS TO DPT-# AIR OR WATER DIFFERENTIAL PRESSURE TRANSMITTER, BY APPLICATION.
MATCH ADJACENT INSULATION PROVIDE AIR TRANSMITTER PER DETAIL 4/ME10.0001/ME10.0001. HAND-OFF-AUTO SWITCH
PROVIDE WATER TRANSMITTER PER DETAIL 6/ME10.0001/ME10.0001.

FZ-# MOTOR
SEAL VAPOR TIGHT WITH LOW TEMPERATURE DETECTION FREEZESTAT, MANUAL RESET, WITH
VAPOR BARRIER MASTIC FLEXIBLE METAL CONDUIT
20 FOOT ELEMENT. PROVIDE PER DETAILS 1/ME10.0001/ME10.0001 NORMALLY OPEN CONTACTS
TO OTHER DEVICES, IF PROVIDE BRACKET IN 5
ATTACH DEVICE TO BRACKET AND 2/ME10.0001/ME10.0001.
NEEDED ACCORDANCE WITH
PROVIDE RIGID FIBERGLASS INSULATION WITH SHEET METAL SCREWS ME100001 ME100001 NORMALLY CLOSED CONTACTS
WITH VAPOR BARRIER, THICKNESS TO
FLEXIBLE CONDUIT BETWEEN JUNCTION BOX AND DEVICE RELAY COIL
MATCH ADJACENT INSULATION DUCT MOUNTED ELECTRONIC TEMPERATURE SENSOR WITH
TO ALLOW REMOVAL, MINIMUM LENGTH OF 3 FT.
20 FOOT AVERAGING ELEMENT. PROVIDE PER DETAILS
TS-# 1/ME10.0001/ME10.0001 AND 2/ME10.0001/ME10.0001. STARTER HOLDING COIL
NOTE: DO NOT USE DEVICE AS A JUNCTION BOX. DO NOT
WIRE THRU DEVICE TO OTHER DEVICES THERMAL MOTOR SWITCH

2 DUCT MOUNTED ELECTRONIC TEMPERATURE SENSOR


5 PNEUMATIC TUBING
WITH RIGID STEM ELEMENT. PROVIDE PER DETAIL 2/ME10.0001/ME10.0001.
DETAIL ME100001 ME100001 DETAIL ME100001 ME100001 TS-#
EXISTING PNEUMATIC TUBING
DEVICE MOUNTING BRACKET DUCT MOUNTED SENSOR PIPE MOUNTED INSERTION TYPE ELECTRONIC
MOTOR STARTER
NO SCALE NO SCALE TEMPERATURE SENSOR WITH WELL.
TS-# ELECTRIC TO PNEUMATIC SOLENOID VALVE MOUNTED IN
NC
C INSTRUMENTATION PANEL, COIL VOLTAGES AS INDICATED
0.25" HARD COPPER TUBING RS-# WALL-MOUNTED ELECTRONIC TEMPERATURE SENSOR EP# NO ON WIRING DIAGRAMS.
PROVIDE WIRE AND CONDUIT
TO FIELD PANEL WALL-MOUNTED HUMIDITY TRANSMITTER. MOUNT ADJACENT TO ROOM
PROVIDE RIGID FIBERGLASS SEAL VAPOR TIGHT WITH HT-# FM-#
TEMPERATURE SENSOR.
INSULATION WITH VAPOR VAPOR BARRIER MASTIC FLOW METER
DP SWITCH
BARRIER, THICKNESS TO (TURBINE-STYLE)
DUCT MOUNTED ELECTRONIC RELATIVE HUMIDITY TRANSMITTER
MATCH ADJACENT INSULATION
FLEXIBLE CONDUIT NO HT-# PROVIDE PER DETAIL 2/ME-1001/ME-1001.
CONNECTION TO DP SWITCH FAN OR PUMP, BY APPLICATION

TEST TEE CHECK


AND PLUG VALVE(E) CURRENT SWITCH
CS DUCT MOUNTED ENTHALPY TRANSMITTER
TEST TEE EN-# PROVIDE PER DETAIL 2/M-701/M-701.
NC
AND PLUG ES-# END SWITCH
AHU CASING/DUCTWORK
0.25" TYPE M BINARY INPUT OR OUTPUT POINT EHO EMERGENCY HVAC OFF (SYSTEM VARIABLE)
PROVIDE 2" STRUT AND MOUNT DP RIGID COPPER TUBE INSULATION
SWITCH MINIMUM 2 FT ABOVE FLOOR.
ANALOG INPUT OR OUTPUT POINT TS-OA OUTSIDE AIR TEMPERATURE SENSOR (SYSTEM VARIABLE)
HOUSEKEEPING SECURE PITOT TUBE MOUNTING FLANGE
PAD(E) STATIC PITOT TUBE NETWORK CONNECTION
TO DUCT WITH TWO #10 SHEET METAL EN-OA OUTSIDE AIR ENTHALPY TRANSMITTER (SYSTEM VARIABLE)
SCREWS AND DUCT SEALANT. T THERMOMETER.
AIR FLOW VFD-# VARIABLE FREQUENCY DRIVE
6 DIRECTION
DETAIL ME100001 ME100001 3 AMS-# AIRFLOW MEASURING STATION - THERMAL DISPERSION TYPE

WATER DIFFERENTIAL DETAIL ME100001 ME100001


PRESSURE SWITCH PITOT TUBE INSTALLATION AIRFLOW MEASURING STATION - PIEZOMETRIC TYPE
NO SCALE NO SCALE AMS-#
FILE NAME: IF1402ME100001.DWG

PLOT DATE: 5/21/2015 9:48:16 AM


OUR REF: 112.09

ALPHA CORPORATION
CONTROLS SYMBOLS, ABBREVIATIONS,
21351 RIDGETOP CIRCLE,
SUITE 200
AND DETAILS
DULLES, VIRGINIA 20166
NOTES GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
30 EXTEND FIBER TO CONNECT TO TRENDNET 100BASE-TX TO 100BASE-FX COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
MULTI MODE SC FIBER CONVERTOR.
G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
31 PROVIDE NETWORK CONNECTION USING CAT-6 CABLES TO CONNECT BTU HWP-1 UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
METER PANEL AND HEAT EXCHANGER CONTROL PANEL TO AHU CONTROL
PANEL ON SECOND FLOOR. R1-2 HWR G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS
OTHERWISE INDICATED.
NC V-1
37 PROVIDE NETWORK CONNECTION USING CAT-6 CABLES FROM SWITCH TO HTWR
EXISTING EMCS CONTROL PANEL. HX-1
NC
HTWS TS-1
39 PROVIDE NETWORK CONNECTION USING CAT-6 CABLES FROM SWITCH TO V-2 AS-1
AHU CONTROL PANEL. HWS CS-1
R1-3
40 DEMOLISH EXISTING MEDIA CONVERTOR. (E)FIBER
X1 X0
120 VAC
39 200

30 OVERLOADS
31

HWS-T-SP
M
BAS
ET-1
AHU (E)EMCS
CONTROL CONTROL
PANEL PANEL HTHW SHUTDOWN R1-1 R-1 120
40
37 0 20 65
RESET
HEATING WATER SUPPLY TEMPERATURE
FLOW DIAGRAM 2 GALLON CHEMICAL
WIRING DIAGRAMS FEED TANK
RESET SCHEDULE
GENERAL
PROVIDE TRENDNET S50G 5-PORT GIGABIT THE HEAT EXCHANGER CONTROLS SHALL BE PROVIDED AND INSTALLED BY SIEMENS BUILDING TECHNOLOGIES, INC., AND SHALL BE INTERFACED WITH THE EXISTING AIRPORT EMCS SYSTEM.
GREENNET SWITCH AND TRENDNET 100BASE-TX TO
100BASE-FX MULTI MODE SC FIBER CONVERTOR SYSTEM ENABLE: ON A CALL FOR HEATING FROM ANY HEATING COIL THE PUMP SHALL START , VALVE V-2 SHALL OPEN, AND VALVE V-1 SHALL MODULATE TO MAINTAIN SETPOINT (INITIALLY 200
HX-1 CONTROL PANEL
NO CALL FOR HEATING FOR 15 MINUTES VALVES V-1 AND V-2 SHALL CLOSE. THE PUMP SHALL CONTINUE TO RUN FOR 15 MINUTES AFTER THE SYSTEM STOPS.
DEMOLISH CONTROL PANEL UPON COMPLETION OF PHASE IV WORK.
31 ON A FAILURE OF THE PUMP, AS INDICATED BY CURRENT SWITCH CS-1, AN ALARM SHALL BE INDICATED. CURRENT SWITCH CS-1 SHALL INDICATE OPERATION.

PROVIDE DUAL CHANNEL


BTU METER PANEL 1. MAXIMUM RATE OF OPENING OF AUTOMATIC TEMPERATURE CONTROL VALVE IN HTHW RETURN PIPE SHALL BE FULL STROKE OF VALVE STEM IN 30 MINUTES (ADJUSTABLE) TO PREVENT THERMAL SHOCK UNDER ALL OPERATING
CONDITIONS.
PROVIDE GE SENSING 2. THE AUTOMATIC TEMPERATURE CONTROL VALVE IN HTHW RETURN PIPE AND THE AUTOMATIC ISOLATION VALVE IN HTHW SUPPLY PIPE SHALL CLOSE UNDER THE FOLLOWING CONDITIONS:
ULTRASONIC BTU METER (DUAL CHANNEL) 2.1. LACK OF OPERATION OF THE SECONDARY HOT WATER PUMP AS SENSED BY THE PUMP STARTER.
2.1.1. LACK OF OPERATION OF THE SECONDARY HOT WATER PUMP AS SENSED BY PUMP DIFFERENTIAL PRESSURE SWITCH SUCH AS, PUMP COUPLING FAILURE.
2.1.2.
TS-4

2.1.3. SECONDARY HOT WATER SUPPLY PRESSURE EXCEEDS 135 PSIG (ADJUSTABLE).
TS-3

2.1.4. DETECTION OF OUT RANGE CONDITION FOR SECONDARY HOT WATER SUPPLY TEMPERATURE TRANSMITTER AND/OR PRESSURE TRANSMITTER.
2.1.5. AFTER VALVES ARE COMMANDED CLOSED, THE SECONDARY HOT WATER PUMP SHALL OPERATE FOR 15 MINUTES (ADJUSTABLE) TO REMOVE RESIDUAL HEAT FROM THE HEAT EXCHANGER BEFORE THEY ARE
SHUT-DOWN.
TS-2

SOFTWARE ALARMS: THE FOLLOWING SOFTWARE ALARMS SHALL BE PROGRAMMED INTO THE EMCS SYSTEM AS A MINIMUM:
TS-1

1. HIGH SECONDARY HOT WATER SUPPLY TEMPERATURE IMMEDIATELY LEAVING THE HEAT EXCHANGER AS SERVED BY A REMOTE BULB THERMOSTAT (BINARY INPUT).
2. HIGH SECONDARY HOT WATER SUPPLY TEMPERATURE IMMEDIATELY LEAVING THE HEAT EXCHANGER (ANALOG).
3. HIGH SECONDARY HOT WATER SUPPLY PRESSURE IMMEDIATELY AFTER THE HEAT EXCHANGER (ANALOG).
4. SECONDARY HOT WATER PUMP ON-OFF STATUS FROM PUMP STARTER AUXILIARY CONTACTS (BINARY INPUT).
5. LOW PRESSURE DIFFERENTIAL PRESSURE ACROSS SECONDARY HOT WATER PUMP (BINARY INPUT).
6. EXPANSION TANK HIGH PRESSURE (ANALOG).
7. EXPANSION TANK LOW PRESSURE (ANALOG).
HTWS

HTWR

8. OUT OF RANGE CONDITION FOR SECONDARY HOT WATER SUPPLY TEMPERATURE TRANSMITTER.
CWS

CWR

9. OUT OF RANGE CONDITION FOR THE SECONDARY HOT WATER SUPPLY PRESSURE TRANSMITTER.

HARDWIRED SAFETIES: THE FOLLOWING HARDWIRED SAFETIES SHALL BE PROVIDED AS A MINIMUM. THESE SAFETIES SHALL NOT BE OVERRIDDEN BY HAND-OFF-AUTOMATIC (HOA) SWITCHES FOR THE SECONDARY HOT WATER PUMPS IN
ANY SWITCH POSITION. VALVES V-1 AND V-2 SHALL CLOSE UNDER THE FOLLOWING CONDITIONS:
4 SETS OF 3 CONDUCTOR CABLES
1. EMCS PANEL FAILURE.
2. LOSS OF POWER TO CONTROL SYSTEM.
3. LACK OF CLOSURE OF AUXILIARY CONTACTS AT MOTOR STARTER ON HWP-1.
4. HIGH SECONDARY HOT WATER SUPPLY TEMPERATURE IMMEDIATELY LEAVING THE HEAT EXCHANGER. PROVIDE MANUAL RESET.
5. LOW DIFFERENTIAL PRESSURE AT HWP-1.
6. CLOSURE OF VALVES BY HARDWIRED SAFETIES SHALL HAVE NO EFFECT ON SECONDARY HOT WATER PUMP OPERATION.
COORDINATE WORK WITH AIRPORT COMMUNICATIONS SYSTEMS (ACS), 703-417-8300
ACS TO PROVIDE FIBER TO MEDIA CONVERTOR.
CONTROLS CONTRACTOR TO PROVIDE ALL CONTROL WIRING AND EQUIPMENT DOWNSTREAM OF FIBER DROP.

SEQUENCE OF OPERATIONS
CONTROL SYSTEMS DIAGRAM HEATING WATER PLANT
FILE NAME: IF1402ME100002.DWG

PLOT DATE: 5/21/2015 9:49:22 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
HEAT EXCHANGER CONTROLS
SUITE 200
DULLES, VIRGINIA 20166
GENERAL
OCCUPIED/UNOCCUPIED CYCLE: THE OCCUPIED OR UNOCCUPIED CYCLE SHALL BE SELECTED BY THE DDC CONTROLLER TIME CLOCK
AND OPTIMUM START FUNCTIONS.
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
SUPPLY FAN: THE AHU SUPPLY FAN SHALL BE STARTED AND STOPPED THROUGH THE BAS. THE VFD SHALL INDICATE OPERATION. MAX MAX COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

SUPPLY AIR TEMPERATURE


(DO TO VALVE POSITION)
DAMPERS: RELAY R1 SHALL PROVIDE A HARDWIRE INTERLOCK BETWEEN THE SUPPLY FAN AND THE OUTSIDE AIR DAMPERS. WHEN THE VAV BOX G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
FAN RUNS THE DDC CONTROLLER SHALL MODULATE THE DAMPER. WHEN THE FAN STOPS, DAMPERS SHALL RETURN TO THEIR NORMAL AIRFLOW UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
POSITIONS. SENSOR

AIR FLOW
SEE SCHEDULE
50% FOR MINIMUM D-1 H
OFF/UNOCCUPIED CYCLE: THE FANS SHALL BE STOPPED AND ALL VALVES AND DAMPERS SHALL RETURN TO THEIR NORMAL POSITIONS.
VALVE V-1 SHALL MAINTAIN 45
VOLUME NOTES
C TS-SA 1 CONTROLS CONTRACTOR MUST COORDINATE WITH TAB CONTRACTOR IN
MIN
ORDER TO DETERMINE THE BALANCED PRESSURE SETPOINT FOR DPT-1.
SHUTOFF BOX ZONE TEMPERATURE, THE SUPPLY FAN SHALL START. THE OUTSIDE AIR DAMPER SHALL REMAIN CLOSED AND THE COILS BALANCED PRESSURE IS DEFINED AS THE PRESSURE READING AT THE
SHALL BE CLOSED. ON A RISE IN TEMPERATURE TO 65 AHU LVG DPT WITH THE UNIT AT DESIGN CONDITIONS.
(-1.5 -1 -0.5 SP +0.5 +1 +1.5) -1.5 -1 -0.5 SP VAV BOX V-1 N.C.
PREOCCUPANCY CYCLE: THE DDC CONTROLLER SHALL START THE SUPPLY FAN THRU THE OPTIMUM START FUNCTION. THE OUTSIDE AIR CONTROLLER
AND RELIEF DAMPERS SHALL REMAIN CLOSED. COIL DISCHARGE TEMPERATURE CONTROL SHALL BE ENABLED. IF THE AVERAGE VAV
BOX SPACE TEMPERATURE IS BELOW SETPOINT, PID CONTROL SHALL RESET THE DISCHARGE TEMPERATURE. AIR FLOW SCHEDULE HEATING VALVE SCHEDULE
GENERAL
OCCUPIED CYCLE: MIN OA DAMPER D-1A AND RETURN DAMPER D-2 SHALL MODULATE TO MAINTAIN THE SCHEDULED MINIMUM REQUIRED MULTI-DROP
OCCUPIED, PREOCCUPANCY, AND NIGHT SETBACK: THE DAMPER AND VALVE SHALL MODULATE IN ACCORDANCE WITH
OUTSIDE AIR, AS SENSED BY AMS-1. FLOOR TS-RM
THE SCHEDULES.
NETWORK
SUPPLY FAN CAPACITY CONTROL: ON A FALL IN SUPPLY DUCT PRESSURE, AS SENSED BY DPT-1, THE VFD SHALL SPEED UP THE FAN TO FLOW DIAGRAM
UNOCCUPIED: THE HEATING COIL VALVE, V-1, SHALL BE CLOSED AND THE DAMPER SHALL BE AT MINIMUM POSITION.
MAINTAIN SETPOINT, INITIALLY SET AT 0.75"W.G. ON A RISE IN DUCT PRESSURE THE REVERSE SHALL OCCUR.

DIFFERENTIAL PRESSURE RESET: DIFFERENTIAL PRESSURE TRANSMITTER DPT-1 SHALL BE RESET UNTIL THE MOST DEMANDING VAV THE ROOM SETPOINT (SP).
BOX IS NEARLY WIDE OPEN, IN ACCORDANCE WITH ASHRAE 90.1.
VENTILATION OPTIMIZATION: CONTROLLER SHALL CALCULATE THE OUTSIDE AIR FRACTION (Zpz), AND CURRENT
SUPPLY AIR TEMPERATURE RESET: WHEN THE SUPPLY FAN HAS REACHED ITS MINIMUM SPEED SETTING, THE DISCHARGE AIR PRIMARY AIR FLOW (Vpz) EVERY 10 MINUTES AND REPORT TO AHU CONTROLLER PER ASHRAE 90.1. Zpz = Voz / Vpz. SEE
TEMPERATURE SHALL BE RESET HIGHER (NOT TO EXCEED 62 VAV BOX SCHEDULE FOR Voz.
ACCORDANCE WITH ASHRAE 90.1. WHEN THE SUPPLY FAN HAS REACHED ITS MAXIMUM SPEED SETTING, THE REVERSE SHALL OCCUR.
THE GRAPHICAL USER INTERFACE ON THE OWS SHALL INDICATE THE CRITICAL ZONE. VAV BOX WITH HEAT
SPACE PRESSURIZATION: ON A RISE IN SPACE PRESSURE, AS SENSED BY DPT-3 DAMPER D-3 SHALL MODULATE OPEN AND DAMPER D-1B
SHALL MODULATE CLOSED TO MAINTAIN SETPOINT, INITIALLY SET AT 0.05"W.G. ON A FALL IN PRESSURE THE REVERSE SHALL OCCUR. D-3
N.C.
DISCHARGE TEMPERATURE: THE DISCHARGE TEMPERATURE SETPOINT SHALL BE 55 RELIEF
INSIDE
TS-3 SD-2
TEMPERATURE CONTROL: ON A FALL IN DISCHARGE TEMPERATURE, AS SENSED BY TS-2, COOLING COIL VALVE V-2 SHALL MODULATE R2-1
CLOSED TO MAINTAIN SETPOINT. ON A FURTHER FALL IN TEMPERATURE, HEATING COIL VALVE V-1 SHALL MODULATE OPEN TO MAINTAIN R1
DPT-3 TS-OA
SETPOINT. ON A RISE IN TEMPERATURE THE REVERSE SHALL OCCUR.
120V CTL POWER NETWORK
LOCATE ON NORTH CONNECTION
OUTSIDE FACE OF BUILDING.
D-2 SHALL CLOSE. ON A FALL IN MIXED AIR TEMPERATURE BELOW THE DISCHARGE TEMPERATURE SETPOINT, AS SENSED BY TS-1, FOR:
SEE ME030001 FOR LOCATION. START/STOP,
DAMPER D-1B SHALL MODULATE CLOSED AND DAMPER D-2 SHALL MODULATE OPEN TO MAINTAIN SETPOINT AT TEMPERATURE SENSOR D-2
TS-2. ON A RISE IN TEMPERATURE THE REVERSE SHALL OCCUR. LOCATE ON SECOND FLOOR. SPEED
N.O. AUX CONTACT
SEE ME030002 FOR LOCATION. REFERENCE,
RETURN
HEATING WATER CIRCULATING PUMP: ON A COMMAND TO OPEN THE HEATING VALVE, PUMP HWCP-1 SHALL START. ON A COMMAND TO MOTOR
DPT-2 EXTERNAL SAFETY
CLOSE THE HEATING VALVE THE PUMP SHALL STOP. CURRENT SWITCH CS-1 SHALL INDICATE OPERATION. EHO OPERATION,
INTERLOCK SPEED INPUT,
D-1B G
FZ-1 DP-1 SD-1 kW
FILTERS: ON A RISE IN FILTER DIFFERENTIAL PRESSURE ABOVE SETPOINT, AS SENSED BY DPT-2, AN ALARM SHALL BE INDICATED. INITIAL N.C.
SETPOINT DPT-2: 1.75" W.G. MAX OA FZ-1 TS-2 SD-1
SUPPLY

PREFILTER
MAX OA R1-1B TS-1 TS-4

PREHEAT

COOLING
FILTER
MONITOR POINTS: POINTS NOT SPECIFICALLY USED IN THIS SEQUENCE FOR CONTROL SHALL BE INDICATED AT THE OWS. SUPPLY FAN VFD WIRING DIAGRAM
EMERGENCY HVAC OFF: ON ACTIVATION OF THE EMERGENCY HVAC OFF SWITCH (EHO), THE SYSTEM SHALL BE OFF. DPT-1
1
UNIT SAFETIES AMS-2 L1 N
MIN OA
WHEN THE SUPPLY FAN FAILS ON THE EXTERNAL SAFETY INTERLOCK THE BAS SHALL INDEX THE SYSTEM TO THE OFF CYCLE. AMS-1 V-1 120 VAC
D-1A VFD-1
R1-1A C N.C.
FREEZESTAT FZ-1, SET AT 38 N.C. HWR
MIN OA N.O.
SMOKE DETECTOR SD-1 SHALL STOP THE UNIT FANS AND RETURN ALL VALVES AND DAMPERS TO THEIR NORMAL POSITIONS. REMOTE
ANNUNCIATION TO THE BUILDING FIRE ALARM SYSTEM SHALL OCCUR PER NFPA 90A. INDUCTIVE
HWS RATED
RESET: ALL PROTECTION CONTROLS SHALL REQUIRE LOCAL MANUAL RESET BEFORE THE UNIT FANS CAN BE RESTARTED AFTER THE RELAY
DEVICES TRIP.
HWCP-1 V-2 HWCP-1 WIRING DIAGRAM
N.C.
CS-1
SEQUENCE OF OPERATION

FLOW DIAGRAM

AHU-1 CONTROLS
FILE NAME: IF1402ME100003.DWG

PLOT DATE: 5/21/2015 9:49:44 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
AHU CONTROLS
SUITE 200
DULLES, VIRGINIA 20166
D-1
L1 N N.C.
H
FAN 120 VAC GENERAL NOTES
N L EF-X
MOTOR RATED G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
120V RELAY COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
C
BAS G2 ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
FAN UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
D-1
CS-1
RT-1A
V-1 RT-1
N.O. X1 X2
RT-1B C D-1
N.C.
WIRING DIAGRAM N.C.
V-1 FLOW DIAGRAM 120VAC EF-X
WIRING DIAGRAM GENERAL H OVERLOADS
FLOW DIAGRAM EF-3 SERVES THE LOCKER ROOM AND EF-4 SERVES THE TOILET ROOMS. THESE FANS ARE O
GENERAL SCHEDULED TO OPERATE DURING OCCUPIED HOURS. A
RT-1
(ADJUSTABLE), THE FAN SHALL START THROUGH LINE VOLTAGE THERMOSTAT RT-1. ON OCCUPIED/UNOCCUPIED CYCLE: THE OCCUPIED OR UNOCCUPIED CYCLE SHALL BE SELECTED BY D-1
A RISE IN TEMPERATURE, THE REVERSE SHALL OCCUR. THE DDC CONTROLLER TIME CLOCK FUNCTION.
R-1 RT-1
UNOCCUPIED CYCLE: THE FAN SHALL STOP AND DAMPER D-1 SHALL CLOSE.
EF-1 & EF-2 WIRING DIAGRAM SF-1 & SF-3 FLOW DIAGRAM
VALVE SHALL CLOSE. OCCUPIED CYCLE: THE FAN SHALL START AND DAMPER D-1 SHALL OPEN.

UNIT HEATERS (UH) FAN OPERATION: THE EXHAUST FAN SHALL BE STARTED AND STOPPED THROUGH THE BAS.
CONTROL SWITCH CS-1 SHALL INDICATE OPERATION.
D-1
X1 X2 N.C.
SF-X
EMERGENCY HVAC OFF: ON ACTIVATION OF THE EMERGENCY HVAC OFF SWITCH (EHO), THE FAN 120VAC
SHALL STOP AND THE DAMPER SHALL RETURN TO ITS NORMAL POSITION.
H OVERLOADS
EF-3 & EF-4 O
A
R-1A
L1 N D-1
D-1
120 VAC N.C.

EF-X
SF-1 & SF-3 WIRING DIAGRAM SF-1 & SF-3 FLOW DIAGRAM

RT-1 D-1
X1 X2 N.C.
D-1 SF-X
120VAC
H OVERLOADS
RT-1 O
WIRING DIAGRAM A
R-1B
FLOW DIAGRAM D-1
GENERAL
EF-5 SERVES THE FIRST FLOOR SHOP ROOM.
SF-2 & SF-4 WIRING DIAGRAM SF-2 & SF-4 DIAGRAM
SHALL START THROUGH LINE VOLTAGE THERMOSTAT RT-1 AND DAMPER D-1 SHALL OPEN. ON A
FALL IN TEMPERATURE, THE REVERSE SHALL OCCUR.
GENERAL
EMERGENCY HVAC OFF: ON ACTIVATION OF THE EMERGENCY HVAC OFF SWITCH (EHO), THE FAN EF-1, SF-1, AND SF-2 ARE A FAN SYSTEM THAT SERVES THE NORTH BAY. EF-2, SF-3, AND SF-4 ARE
SHALL STOP AND THE DAMPER SHALL RETURN TO ITS NORMAL POSITION. FAN SYSTEM THAT SERVES THE SOUTH BAY.

EF-5 THE FAN SHALL START THROUGH LINE VOLTAGE THERMOSTAT RT-1 AND DAMPER D-1 SHALL
OPEN. ON A FALL IN TEMPERATURE, THE REVERSE SHALL OCCUR.
SEQUENCE OF OPERATIONS
SUPPLY FAN OPERATION: SF-1 AND SF-2 SHALL START AND ASSOCIATED DAMPERS D-1 SHALL
OPEN THROUGH A HARDWIRE INTERLOCK WITH EF-1. SF-3 AND SF-4 SHALL START AND
1. EMERGENCY POWER OFF - WHEN THE BUILDING EMERGENCY POWER OFF (EHO) SWITCH IS
ASSOCIATED DAMPERS D-1 SHALL OPEN THROUGH A HARDWIRE INTERLOCK WITH EF-2.
DEPRESSED ALL OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL CLOSE AND ALL HVAC FANS (SUPPLY,
RETURN, AND EXHAUST) SHALL BE DISABLED AND SHALL NOT RUN. THE PHYSICAL EPO SWITCH SHALL
EMERGENCY HVAC OFF: ON ACTIVATION OF THE EMERGENCY HVAC OFF SWITCH (EHO), THE FAN
BE HOUSED IN A GLASS BREAK ENCLOSURE AND SHALL BE LOCATED IN THE VICINITY OF THE FIRE
SHALL STOP AND THE DAMPER SHALL RETURN TO ITS NORMAL POSITION.
ALARM ANNUNCIATOR PANEL. THE EXACT LOCATION OF THE SWITCH SHALL BE COORDINATED WITH
THE FURNITURE LAYOUT AND SHALL BE APPROVED BY THE CONTRACTING OFFICER'S
REPRESENTATIVE. THE EPO SWITCH ENCLOSURE SHALL BE PERMANENTLY LABELED "EMERGENCY
HEATING, VENTILATION, AND AIR CONDITIONING POWER OFF SWITCH". PROVIDE PASSWORD
PROTECTED GRAPHICAL SOFTWARE SWITCH ON MAIN PAGE AT OWS.
EF-1, EF-2, SF-1, SF-2, SF-3, & SF-4
2. EPO RESET - WHEN THE BUILDING EPO RESET SWITCH IS DEPRESSED ALL BUILDING HVAC SYSTEMS
SHALL RETURN TO THE NORMAL MODE OF OPERATION. THE EPO RESET SWITCH SHALL BE HOUSED IN
A LOCKABLE ENCLOSURE AND SHALL BE LOCATED ADJACENT TO THE EPO SWITCH IN THE VICINITY OF
THE FIRE ALARM ANNUNCIATOR PANEL. THE EXACT LOCATION OF THE SWITCH SHALL BE
COORDINATED WITH THE FURNITURE LAYOUT AND SHALL BE APPROVED BY THE CONTRACTING
OFFICER'S REPRESENTATIVE. THE EPO SWITCH ENCLOSURE SHALL BE PERMANENTLY LABELED
"EMERGENCY HEATING, VENTILATION, AND AIR CONDITIONING POWER OFF RESET SWITCH". PROVIDE
PASSWORD PROTECTED GRAPHICAL SOFTWARE SWITCH ON MAIN PAGE AT OWS.

HVAC EMERGENCY POWER OFF (EPO)


FILE NAME: IF1402ME100004.DWG

PLOT DATE: 5/21/2015 9:50:47 AM


OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
HVAC CONTROLS
SUITE 200
DULLES, VIRGINIA 20166
SYMBOLS
LIGHTING FIXTURE TYPE. SYMBOLS GENERAL NOTES
DETAIL NUMBER: G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
2'x4' FLUORESCENT LIGHTING FIXTURE, TYPE AS NOTED. COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
1'x4' RECESS FLUORESCENT LIGHTING FIXTURE, TYPE AS NOTED. - NUMBER INDICATES DETAIL.
G2 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
2'x2' FLUORESCENT LIGHTING FIXTURE, TYPE AS NOTED. COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
- SHEET NUMBER WHERE DETAIL IS REFERENCED.
1'x4' STRIP FLUORESCENT LIGHTING FIXTURE, TYPE AS NOTED.
- SHEET NUMBER WHERE DETAIL IS DRAWN.
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,
NEMA 5-20R CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x ELEVATION DETAIL, ALL OTHER CHARACTERISTICS SAME AS
1-1/2" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE ABOVE.
FINISHED FLOOR.

J JUNCTION BOX, 4" SQUARE x 1-1/2" DEEP GALVANIZED PRESSED


STEEL, RECESS MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH ABBREVIATIONS
BLANK COVER PLATE.
A AMPERES.
PUMP CONTROLLER
AF FRAME SIZE IN AMPERES.
LIGHTING CONTACTOR AT TRIP SIZE IN AMPERES.
AWG AMERICAN WIRE GAUGE.
BLDG. BUILDING.
MOTOR, SEE MOTOR AND EQUIPMENT SCHEDULE FOR C/B CIRCUIT BREAKER.
SIZES AND CHARACTERISTICS. EQUIPMENT IDENTIFICATION NUMBER.
CBM CERTIFIED BALLAST MANUFACTURERS.
EC EMPTY CONDUIT.
FIRE ALARM ADDRESSABLE CONTROL MODULE DRAWING REVISION NUMBER. FA FIRE ALARM.
FAAP FIRE ALARM ANNUNCIATOR PANEL.
CENTER LINE. FACP FIRE ALARM CONTROL PANEL.
DUCT SMOKE DETECTOR FLA FULL LOAD AMPERES.
CONDUIT UP. FVNR FULL VOLTAGE NON-REVERSING.
COMBINATION SAFETY SWITCH AND MAGNETIC MOTOR STARTER, GFI GROUND FAULT INTERRUPTER.
SEE MOTOR AND EQUIPMENT SCHEDULE FOR SIZES AND CONDUIT DOWN. GRD. GROUND CONDUCTOR.
CHARACTERISTICS. HH HAND HOLE
FCP-SHOPS 3 DELTA CONFIGURATION. HOA HAND-OFF-AUTOMATIC SELECTOR SWITCH.
KAIC THOUSAND AMPERE INTERRUPTING CAPACITY.
WYE GROUNDING CONFIGURATION. KW KILO-WATTS.
MH MANHOLE
M.L.O. MAIN LUGS ONLY.
N.C. NORMALLY CLOSED.
MECHANICAL EQUIPMENT OUTLINE. N.E.C. NATIONAL ELECTRICAL CODE.
NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION.
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN EXPOSED. NFSS NON-FUSED SAFETY SWITCH.
SIZE IN ACCORDANCE WITH N.E.C. RACEWAY SHALL BE N.O. NORMALLY OPEN.
MINIMUM 3/4" CONDUIT, AND WIRE SHALL BE MINIMUM SIZE P NUMBER OF POLES.
RISER DIAGRAM #12 AWG COPPER WITH THHN INSULATION, UNLESS OTHER PH. NUMBER OF PHASES.
SIZES ARE SPECIFICALLY NOTED. RGS RIGID GALVANIZED STEEL.
U.L. UNDERWRITER'S LABORATORIES.
HOME RUN TO PANEL. NUMBER OF ARROWS INDICATE V VOLTAGE.
ACTION TAKEN THE NUMBER OF CIRCUITS. WP WEATHERPROOF, OR NEMA 3R ENCLOSURE.

ACTIVATE ALARM DISPLAY AND LOCAL


NUMBER OF SLASH MARKS INDICATE THE NUMBER OF
CONDUCTORS IN RACEWAY. NO SLASH MARKS INDICATE
2 CIRCUIT CONDUCTORS PLUS A GROUND CONDUCTOR.

AUDIBLE ALARM AT THE FCP

SEND FAN STATUS TO EMCS


GREEN GROUND CONDUCTOR RUN IN RACEWAY.

EM2 PANEL NAME TO WHICH CIRCUITS RUN.

SHUT DOWN AHU 1,3,5 CIRCUIT BREAKERS IN PANEL SERVING THESE CIRCUITS.

#10 WIRE SIZE IN AWG. SIZE NOT SHOWN INDICATES #12 AWG.
#10
BRANCH CIRCUIT CONDUIT AND CONDUCTORS RUN CONCEALED
DUCT SMOKE DETECTORS X X X EM2 IN CONCRETE, ALL OTHER CHARACTERISTICS SAME AS SHOWN
1,3,5

SEQUENCE OF OPERATIONS MATRIX EXISTING CONDUIT AND CONDUCTORS TO REMAIN.

CIRCUIT BREAKER TYPE PANELBOARD.

ELECTRICAL POINT OF CONNECTION.

S LIGHT SWITCH, FLUSH TUMBLER TYPE, SINGLE POLE,


20 AMPERE, 120/277V, A.C. ONLY, RECESS MOUNTED AT
48" ABOVE FINISHED FLOOR.
PLOT DATE: 5/21/2015 10:01:39 AM
FILE NAME: IF1402EL000001.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SYMBOLS AND ABBREVIATIONS
SUITE 200
DULLES, VIRGINIA 20166
NOTES GENERAL NOTES
3 DISCONNECT AND REMOVE TELEPHONE. TAG, PROTECT, AND RETAIN G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
TELEPHONE AND COMMUNICATION CABLING FOR REUSE. COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

4 DISCONNECT UNIT HEATER RETAIN BRANCH CIRCUIT FOR REUSE. G2


CONDUCTORS SHALL INCLUDE REMOVAL OF CONDUIT, SUPPORT
SYSTEMS, AND JUNCTION BOXES SURFACE MOUNTED OR ABOVE

BE REMOVED BACK TO SOURCE, UNLESS OTHERWISE NOTED.

G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS


OTHERWISE INDICATED.

NOTES
1 DISCONNECT EQUIPMENT. REMOVE CONDUIT AND CONDUCTORS
BACK TO SERVING PANEL.

2 DISCONNECT AND REMOVE LIGHT FIXTURE. RETAIN CONDUIT AND


CONDUCTORS FOR REUSE.

D4 D3 D2 1 A.C. UNIT 1
2 3 4 5 6 7

1 A.C. UNIT

3 TELEPHONE 2 PHASE II

PHASE II

A.C. UNIT 1

UH 4

GRAPHIC SCALE
FIRST FLOOR PLAN - DEMOLITION N 1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALES MUST BE USED.
PLOT DATE: 5/21/2015 10:01:50 AM
FILE NAME: IF1402EL020001.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
FIRST FLOOR PLAN -
21351 RIDGETOP CIRCLE,
SUITE 200
ELECTRICAL DEMOLITION
DULLES, VIRGINIA 20166
NOTES
3 DISCONNECT AND REMOVE LIGHT FIXTURE. REMOVE CONDUIT AND
GENERAL NOTES
CONDUCTORS BACK TO SERVING PANEL. G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
4 DISCONNECT MAGNETIC DOOR LOCK AND RETAIN DOOR LOCK AND
CONDUCTORS FOR REUSE. G2
CONDUCTORS SHALL INCLUDE REMOVAL OF CONDUIT, SUPPORT
5 DISCONNECT UNIT HEATER RETAIN BRANCH CIRCUIT FOR REUSE. SYSTEMS, AND JUNCTION BOXES SURFACE MOUNTED OR ABOVE

BE REMOVED BACK TO SOURCE, UNLESS OTHERWISE NOTED.

G3 ALL WORK IS TO BE PROVIDED UNDER PHASE I UNLESS


OTHERWISE INDICATED.

NOTES
1 DISCONNECT MOTOR. REMOVE MOTOR CONTROLLER, SAFETY
SWITCH AND ALL ASSOCIATED CONDUIT AND CONDUCTORS BACK TO
SERVING PANEL.

2 DISCONNECT CEILING FAN. REMOVE CONDUIT AND CONDUCTORS


BACK TO SERVING PANEL.

D4 D3 D2 1 2 3 4 5 6 7

HVC-2 (E)1"CONDUIT
STARTER
D
1 FAN HVC-2 1

3 3 3

3
(E) SHELVING UNIT 3 3
3 2 3

3 PHASE I
3 3
2
CEILING FAN 2
3 UH 5
C 1 3 2
(E)4"ST
2
3 3
HV-1 (E)JB
(E)1"CONDUIT UH, PHASE IV 5
UH UH 5 UH, PHASE IV 5
5 (E)3"CONDUIT 5 UH, PHASE IV
(E)1"CONDUIT
5 UH 3
3 3 3 (E)2"CONDUIT
(E)CONDUIT
3 2
(E)CONDUIT
2
3 (E)DOOR RELEASE BUTTON
PHASE I 2
FAN 1 3 3
B UH 5

2
(E)2"CONDUIT 2
3
3 FAN
PV-1 1 (E)JB
3 AHU 1
3 3
(E)JB
PHASE III

GRAPHIC SCALE
SECOND FLOOR PLAN - DEMOLITION N
1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALES MUST BE USED.
PLOT DATE: 5/21/2015 10:05:14 AM
FILE NAME: IF1402EL020002.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
SECOND FLOOR PLAN - ELECTRICAL
21351 RIDGETOP CIRCLE,
SUITE 200
DEMOLITION
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

G2
CONDUCTORS SHALL INCLUDE REMOVAL OF CONDUIT, SUPPORT
SYSTEMS, AND JUNCTION BOXES SURFACE MOUNTED OR ABOVE

BE REMOVED BACK TO SOURCE, UNLESS OTHERWISE NOTED.

NOTES
1 DISCONNECT MOTOR. REMOVE MOTOR CONTROLLER AND CONDUIT
AND CONDUCTORS BACK TO SERVING PANEL.

(E)ROOF ACCESS
HATCH

(E)4"R.D.

(E)ANTENNA

(E)FAN (E)FAN

(E)FAN (E)FAN (E)FAN (E)FAN (E)FAN

CONDENSING UNIT, PHASE III 1

GRAPHIC SCALE
ROOF PLAN - DEMOLITION N 1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALES MUST BE USED.
PLOT DATE: 5/21/2015 10:02:11 AM
FILE NAME: IF1402EL020003.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
ROOF PLAN -
21351 RIDGETOP CIRCLE,
SUITE 200
ELECTRICAL DEMOLITION
DULLES, VIRGINIA 20166
GENERAL NOTES
1 2 3 G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
1 2 3 COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

(E) SHELVING UNIT G2 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

NOTES
2 B 1 CONNECT LIGHT SWITCH WITH INTEGRAL OCCUPANCY SENSOR TO
A A A A
LIGHT SWITCH CIRCUIT RETAINED UNDER DEMOLITION. SET
OCCUPANCY SENSOR TO VACANCY MODE AND SET TO TURN OFF
2 B AFTER 15 MINUTES AFTER OCCUPANT HAS LEFT THE SPACE.
A

S
2 CONNECT LIGHT FIXTURE TO CIRCUIT RETAINED UNDER DEMOLITION.
A 2 B
A A
PHASE II
PHASE II 1 S OC
A A

A
A A
A S
T
PHASE I
PHASE I A

A A
AHU-1
A
A

A
S

A A A
A

A A

A
A A HP-1
HP-1
21
26

A A A

FIRST FLOOR PLAN N


SECOND FLOOR PLAN N

GRAPHIC SCALE
1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALES MUST BE USED.
PLOT DATE: 5/21/2015 10:02:24 AM
FILE NAME: IF1402EL030001.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
FIRST AND SECOND FLOOR
21351 RIDGETOP CIRCLE,
SUITE 200
LIGHTING PLAN
DULLES, VIRGINIA 20166
NOTES
PROVIDE SECURITY CAMERA WITH REMOTE MONITOR. LOCATE MONITOR
GENERAL NOTES
3
IN 2ND FLOOR OFFICE. COORDINATE EXACT LOCATION WITH THE G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
AUTHORITY. COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

4 INSTALL ELECTRO MAGNETIC DOOR LOCK RETAINED UNDER DEMOLITION G2 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
ON NEW DOOR. COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

5 PROVIDE DOOR RELEASE BUTTON ADJACENT TO REMOTE CAMERA G3 ALL WORK TO BE PROVIDED UNDER PHASE I UNLESS OTHERWISE
MONITOR. EXTEND EXISTING DOOR RELEASE CIRCUIT TO NEW BUTTON. INDICATED.
CONNECT SO THAT EITHER BUTTON WILL ALLOW DOOR TO OPEN.

6 INSTALL TELEPHONE RETAINED UNDER DEMOLITION ADJACENT TO CARD


READER. MATCH HEIGHT OF PREVIOUS INSTALLATION. PROVIDE
CONDUCTOR TO MATCH EXISTING. INTERCEPT EXISTING AND EXTEND TO
NOTES
NEW LOCATION. 1 SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR AND FEEDER
CHARACTERISTICS.
7 PROVIDE DEDICATED CIRCUIT FOR BTU METER.
2 ROUTE FEEDER TO ROOF MOUNTED FAN. SEE EL04.0002 FOR FAN
8 EXTEND CIRCUIT RETAINED UNDER DEMOLITION TO UNIT HEATER. LOCATIONS.

D4 D3 D2 1 2 3 4 5 6 7

D SF-3 MOTOR CONTROLLER(PHASE IV) 2


(E)
(E)JB

HP-3
2 EF-2 MOTOR
HP-3 37
CONTROLLER (PHASE IV)
26
HP-3 2 SF-4 MOTOR
32 CONTROLLER(PHASE IV)

C
1 EF-3
LP1B
34
S
PHASE II M
PHASE II
7 BTU METER
LP1B
39

HP-3 J
25
HP-3 2 SF-1 MOTOR
20 CONTROLLER (PHASE IV)
2 SF-2 MOTOR
B CONTROLLER (PHASE IV)
HP-3
31 2 EF-1 MOTOR
CONTROLLER (PHASE IV)

UH 8 1

(E)JUNCTION BOX
6 TELEPHONE
LP1B
36
(E)CONDUIT UP&DN.

1 EF-5, PHASE II S
A M

FIRST FLOOR PLAN N


GRAPHIC SCALE
1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALES MUST BE USED.
PLOT DATE: 5/21/2015 10:02:39 AM
FILE NAME: IF1402EL040001.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
FIRST FLOOR PLAN
21351 RIDGETOP CIRCLE,
SUITE 200
POWER
DULLES, VIRGINIA 20166
NOTES GENERAL NOTES
3 PROVIDE SECURITY CAMERA WITH REMOTE MONITOR. LOCATE G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
MONITOR IN 2ND FLOOR OFFICE. COORDINATE EXACT LOCATION COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
WITH THE AUTHORITY.
G2 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
4 INSTALL ELECTRO MAGNETIC DOOR LOCK RETAINED UNDER COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
DEMOLITION ON NEW DOOR.
G3 ALL WORK TO BE PROVIDED UNDER PHASE I UNLESS OTHERWISE
5 PROVIDE DOOR RELEASE BUTTON ADJACENT TO REMOTE CAMERA INDICATED.
MONITOR. EXTEND EXISTING DOOR RELEASE CIRCUIT TO NEW
BUTTON. CONNECT SO THAT EITHER BUTTON WILL ALLOW DOOR TO
OPEN. NOTES
1 SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR AND FEEDER
6 EXTEND CIRCUIT RETAINED UNDER DEMOLITION TO EQUIPMENT. CHARACTERISTICS.
7 PROVIDE DEDICATED CIRCUIT FOR EMCS CONTROL PANEL. 2 ROUTE FEEDER TO ROOF MOUNTED FAN. SEE EL04.0002 FOR FAN
LOCATIONS.
8 RELOCATE JUNCTION BOX AS NECESSARY FOR THE INSTALLATION OF
THE NEW WALL.

D4 D3 D2 1 2 3 4 5 6 7

NETWORK SWITCH 7 EMCS PANEL


1 EF-4

D (E)ROOF ACCESS S
M LP1B
S 40
1 HWP-1 M
LP1B LP1B
33 35

PHASE I
PHASE I
LP1B
CONTROL PANEL 41

1 VFD 3 UH-6 1 6

C HP-3
1 HWCP-1 14
(E)1"CONDUIT S
(E)1"CONDUIT
M
UH-3 1 6 UH-8, PHASE IV 1 6
UH-1 1 6 LP1B (E)3"CONDUIT (E)1"CONDUIT UH-9, PHASE IV 1 6
1 6 UH-4 37 AHU-1 1 (E)1"CONDUIT
(E)2"CONDUIT UH-7, PHASE IV 1 6
1 6 UH-2 (E)CONDUIT
(E)JB
(E)3"CONDUIT
(E)CONDUIT
(E)DOOR RELEASE BUTTON

UH-5, PHASE IV 1 6

(E)2"CONDUIT

(E)PANEL HP3
(E)PANEL HP2 (E)JB
(E) (E)PANEL HP1
(E) T-2 T-1

8 (E)JB (E)T-3
(E)MDP
A
(E)PANEL LP1A
(E)PANEL LP1B
(E)PANEL LP2B
(E)PANEL LP2A
GRAPHIC SCALE
SECOND FLOOR PLAN N 1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALES MUST BE USED.
PLOT DATE: 5/21/2015 10:02:51 AM
FILE NAME: IF1402EL040002.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
SECOND FLOOR PLAN
21351 RIDGETOP CIRCLE,
SUITE 200
POWER
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

NOTES
1 ROUTE CIRCUIT ADJACENT TO DUCTWORK PENETRATION TO MOTOR
CONTROLLER BELOW.

2 MOUNT RECEPTACLE ON ROOF CURB. ROUTE 3/4" LIQUID TIGHT


CONDUIT ADJACENT TO DUCTWORK FROM RECEPTACLE TO
JUNCTION BOX ON FLOOR BELOW. CONNECT ALL JUNCTION BOXES
USING EMT TO CIRCUIT 38 IN PANEL LP1B. SEE MECHANICAL DETAILS
FOR CONDUIT ROUTING.

3 SEE MOTOR AND EQUIPMENT SCHEDULE FOR MOTOR AND FEEDER


CHARACTERISTICS.

D4 D3 D2 1 2 3 4 5 6 7

ROOF ACCESS PHASE IV.


HATCH
D
3 1 SF-3
GFI, WP

LP1B
(E)4"R.D. 38

(E)4"R.D.
(E)4"R.D. (E)4"R.D. (E)4"R.D. (E)4"R.D.

EF-1 1 3

GFI, WP
LP1B
38 GFI, WP 2
LP1B GFI, WP 2
GFI, WP 2 38
3 1 SF-1 LP1B (E)4"R.D.
38
LP1B GFI, WP 2
3 SF-4
38
LP1B 3 1 EF-2
3 1 SF-2 38
B
(E)4"R.D. (E)4"R.D.
(E)4"R.D. (E)4"R.D.

(E)4"R.D.

PHASE IV.
GRAPHIC SCALE
ROOF PLAN N 1/8"=1'-0"
8' 4' 0 8' 16'
CAUTION: IF THIS DRAWING IS A REDUCTION,
GRAPHIC SCALES MUST BE USED.
PLOT DATE: 5/21/2015 10:03:05 AM
FILE NAME: IF1402EL040003.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
ROOF PLAN
21351 RIDGETOP CIRCLE,
SUITE 200
POWER
DULLES, VIRGINIA 20166
GENERAL NOTES
G1 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
(E)PANEL HP-3 SCHEDULE COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.

MOUNTING: SURFACE G2 VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND


200A MAIN CIRCUIT BREAKER LOCATION: SHOPS 1 COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
MOTOR AND EQUIPMENT SCHEDULE BOLT-ON BRANCH CIRCUIT BREAKERS ENCLOSURE: NEMA 1
SWITCH MOTOR STARTER FEEDER NOTES

TYPE

TYPE
kVA LOAD CIRCUIT BREAKER CIRCUIT BREAKER kVA LOAD
DESCRIPTION PER PHASE FRAME/TRIP/KAIC FRAME/TRIP/KAIC PER PHASE DESCRIPTION
EQUIPMENT NAME VOLTAGE PHASE FLA HP FRAME AUX. CONTACTS LOCAL WIRE NOTES 1
POLES TYPE TYPE CONDUIT PROVIDE BREAKER IN EXISTING SPACE.
SIZE N.O. N.C. NO. SIZE GRD. O 14.3 1 2 -- O
AHU 480 11 7.5 30 3 NFSS VARIABLE FREQUENCY DRIVE 3 #12 #12 3/4" 2 (E)RECEPTACLE O 11.2 100/50/25 3 4 100/50/25 -- O (E)RECEPTACLE 2 SEE FLOOR PLANS FOR PHASING OF EQUIPMENT.
SF-1 480 7.6 5 30 3 NFSS FVNR 2 2 HOA 3 #12 #12 3/4" 2 O 12.1 5 6 -- O
FVNR HOA - 7 8 -- -- 3 PROVIDE ADJACENT TO MOTOR RATED TOGGLE SWITCH(MRTS). SEE
SF-2 480 7.6 5 30 3 NFSS 2 2 3 #12 #12 3/4" 2 O
- -- --
MECHANICAL CONTROL DRAWINGS FOR DETAILS
SF-3 480 7.6 5 30 3 NFSS FVNR 2 2 HOA 3 #12 #12 3/4" 2 (E)WELDER O 100/50/25 9 10 100/15/25 SPARE
SF-4 480 7.6 5 30 3 NFSS FVNR 2 2 HOA 3 #12 #12 3/4" 2 O - 11 12 -- --

EF-1 480 11 7.5 30 3 NFSS FVNR 2 2 HOA 3 #12 #12 3/4" 2 O 16.7 13 14 3.0 M
EF-2 480 11 7.5 30 3 NFSS FVNR 2 2 HOA 3 #12 #12 3/4" 2 (E)AIRCOMPRESSOR #2 O 16.7 100/40/25 15 16 10020/25 3.0 M AHU-1 1 2
EF-3 120 5.8 1/4 20 1 NFSS 20A INDUCTIVE RELAY 3 HOA 3 #12 #12 3/4" 2 O 16.7 17 18 3.0 M
EF-4 120 5.8 1/4 20 1 NFSS 20A INDUCTIVE RELAY 3 HOA 3 #12 #12 3/4" 2 O 16.7 19 20 3.0 M
EF-5 120 7.2 1/3 20 1 NFSS 20A INDUCTIVE RELAY 3 HOA 3 #12 #12 3/4" 2 (E)LIFT OIL PUMP O 16.7 100/40/25 21 22 10020/25 3.0 M EF-1 1 2
HWP-1 460 3.0 1.5 20 3 NFSS 20A INDUCTIVE RELAY 3 HOA 3 #12 #12 3/4" 2 O 16.7 23 24 3.0 M
HWCP-1 120 9.8 1/2 20 1 NFSS 20A INDUCTIVE RELAY 3 HOA 3 #12 #12 3/4" 2 M 2.1 25 26 3.0 M
SF-1 1 2 M 2.1 100/20/25 27 28 100/20/25 3.0 M EF-2 1 2
M 2.1 29 30 3.0 M
2 LIGHTING FIXTURE SCHEDULE M 2.1 31 32 2.1 M
SF-2 1 2 M 2.1 100/20/25 33 34 100/20/25 2.1 M SF-4 1 2
MANUFACTURER OR
TYPE APPROVED EQUAL CATALOG NUMBER LAMPS VOLTAGE DESCRIPTION/MOUNTING M 2.1 35 36 2.1 M
A FAILSAFE HVSL12 4 LD3 STD 3500 UNV C ED2C LED 277 PENDANT MOUNTED M 2.1 37 38 .83 M
B CORELITE DRI WS 2 3500 1 UNV 22 T1 LED 277 2X2 RECESSED SF-3 1 2 M 2.1 100/20/25 39 40 100/20/25 .83 M HWP-1 1 2
M 2.1 41 42 .83 M

(E)PANEL HP-1 SCHEDULE (E)PANEL LP1B SCHEDULE


MOUNTING: SURFACE MOUNTING: SURFACE
200A MAIN CIRCUIT BREAKER LOCATION: SHOPS 1 200A MAIN CIRCUIT BREAKER LOCATION: SHOPS 1
BOLT-ON BRANCH CIRCUIT BREAKERS ENCLOSURE: NEMA 1 BOLT-ON BRANCH CIRCUIT BREAKERS ENCLOSURE: NEMA 1

TYPE

TYPE
kVA LOAD kVA LOAD
TYPE

TYPE
kVA LOAD CIRCUIT BREAKER CIRCUIT BREAKER kVA LOAD CIRCUIT BREAKER CIRCUIT BREAKER
DESCRIPTION PER PHASE PER PHASE DESCRIPTION DESCRIPTION PER PHASE FRAME/TRIP/KAIC FRAME/TRIP/KAIC PER PHASE DESCRIPTION
FRAME/TRIP/KAIC FRAME/TRIP/KAIC

O 14.3 1 2 -- O O 14.3 1 2 -- O
225/150/25 3 4 100/20/25 -- (E)LOUNGE UNIT EAST BAY 5 O 11.2 100/100/10 3 4 100/100/10 -- O (E)LOUNGE UNIT WEST BAY 5
(E)TRANSFORMER 1 O 11.2 O (E)PARKING LOT CONTACTOR
O 12.1 5 6 -- O O 12.1 5 6 -- O
- 7 8 100/20/25 -- -- O - 7 8 -- --
O SPARE
- 225/200/25 9 10 100/20/25 -- (E)BOOSTER PUMP TO ATC PANEL O - 100/50/10 9 10 100/50/10 -- -- (E)DOOR OPENER 5&6
(E)LIGHTS ROADWAY WEST O O (E)LIGHTS
- 11 12 100/20/25 -- O - 11 12 -- --
O O (E)LIGHTS MACH SHOP AND LOFT
SPARE O 16.7 100/20/25 13 14 100/20/25 16.7 O (E)LIGHTS MACH SHOP O 16.7 13 14 16.7 O

(E)LIGHTS BATHROOM/DAY ROOM O 16.7 100/20/25 15 16 100/20/25 16.7 O (E)DOORS 5&6 WEST O 16.7 100/20/10 15 16 100/50/10 16.7 O (E)BAY 2 STEAM GINRY
(E)DEVICE O 16.7 100/20/25 17 18 100/20/25 16.7 O O 16.7 17 18 16.7 O

(E)LIGHTS SO. APP BAY 4 SOUTH O - 100/20/25 19 20 100/20/25 16.7 O (E)LIGHTS WASH RACK M 2.1 19 20 16.7 O

1 2 LIGHTING 2ND FLOOR STORAGE O - 100/20/25 21 22 100/20/25 16.7 O (E)LIGHTS NO APP BAY (E)DOORS 1&2 EAST M 2.1 100/20/10 21 22 100/20/10 16.7 O (E) DOORS 5&6 EAST
(E)LIGHTS SO. APP BAY 4 NORTH O - 100/20/25 23 24 100/20/25 16.7 O (E)LIGHTS NO APP BAY M 2.1 23 24 16.7 O
- 100/20/25 25 26 100/20/25 -- M 2.1 25 26 -- -- (E)DEVICE
(E)LIGHTS SO. APP BAY 4 SOUTH O O LIGHTING 2ND FLOOR STORAGE 1 2
- 100/20/25 27 28 100/--/-- -- -- (E)DEVICE M 2.1 100/20/10 27 28 100/20/10 -- -- (E)EXHAUST FAN - BATHROOM
(E)LIGHTS SO. APP BAY 2 SOUTH O SPACE
- 100/20/25 29 30 100/--/-- -- -- M 2.1 29 30 100/--/-- -- -- SPACE
(E)LIGHTS BAY 3 SOUTH O SPACE
(E)LIGHTS OUTSIDE EAST SIDE O - 100/20/25 31 32 100/--/-- -- -- SPACE (E)RECEPT R 2.1 100/20/10 31 32 100/20/10 2.1 M (E)RECEPT
(E)LIGHTS FUEL ISLAND O - 100/20/25 33 34 100/20/25 -- O (E) LIGHTS NO APP BAY S. BAY 5 EF-4 1 2 M 2.1 100/20/10 33 34 100/20/10 2.1 M EF-3 1 2
-- - 100/--/-- 35 36 100/--/-- -- -- SPACE -- - 100/--/-- 35 36 100/20/10 2.1 M EF-5 1 2
SPACE SPACE
SPACE -- - 100/--/-- 37 38 100/--/-- -- -- SPACE HWCP-1 1 2 M 1.2 100/20/10 37 38 100/20/10 1.1 R ROOF RECEPT 1 2
SPACE -- - 100/--/-- 39 40 100/--/-- -- -- SPACE BTU MOTOR 1 2 O 0.6 100/20/10 39 40 100/20/10 0.5 R 1 2
-- - 100/--/-- 41 42 100/--/-- -- -- CONTROL PANEL 1 2 O 0.6 100/20/10 41 42 100/--/-- -- -- SPACE
SPACE SPACE
PLOT DATE: 5/21/2015 10:03:20 AM
FILE NAME: IF1402EL090001.DWG

SJS

CPC SJS
OUR REF: 112.09

ALPHA CORPORATION
21351 RIDGETOP CIRCLE,
SCHEDULES
SUITE 200
DULLES, VIRGINIA 20166