Professional Documents
Culture Documents
Diagnostic Testing Solutions For Power Transformers
Diagnostic Testing Solutions For Power Transformers
Diagnostic Testing Solutions For Power Transformers
Power Transformers
Prevention is Better than Cure - Know More About
manufacturing commissioning
mechanical impacts
>transportation
> event
>post
> fault event
>seismic
> activity event
>etc.
>
100 %
transformer condition
with testing
testing during manufacturing > periodic testing
factory acceptance testing
commissioning acceptance testing > testing after an event - relocation, protection trip
maintain OLTC
>corroded
> contacts
>diverter
> switch
>motor
> & brake
2
the Condition of Your Transformer
operation replacement
aging
>overloading
>
>overheating
>
>moisture
>
protection problems
>protection
> underfunction
>protection
> failure
good condition
actions
3
Transformer Parts and Their Possible Faults
Part
Bushings
Bushing CTs
Insulation materials
Leads
OLTC
Windings
Core
Surge arresters
4
Transformer Dielectric response Frequency response Partial discharge Current transformer
diagnostic set: analysis instrument: analysis instrument: analysis system: testing instrument:
see pages 6-21 see pages 22-23 see pages 24-25 see pages 26-29 see CT Analyzer brochure
dissipation factor
Exciting current
measurement
Tip up test
Faults detectable Measurement
Partial breakdown between capacitive graded layers,
cracks in resin-bonded insulation x x x x
Aging and moisture x x x
Open or compromised measuring tap connection x x
Partial discharges in insulation x x
Loss of oil in an oil-filled bushing x
Current ratio or phase error considering burden, excessive residual
magnetism, non-compliance to relevant IEEE or IEC standard x
Moisture in solid insulation x1 x1 x
Aging, moisture, contamination of insulation fluids x x x
Partial discharges x x
Contact problems x x
Mechanical deformation x
Contact problems in tap selector and at diverter switch x x x x
Open circuit, shorted turns, or high resistance connections in the OLTC
preventative autotransformer, series autotransformer or series transformer x x x
Contact problems in the DETC x x x
Short circuits between windings or between turns x x x x
Strand-to-strand short-circuits x x
Open circuits in parallel strands x x x
Short circuit to ground x x x
Mechanical deformation x x x x
Contact problems, open circuits x x
Mechanical deformation x2 x2 x
Floating core ground x x x
Shorted core laminates x x
Deterioration and aging x
Notes:
1) Power factor / dissipation factor measurements at 50 Hz or 60 Hz can detect high moisture contents, but have a blind spot for low moisture contents. Measuring power factor / dissipation factor at
5
lower frequencies, such as 15 Hz, improves sensitivity. The most sensitive method to determine moisture in solid insulation is dielectric response analysis.
2) If the core ground can be opened.
All in One: the Multi-Functional Transformer Test
winding resistance
I
RHV RLV
V
TR
TR
winding strands
I
TR
6
Set CPC 100 / CP TD1
NP/NS
VP VS
TR
core
I f
TR
I
IR IC
V
Insulation
7
Measuring Capacitance & Power Factor / Dissipation
Surge arresters Bushings OLTC Leads Insulation materials Windings Core Damaged TR after
Capacitance values of bushings show if there Typical loss shapes in 15 - 400 Hz range Capacitive layers
have been breakdowns between capacitive
layers. For resin bonded paper bushings, cracks
into which oil has leaked, can also change the polarization losses conductive losses
value of the capacitance.
8
Factor
High voltage is applied to the insulation to If values deviate more than indicated by the
be tested, i.e. the bushing tip, and a low loss standards, then dielectric response analysis
reference capacitor (integrated in CP TD1) is can be performed to check for increased
connected in parallel. The currents flowing through moisture.
the insulation and through the reference capacitor
are measured and the time difference between Chemical tests can be performed to verify
their zero crossings is determined. The loss angle d the quality of the insulation fluid (DGA,
is then calculated from this time difference. The dielectric breakdown strength, interfacial
tangent of this angle is the dissipation factor. The tension, etc.) Measuring the power factor /
cosine of the angle between voltage and current is dissipation factor of the insulation fluid can
the power factor. Results are compared with values also be done with a CPC 100 accessory, the
given in IEEE C57.10.01 and IEC 60137, and can CP TC12 oil test cell.
be compared with a base measurement, another
phase, or a sister transformer.
impregnated
Insulation
bonded
paper
paper
paper
Resin
Resin
Oil
CA
Typical new
0.3 - 0.4 0.2 - 0.4 0.5 - 0.6
values
*) at 50 / 60 Hz and 20 °C
9
Measuring Capacitance & Power Factor / Dissipation
Power factor / dissipation factor (PF / DF) Energize HV to measure CH + CHL | CH | CHL, then energize LV to measure
measurement indicates the condition of the
liquid and solid insulation within a transformer.
Modular equipment LV
The modular equipment (CPC 100: 29 kg /
65 lbs, CP TD1: 26 kg / 56 lbs) can be easily IN A
transported thanks to its sturdy cases, which
can also be used to place the instruments onto
them for working at a comfortable height, as
shown on page 12.
CL
For convenient transport or mobile use such as
in test fields or in substations/power plants, the
instruments can be mounted onto a trolley.
10
Factor
Your Benefits
>> perfect digitally generated sine wave
test signal that is independent from
power quality and line frequency
11
Measuring Ratio & Exciting (No-Load) Current
Surge arresters Bushings OLTC Leads Insulation materials Windings Core Principal
VP / VS =
Ratio measurement with the CPC 100 Setup for automatically measuring ratio and resistance per tap (see
The CPC 100 measures the transformer ratio by
applying a high voltage at the HV winding of
one transformer leg. In amplitude and phase, it
measures the applied voltage and the voltage at
the LV winding, as well as the exciting (no-load)
current. The deviation from rated values is
displayed as a percentage.
12
test setup How does it work? How can results be confirmed?
The winding ratio between primary and With the turns-ratio test, shorted turns can
secondary windings is measured for each be detected. If a problem is suspected from
transformer leg, applying high voltage at the a DGA, a dissipation factor test, or a relay
HV side and measuring on the LV side. The ratio trip, a turns-ratio test can be performed to
of these voltages, equalling the turns ratio, is rule out / verify if turns are shorted.
VS calculated. Results are compared with name-
plate values and across phases. If the exciting current test shows deviations,
and DC winding resistance and ratio test do
The exciting current is the corresponding current not show errors, then the cause may be a
flowing in the HV winding if the LV winding is core failure or unsymmetrical residual flux.
open. Results are compared with a reference
measurement, or a measurement performed on
TR a sister transformer; in three phase transformers,
= NP / NS
the two outer phases can also be compared.
Your Benefits
>> powerful AC voltage source,
controllable from 0 to 2000 V
13
Measuring DC Winding Resistance and OLTC
Surge arresters Bushings OLTC Leads Insulation materials Windings Core Burn-off at a
Measuring resistance with the CPC 100 Table in CPC 100 TRTapCheck test card Switching
The CPC 100 injects DC current into the
winding, measures current and voltage and then
calculates and displays the resistance. When the
resistance value is stable, the CPC 100 makes the
final measurement, and reduces the test current
to zero to discharge the energy saved in the
winding. When it is safe to remove test leads,
the CPC 100 illuminates its green safety light.
14
diverter switch How does it work? How can results be confirmed?
To measure the winding resistance, the Results should not differ more than 1 %
winding under test must first be loaded with compared to the reference measurement.
energy (E=1/2*L*I2) until the inductance of Differences between phases are usually less
the winding is saturated. Then the resistance than 2 - 3 %.
can be determined by measuring DC current
and DC voltage. For tapped windings, this Transformer turns ratio or frequency
should be done for every tap position, hence response analysis can be used to confirm
testing the OLTC and the winding together. contact problems. In both cases, hot spots
Results should be compared to a reference in the transformer will result in a DGA
measurement, across phases, or with a sister indicating increased heat. However, gas
transformer. In order to compare measurements, signatures are not unique and thus do not
the resistance values have to be re-calculated, allow for the identification of the root cause.
to reflect different temperatures during
the measurements.
Your Benefits
>> convenient and quick testing by using
OLTC operation as a trigger for the
next tap measurement
15
Automatically Measuring Ratio & Winding Resistance
Using the CP SB1 accessory, the CPC 100 can Faster Safer
automatically
>> measure ratio and the exciting current of all
of the taps and all phases
>> confirm the vector group
>> measure static and dynamic winding
resistance of all of the taps and all phases
Ratio measurement
The CPC 100 only requires the user to enter
ratio and the vector group to measure the
ratio and the exciting current for each tap of
each phase automatically. For each tap, results
are compared to the specified ratio and the
deviations are displayed.
16
of All Taps and All Phases
OLTC HV
Your Benefits
>> several times faster than conventional
wiring technique:
- minimum wiring - only once for all
connections
- automatic discharging of the
windings between measurements
- automatic tap changer operation
17
Measuring Short Circuit Impedance / Leakage Reactance
Surge arresters Bushings OLTC Leads Insulation materials Windings Core Regional
Numerous incidents exist of asset managers Measuring frequency response of stray losses
investigating the reason why their transformer is
gassing even though all standard electrical tests
show acceptable results. This illustrates that
their tools do not cover all trouble and failure
possibilities.
18
& Frequency Response of Stray Losses
An AC source is connected to each phase of the Leakage reactance: deviations of more than
HV winding with the corresponding LV winding 1 % ought to be investigated with other
shorted. The current and the voltage across tests such as FRA. Differences between
the HV winding are measured in amplitude phases are usually less than 2 %. Deviations
and phase, and the short circuit impedance of more than 3 % are considered significant.
is calculated. Short-circuit impedance Frequency response of stray losses (FRSL) results
measurements should ideally be performed over can be cross-checked with PD measurement,
a range of frequencies, commonly known as FRA, and DGA. If parallel strands are shorted,
Frequency Response of Stray Losses. Here, the higher losses in the stray channel will
AC source features variable frequency. After cause high internal temperatures, normally
source current and voltage have been measured indicated by a DGA. The gas signature
across the HV winding, the stray losses are is not unique and does not provide the
represented by the inductive part of the short identification of the root cause, however.
circuit impedance at higher frequencies. FRSL is unique in this respect.
Your Benefits
Leakage flux
>> a perfect digitally generated
sine wave test signal that is
independent from power quality
19
CPC 100 / CP TD1 - Operation According to Individual
20
Needs
1. Asset management
21
Dielectric Response Analysis of Power Transformers and
Surge arresters Bushings OLTC Leads Insulation materials Windings Core Typical shape of
1
Dissipation factor
Dielectric response analysis is used to assess the Moist
high Insula
water content of the solid insulation (cellulose) Oil co
and thus periodically monitor its condition.
0,001
0,001 Hz 1
Displaying the dissipation factor over a wide Verifying the insulation condition with DIRANA
frequency range provides insight into the
specific properties of the oil, the geometry
of the solid insulation in the form of spacers
and barriers, and the condition of the solid
insulation itself. This is the only method that
can - non-invasively - directly measure the actual
moisture content in the solid insulation.
22
Bushings
ture and aging of cellulose If the dissipation factor of a transformer is There are no other non-invasive ways to
ation Geometry
onductivity
plotted against a wide frequency range, the assess moisture in a transformer; dielectric
resulting dielectric response curve contains response analysis is unique in this respect.
information on the insulation condition.
The Karl Fischer titration method can
The very low and the high sections contain determine moisture content in oil or in
high information on moisture and aging in the solid paper, but has several disadvantages.
low insulation, while the position of the slope in the
mid range frequencies indicates the conductivity For instance, to determine moisture in
high of the liquid insulation. paper, the method requires opening the
transformer and taking a paper sample.
This curve is compared to model curves to During the process, the insulation itself is
low evaluate aging, particularly for assessing the being damaged and the sample takes up
1 Hz 1000 Hz moisture content in the insulation. new moisture.
Frequency
f range duration
Your Benefits
DIRANA comprehensive ~ 2.9 h
>> insulation condition assessment
concerning moisture / aging of
cellulose and oil conductivity
23
Sweep Frequency Response Analysis
Surge arresters Bushings OLTC Leads Insulation materials Windings Core Elements forming a
Frequency response analysis (FRA) is based on Test lead connection on transformer bushing using broad braids, clamps
the comparison of a reference test with an
actual test, where the reference test is usually a
fingerprint that has been previously measured.
When such a fingerprint is not available, another
phase or a sister transformer can also be used
for comparison.
24
unique fingerprint How does it work? How can results be confirmed?
A low voltage sinusoidal signal with variable Frequency response analysis can detect a
frequency is applied to one terminal of a wide range of faults. Some of these faults
winding and at the other end of the winding can be confirmed by other measurements,
the response signal is measured. The voltage such as DC winding resistance, frequency
transfer function of the winding is determined response of stray losses, short-circuit
as the output / input ratio. impedance / leakage reactance, exciting
current, or ratio measurement.
The transfer function of a winding depends on
the resistive, inductive and capacitive elements However, no other method can give as
of the transformer. Changes in these elements clear an indication as frequency response
as a consequence of a failure lead to changes in analysis can to determine whether windings
the transfer function. Results are represented in have been deformed, for example by the
magnitude and phase as in a Bode diagram. mechanical forces resulting from a fault.
Your Benefits
>> non-invasive detection of:
- winding deformations
- shorted parallel strands
- winding or interturn short circuits
- winding shorted to ground
- shorted core laminates
- floating core ground
- open circuits
- contact resistance problems
25
Partial Discharge Analysis
Surge arresters Bushings OLTC Leads Insulation materials Windings Core Partial discharge
The OMICRON MPD PD system offers quick and PD analysis on a three phase transformer
precise recording of pulses on the three phases
of a transformer using data acquisition from
three or more channels.
Digital filter
In the MPD 600 the classical analog bandpass
filter has been replaced by a digital filter using
a mathematical algorithm. Digital system
design eliminates aging effects and temperature
drift making measurements comparable and
reproducible by perfectly reproducing settings:
>> the digital filter can be easily adapted to
the conditions on site by tuning its center
frequency and bandwith to minimize
disturbances with fixed frequency bands
>> calibration values for charge and voltage
can be set directly on the laptop controlling
the test, fully reproducible during the next
measurement
Optical Isolation
Between individual PD acquisition units
and between the acquisition units and the
PC / laptop, fiber-optics are used for the
communication. Communication with fiber-
optics ensures a continuous, disturbance-free
transmission of PD events and test voltage. The
units are supplied using a battery power supply.
This design provides complete galvanic isolation
between the individual components, minimizing
ground loops and so reducing interference.
26
measurement How does it work? How can results be confirmed?
Multi-channel measurement
Measuring simultaneously with several channels
with synchronization accuracy in the range of
nanoseconds has several advantages:
>> it minimizes the time for which high voltage
has to be applied to a suspect transformer
and speeds up testing
>> it allows for real-time de-noising of the data
to minimize the influence of disturbances,
and helps separating different sources of PD
and identifying the type of PD sources
27
Partial Discharge Analysis
28
Ultra high frequency PD detection
Within liquid-insulated transformers, PD can also
be measured using ultra high frequency (UHF)
sensors. PD is directly measured from within
the tank, by flanging UVS 610 sensors directly
onto it, using its natural screening effect. The
UHF 608 accessory converts the signals for the
MPD. UHF measurement can also be used to
trigger an acoustic PD measurement, or as an
additional gating mechanism - then pulses from
an electrical measurement are only accepted if a
UHF pulse is also present.
noise cluster
Your Benefits
>> lightweight
29
Power Transformer Services, Training and Support
Technical support
High quality technical support teams also
provide answers to questions on the use of the
equipment, and are the first point of contact
should a functional problem occur. If a repair is
necessary, repair times are short - typically in the
range of less than one or two weeks.
Dedicated events
OMICRON hosts the regular Diagnostic
Measurements on Power Transformers
Workshop. There, typically over a hundred
delegates from all over the world share and
discuss case studies and recent developments in
transformer diagnosis.
30
Customer theoretical training Training courses
OMICRON training courses provide a solid
theoretical and practical background and answer
a client’s individual questions. Training courses
are held at either the customer’s site, online
through a webinar, or in one of the OMICRON
training centers wordwide.
Your Benefits
>> assistance in interpretation and
assessment of results
31
OMICRON is an international company serving the electrical
power industry with innovative testing and diagnostic solutions.
The application of OMICRON products allows users to assess
the condition of the primary and secondary equipment on their
systems with complete confidence. Services offered in the area of
consulting, commissioning, testing, diagnosis, and training make
the product range complete.