HW021-350-E-PR-DS-002 Page 11of 21

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

INSTRUMENT PROCESS DATASHEET

CLIENT ADANI HAZIRA PORT LTD DOC NO.


JOB NO HW021 HW021-350-E-PR-DS-002

PROJECT BERTH-4 EXTENSION


LOCATION HAZIRA,SURAT,GUJARAT

1 TAG NO PT-3091 PT-3101 PT-3111


PRESSURE PRESSURE PRESSURE
2 TYPE TRANSMITTER TRANSMITTER TRANSMITTER
3 FLUID STATE LIQUID LIQUID LIQUID
4 LOCATION P-29248-A21A-12''-IC P-29253-A1M-10'' P-29258-A21A-12''
HW021-350-E-PR- HW021-350-E-PR-DG- HW021-350-E-PR-
5 P&ID NO DG-002 Sheet 2 of 6 002 Sheet 2 of 6 DG-002 Sheet 5 of 6
6 OPERTATING CONDITIONS
OPERATING TEMPERATURE(deg C)
Minimum 10 10 10
Normal 35 35 35
Maximum 70 70 70
OPERATING PRESSURE(kg/cm2g) 7 7 7
7 DESIGN CONDITIONS
DESIGN TEMPERATURE(deg C) 80 80 80
DESIGN PRESSURE(kg/cm2g) 13.5/ Full Vacuum 11/ Full Vacuum 13.5/ Full Vacuum
8 ALARM SET VALUES
LOW (kg/cm2g) 2.5 2.5 2.5
HIGH (kg/cm2g) 7 7 7
LOW LOW (kg/cm2g) 1.0 1.0 1.0
HIGH HIGH (kg/cm2g) 12 10 12

9 REMARKS Note-1 Note-1 Note-1

1 TAG NO PT-3121 PT-3131


2 TYPE PRESSURE TRANSMITTER PRESSURE TRANSMITTER
3 FLUID STATE LIQUID LIQUID
4 LOCATION P-29263-A21A-12''-IC P-29268-A1M-10''-IC
HW021-350-E-PR-DG-002 HW021-350-E-PR-DG-002 Sheet
5 P&ID NO Sheet 5 of 6 5 of 6
6 OPERTATING CONDITIONS
OPERATING TEMPERATURE(deg C)
Minimum 10 10
Normal 35 35
Maximum 70 70
OPERATING PRESSURE(kg/cm2g) 7 7
7 DESIGN CONDITIONS
DESIGN TEMPERATURE(deg C) 80 80
DESIGN PRESSURE(kg/cm2g) 13.5/ Full Vacuum 11/ Full Vacuum
8 ALARM SET VALUES
LOW (kg/cm2g) 2.5 2.5
HIGH (kg/cm2g) 7 7
LOW LOW (kg/cm2g) 1.0 1.0
HIGH HIGH (kg/cm2g) 12 10

9 REMARKS Note-1 Note-1

HW021-350-E-PR-DS-002 Page 11of 21


11

You might also like