PCXCW14

Air-Cooled
PRODUCT SYSTEM
Application
Air Cooled Mini
Chiller
Solution
Fan Coil Unit

Chilled Water System


Solution Product Catalogue

Products manufactured in an ISO certified facility.


This document contains the most current product information as of this printing.
@2014-06
Contents Products Overview
kW
Cooling & Heating Capacity
4.0 6.0 8.0 10.0 15.0 20.0 25.0 30.0 40.0 50.0

R22 020/025/030/040/050/060/080/100/120/150

UAE 020/025/030/040/050/060/080/100/120/150
Application
025/030/040/050/060/080/100/120/150

01 R407C
UAP 060/080/100/120/150

020/025/030/040/050/055

Air Cooled Mini Chiller R410A


UAQ 020/025/030/040/050/055

04

FWE-E
Solution

FWC-C
13

Fan Coil Units


FUD-B

19 20 21 22 24
Wall Mounted Ceiling Cassette Ceiling Cassette Ceiling Cassette Ceiling Convertible
Compact Type (600 x 600) Type (900 x 900) Type (900 x 900) Type
With Brushless DC Motor

25 27
Ceiling Concealed Type Ducted Blower Type

Remark: All unit photos in this catalog are solely for illustration purpose, actual outlook may differ slightly.
All specifications are subjected to change by the manufacturer without prior notice.
Application

AIR COOLED MINI CHILLER APPLICATION EXAMPLES :

Private Houses Gym Centres Universities & Halls

Availablility of
cooling only
& heatpump
models
Hotels Office Rooms @ Coffee Houses

Restaurant

CHILLED WATER SYSTEM


SOLUTION ADVANTAGES :

Long Piping
Application

Simple On Site Quiet Operation


Installation

Chilled Water
System Solution
Advantages

Versatility In Less Refrigerant


Multiple temprature Serviceability & Error Energy Saving Dry Contact BMS System Coupling Handling
Centralized Control Master/Slave Option
Zone Control Code Troubleshooting Programmable Timer Compatibility
Network supports up Operation can be managed Easy access for servicing Customizable operation Control based on Abiblity to be integrated
to 50 chillers and 120 according to zones for all components. Error code schedule of chiller and FCU network grouping or with BMS
FCU different comfort need displayed on control panel based on requirement to application
No Necessity To
for troubleshooting promote energy saving Use Cooling Towers
purpose

LONG PIPING APPLICATION


Daikin chilled water system has no limitation in piping lengths unlike direct expansion
refrigerant system. As long as the water pump head pressure is sufficient to pump the
water through the water pipe network, the chiller can be installed far away from the fan
coil units. Daikin Mini Chiller is designed to support water operating pressure up to
1000kPa. With such high design pressure, Daikin mini chiller is capable of fulfiling In the
case where the Mini Chiller's built in pump head is insufficient to support the overall
friction loss, additional pump can be installed to cater for higher pump head requirement.

1 2
Air Cooled
QUIET OPERATION VERSATILITY IN SYSTEM COUPLING
Quiet operation due to fan coil units Chilled water system is designed with versatility in system
and chiller can be placed far away coupling where there is no limitation in the number of

Mini Chiller
from room fan coil unit coupling with mini chiller as long as they meet
the designed capacity requirament & water flow rate.
System coupling of one to one and one to many
configurations

Mini chiller can be installed


far away from fan coil units ONE TO ONE

LESS REFRIGERANT HANDLING


EASY INSTALLATION AND MAINTENANCE :
› Less Refrigerant Handling
› No Refrigerant Used In Occupied Space INTEGRATED HYDRONIC COMPONENTS
› Water As Cooling Medium
Daikin Mini Chiller is fully integrated and equipped with key
Refrigerant is only circulating within the mini chiller hydronic components such as expansion tank, water tank,
unit. Meanwhile, water acts as the cooling medium brazed plate heat exchanger and water circulating pump. As Brazed Plate Heat Exchanger
for FCU. When there is less refrigerant used, the all hydronic components are assembled and tested in the Plate type heat exchanger has a
scope of care on refrigerant handling is smaller. In factory, installation of additional component on site can be compact structure and a high level
case when there is a leak water is definitely easier eliminated. of heat exchange efficiency
to handle in term of process and cost.
ONE TO MANY
NO NECESSITY TO USE COOLING TOWERS MULTISTAGE END SUCTION
WATER PUMP Diaphragm Expansion Tank
Daikin mini chiller is designed for air cooled
application where is no necessity to use Impeller and all movable parts Prevent damage of hydraulic
components and cracking of
the cooling tower especially for small and in contact with the water are
piping due to expansion of hot
medium size of chilled water application made of stainless steels.
water in the pipes.

WATER STORAGE TANK


Prevent the compressor from
switching ON/OFF too frequently
FILTER DRIER during low load conditions such as
Remove dirt and moisture in night time.
the refrigerant circuit. NOTE:
Model UA(E/P)080~150C/CR water
tank is offered as an optional device.
SIMPLE ON SITE INSTALLATION

The Daikin mini chiller is fully assembled, complete FACTORY PRECHARGED REFRIGERANT
with all necessary components in one unit like water
Each heat exchanger in the chiller is brazed
pump, internal wiring, fully charged with refrigerant SERVICEABILITY & ERROR CODE FOR EASE OF
and undergo strict testing and quality check before and tested against leakages through dried air
TROUBLESHOOTING
delivery. Only connection to water piping and power at 30 bars. After that, another process of
supply is required at site. system vacuuming is done before it is By opening the front panel, one can access and service all the
components in the chiller. The chiller is equipped with self
accurately charged with refrigerant to ensure
diagnosis function which allow the chiller panel to display total of
optimum performance. Thus, it saves the 19 type of faulty occurred in the system by showing different
hustles of field charging by installers. error code on the LCD screen of the panel.

Refrigarent

3 4
PARALLEL INSTALLATION MICROPROCESSOR CONTROL SAFETY PROTECTION
Daikin Mini Chiller provides flexibility in adding Daikin chillers are equipped with microprocessor The safety protections provided for the Daikin chiller
capacity for building extension. This can be done controller that will control and regulate the operation are:
by installing the mini chiller in parallel of the unit. • High & Low Pressure Switches
connection. • Anti-Freeze Protection Sensor
Besides that, the controller that contains the well • Discharge Temperature Sensor
A network of up to 50 chillers is possible to be
developed algorithm will provide protection to the • Over Pressure Relief Valve
connected in a system. For ease of controlling
chiller by accurately sensing the key temperatures in • Water Pressure Differential Switch
and setting, Daikin Mini Chiller panel implement both the water and refrigerant circuit. Should there be • Anti-Freeze Heater on BPHE
Master and Slave function. This function allows any abnormal reading received by controller, an alarm • Compressor Water Pump & Fan Motor Overload
user to monitor all the settings on the slave units signal will be sent to chiller panel, followed by Protector
at the master unit. protection action plans such as to stop the operation
of compressor, condenser fan motor or circulating
water pump.
Supported Up To 50 Units Of Chiller
Chiller 0 Chiller 1 Chiller 2
BRAZED PLATE HEAT EXCHANGER (BPHE)
The heat exchanger is
made of AISI 316
stainless steel plates
closely arranged and
brazed together to
5 way wire (CM8)
Chiller
maximize possible
Chiller Panel 0 Chiller Panel 1 Communication Bus heat exchange
(Master) (Slave) efficiency.
AISI 316 stainless steel BPHE

SUPERIOR RELIABILITY :
EFFICIENCY AND PERFORMANCE :
State-Of-The-Art Components
CHILLER CONTROL PANEL • The display is shown in an 8-lines graphical LCD
SCROLL COMPRESSOR ANTI-FREEZE PROTECTION display. There are 8 dedicated keys available in the
The chiller panel controller is designed to control the
panel.
Scroll Compressors are used for the units to offer a The chiller unit has several anti-freeze protection chiller operation. This device allows the user to have
• Menu selection.
quieter and more reliable performance over a wide features: customized control for each connected unit.
• Navigation on the screen.
operating temperature range. (Except UAE020C/CR
1. Built-in heater in BPHE • Modification of the selected value.
which uses rotary compressor). Each chiller will have a chiller control panel that
The BPHE has a strip heater around it to prevent water
comes as a standard accessory. At the same time, the
freezing inside.
For UA(E/P) 030, 040, 050, 060, 080, 100, 120, 150 chiller control panel is able to be installed remotely
CR, phase protector is provided to prevent the 2. Anti-Freeze sensor through the cable up to a distance of 100 meters.
compressor from rotating in the wrong directions. BPHE can avoid the frosting as the anti-freeze sensor Example, the chiller panel can be installed in a
will send the signal to cut out the compressor if the centralized plant control room for the building.
water temperature becomes too cold.
Copeland 3. Water pressure differential switch The chiller control panel has been designed taking into
Compliant ®
This protection feature will ensure there is water flow consideration of the user friendly and yet versatile
Scrolls
in pipings when the chiller is in operation. Otherwise, control features.
High Efficiency
the compressor will cut out immediately.
Motor
Features:
• Whole system configuration.
Quiet Shutdown • Unique parameter settings.
Device
• Operation status display.
• Tracing fault record (offer quick troubleshooting
solutions).

5 6
LOAD BALANCING CONTROL ANTI CORROSION GOLD ALUMINUM FIN
FLEXIBILITY :
For UA(E/P)080 ~ 150 C/CR both compressors will Gold Aluminum fin is offered as the standard material
cut in and cut out depending on their of the condenser heat exchanger of this series of
TRUE DUAL CIRCUITS BPHE
accumulative operating time. This sequencing chiller. Apply sophisticated technology of true dual circuit
control feature will ensure no single compressor is BPHE.
overload in operation as well as to ensure longer
reliability of compressors. The true dual BPHE puts the secondary circuit
(water) in contact with 2 primary circuits
CAPACITY STEP CONTROL (refrigerant). So even if one primary circuit is shut
UA(E/P)080 ~ 150 C/CR has been designed with two off, each secondary channel is still in contact with a
separate refrigerant circuits, i.e. it has two primary channel. These advantages have made the
compressors. By doing so, the unit has part loading product the natural choice for flexible chillers,
capabilities, i.e. 0-50-100% of rated capacity. This will climate control applications and high-precision
improve the reliability and energy efficiency of the systems food cooling cabinets in supermarkets.
unit, especially during low loading operations.
Ref.1 Ref.2 Ref.1 Ref.2 Ref.1

EFFICIENCY AND PERFORMANCE :


water water water water

BETTER PERFORMANCE
PARALLEL INSTALLATION
• Usage of higher efficient R-410A rotary compressors
Air-Cooled Mini Chiller in tandem configuration A network up to 50 chillers in a system is possible.
• Tight tolerances between moving parts resulting in Control on the operation of the chillers will be done
Model: UAQ 030/040/055 CR high compressor volumetric efficiency through the microprocessor controller. The external
• Minimize mechanical losses water piping connection can be made either from
This innovative air cooled chiller by Daikin the left or right side of the unit.
• Minimize gas flow losses and turbulence
was designed with one purpose in mind,
• Optimize compressor oil return
which is to offer cost and energy saving for
users.
CAPACITY STEP CONTROL
3 steps compressor loading (0%-40%-60%-100%) for
UAQ 040 CR & UAQ 050 CR

2 steps compressor loading (0%-50%-100%) for


UAQ 030 CR & UAQ 055 CR

ELIMINATION OF WATER TANK


Combining the Tandem Compressors technology Chiller Panel Comes As
with the algorithm of the microprocessor control, The Standard Controller
water tank can be eliminated in most instances.

CHOICES OF SINGLE PHASE AND


3 PHASE POWER SUPPLY CONNECTION
• Usage of single phase power supply compressors
and circulating water pump.
• Offers flexibility to field installation.
Compatible With Smart Manager

7 8
R22 AIR COOLED MINI CHILLER SPECIFICATION
R22 COOLING MODEL R22 HEATPUMP MODEL
MODEL UAE020C UAE025C UAE030C UAE040C UAE050C UAE060C MODEL UAE020CR UAE025CR UAE030CR UAE040CR UAE050CR UAE060CR
Btu/h 20,000 24,200 30,000 39,500 48,500 54,000 Btu/h 19,000 23,000 27,500 38,000 44,000 50,000
NOMINAL COOLING CAPACITY NOMINAL COOLING CAPACITY W 5,570 6,740 8,060 11,140 12,900 14,650
W 5,860 7,090 8,790 11,580 14,210 15,830
NORMAL TOTAL INPUT POWER (COOLING) W 2,650 2,680 3,580 4,490 5,080 5,770 Btu/h 22,000 27,000 35,000 43,000 50,000 55,000
NOMINAL HEATPUMP CAPACITY
NORMAL RUNNING CURRENT (COOLING) A 12.25 12.17 16.41 9.67 9.75 12.01 W 6,450 7,910 10,260 12,600 14,650 16,120
EER W/W 2.21 2.65 2.48 2.58 2.80 2.74 COOLING W 2,530 2,670 3,440 4,230 5,190 5,580
NORMAL TOTAL INPUT POWER
HEATPUMP W 2,600 2,790 3,440 4,390 5,100 5,320
REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
REFRIGERANT CHARGE kg 1.25 1.80 1.88 2.80 3.15 3.30 COOLING A 11.78 12.17 17.27 9.05 9.77 12.60
NORMAL RUNNING CURRENT
POWER SOURCE (OUTDOOR) V/Ph/Hz 220-240/1/50 380-415/3/50 HEATPUMP A 11.62 12.70 17.25 9.14 9.72 11.50
REFRIGERANT TYPE R22 EER W/W 2.20 2.52 3.44 2.63 2.48 2.63
SOUND PRESSURE LEVEL dBA 57 57 58 59 59 59 COP W/W 2.48 2.84 3.43 2.87 2.87 3.03
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 790 x 1,160 x 460 1,140 x 1,160 x 460 REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
PACKING HEIGHT X WIDTH X DEPTH mm 920 x 1,270 x 570 1,551 x 1,270 x 570 REFRIGERANT CHARGE kg 1.43 1.75 1.83 3.50 4.10 4.00
UNIT WEIGHT kg 116 123 126 182 189 196 POWER SOURCE (OUTDOOR) V/Ph/Hz 220-240/1/50 380-415/3/50
NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 0.29 / 1.03 0.33 / 1.20 0.42 / 1.51 0.53 / 1.90 0.67 / 2.40 0.76 / 2.73 REFRIGERANT TYPE R22
INDOOR UNIT

TYPE ROTARY SCROLL SOUND PRESSURE LEVEL dBA 57 57 58 59 59 60


COMPRESSOR
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100% 0 - 100% 0 - 100% UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 790 x 1,160 x 460 1,140 x 1,160 x 460
TYPE THREAED PACKING HEIGHT X WIDTH X DEPTH mm 920 x 1,270 x 570 1,551 x 1,270 x 570
PIPING CONNECTION mm 25.4 UNIT WEIGHT kg 116 123 128 189 197 203
HEAD COOLING kPa 79 92 86 114 90 92 COOLING I/s/m3/hr 0.26 / 0.93 0.31 / 1.12 0.39 / 1.39 0.56 / 2.00 0.62 / 2.20 0.64 / 2.50

INDOOR UNIT
NOMINAL WATER FLOW RATE
CAPACITY / VOLUME L 22 40 HEATPUMP I/s/m3/hr 0.31 / 1.12 0.38 / 1.38 0.49 / 1.75 0.56 / 2.00 0.62 / 2.20 0.76 / 0.72
TANK
MATERIAL MILD STEEL WITH ZINC TYPE ROTARY SCROLL
COMPRESSOR
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100% 0 - 100% 0 - 100%
TYPE THREAED
MODEL UAE080C UAE100C UAE120C UAE150C
CONNECTION mm 25.4
Btu/h 65,000 95,000 116,000 138,000 PIPING 110
NOMINAL COOLING CAPACITY COOLING kPa 79 94 92 118 104
W 24,910 27,840 34,000 40,450 HEAD
HEATPUMP kPa 79 86 73 103 85 87
NORMAL TOTAL INPUT POWER (COOLING) W 8,870 10,590 11,370 14,220 CAPACITY / VOLUME L 22 40
NORMAL RUNNING CURRENT (COOLING) A 17.00 18.50 25.83 31.80 TANK
MATERIAL MILD STEEL WITH ZINC
EER W/W 8.87 2.63 2.99 2.84
REFRIGERANT CONTROL (EXPENSION DEVICE) TXV
REFRIGERANT CHARGE kg 3.90 x 2 4.60 x 2 6.00 x 2 7.10 x 2
POWER SOURCE (OUTDOOR) V/Ph/Hz 380-415/3/50 380-415/3/50 MODEL UAE080CR UAE100CR UAE120CR UAE150CR
REFRIGERANT TYPE R22 Btu/h 80,000 95,000 113,000 138,000
SOUND PRESSURE LEVEL dBA 63 63 67 67 NOMINAL COOLING CAPACITY W 23,450 27,840 33,120 40,450
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 1,245 x 1,500 x 900 1,245 x 1,800 x 1,150 Btu/h 95,000 105,000 120,000 132,000
NOMINAL HEATPUMP CAPACITY
PACKING HEIGHT X WIDTH X DEPTH mm 1,452 x 1,732 x 1,032 1,452 x 2,032 x 1,282 W 27,840 30,770 35,170 38,690
INDOOR UNIT

UNIT WEIGHT kg 328 340 480 560 COOLING W 8,490 11,100 12,070 14,320
NORMAL TOTAL INPUT POWER
NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 0.29 / 1.03 0.33 / 1.20 0.42 / 1.51 0.53 / 1.90 HEATPUMP W 8,750 10,310 12,370 15,020
TYPE SCROLL COOLING A 18.40 18.90 26.60 31.40
COMPRESSOR NORMAL RUNNING CURRENT
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100% HEATPUMP A 18.90 17.10 26.80 32.20
TYPE THREAED EER W/W 2.76 2.51 2.74 2.82
PIPING CONNECTION mm 31.75 COP W/W 3.18 2.98 2.86 2.58
HEAD COOLING kPa 229 229 188 157 REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
REFRIGERANT CHARGE kg 5.00 x 2 5.40 + 5.30 7.60 x 2 6.50 x 2
ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE POWER SOURCE (OUTDOOR) V/Ph/Hz 380-415/3/50
ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT) REFRIGERANT TYPE R22
SOUND PRESSURE LEVEL dBA 63 63 67 67
TEMPERATURE COOLING HEATING UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 1,245 x 1,500 x 900 1,245 x 1,800 x 1,150

ENTERING 12°C 40°C PACKING HEIGHT X WIDTH X DEPTH mm 1,452 x 1,732 x 1,032 1,452 x 2,032 x 1,282
EVAPORATOR UNIT WEIGHT kg 328 340 480 560
LEAVING 7°C 45°C

INDOOR UNIT
COOLING I/s/m3/hr 1.13 / 4.05 1.33 / 4.80 1.67 / 6.00 2.00 / 7.20
NOMINAL WATER FLOW RATE
CONDENSOR AMBIENT 35°C 7°C / 6°C HEATPUMP I/s/m3/hr 1.13 / 4.05 1.33 / 4.80 1.67 / 6.00 2.00 / 7.20
SCROLL
COMPRESSOR
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100%
TYPE THREAED
CONNECTION mm 31.75
PIPING COOLING kPa 254 173 188 157
HEAD
HEATPUMP kPa 229 144 188 157

ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT)

TEMPERATURE COOLING HEATING


ENTERING 12°C 40°C
EVAPORATOR
LEAVING 7°C 45°C
CONDENSOR AMBIENT 35°C 7°C / 6°C

9 10
R407C AIR COOLED MINI CHILLER SPECIFICATION R407C HEATPUMP MODEL
R407C COOLING MODEL MODEL UAP060CR UAP080CR UAP100CR UAP120CR UAP150CR
Btu/h 50,000 74,000 87,500 110,000 130,000
MODEL UAP025C UAP030C UAP040C UAP050C UAP060C NOMINAL COOLING CAPACITY W 14,650 21,690 25,640 32,240 38,100
Btu/h 23,000 26,900 38,500 47,000 50,000 Btu/h 55,000 90,000 96,000 118,000 144,000
NOMINAL COOLING CAPACITY NOMINAL HEATPUMP CAPACITY
W 6,740 7,880 11,280 13,920 14,650 W 16,120 26,380 28,140 34,500 42,200
NORMAL TOTAL INPUT POWER (COOLING) W 2,950 3,770 4,680 5,430 6,040 (COOLING) W 6,280 8,990 11,100 12,630 15,900
NORMAL TOTAL INPUT POWER
NORMAL RUNNING CURRENT (COOLING) A 13.30 17.41 9.62 10.20 11.28 (HEATPUMP) W 5,570 9,350 11,110 12,750 16,100
EER W/W 2.29 2.09 2.41 2.56 2.43 (COOLING) A 11.60 18.90 19.00 27.10 34.40
NORMAL RUNNING CURRENT
(HEATPUMP) A 11.50 19.00 19.10 26.10 34.80
REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE 2.55
EER W/W 2.33 2.41 2.31 2.40
REFRIGERANT CHARGE kg 1.72 1.63 3.00 3.30 3.20 COP W/W 2.83
2.89 2.53 2.71 2.62
POWER SOURCE (OUTDOOR) V/Ph/Hz 220-240/1/50 380-415/3/50 REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
REFRIGERANT TYPE R407C REFRIGERANT CHARGE kg 4.00 3.70 X 2 4.80 + 4.70 5.80 x 2 6.40 x 2
SOUND PRESSURE LEVEL dBA 57 58 59 59 60 POWER SOURCE (OUTDOOR) V/Ph/Hz 380-415/3/50 380-415/3/50
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 790 x 1,160 x 460 1,140 x 1,160 x 460 REFRIGERANT TYPE R407C
mm 920 x 1,270 x 570 1,551 x 1,270 x 570 SOUND PRESSURE LEVEL dBA 60 63 63 67 67
PACKING HEIGHT X WIDTH X DEPTH
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 1,140 x 1,160 x 460 1,245 x 1,500 x 900 1,245 x 1,800 x 1,150
UNIT WEIGHT kg 123 126 188 189 196 PACKING HEIGHT X WIDTH X DEPTH mm 1,551 x 1,270 x 570 1,452 x 1,732 x 1,032 1,452 x 2,032 x 1,282
INDOOR UNIT

NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 0.31 / 1.11 0.38 / 1.36 0.53 / 1.90 0.64 / 2.30 0.69 / 2.50 UNIT WEIGHT kg 203 340 340 480 560
COOLING I/s/m3/hr 0.64 / 2.30 1.03 / 3.70 1.25 / 4.50 1.67 / 6.00 1.89 / 6.80

INDOOR UNIT
TYPE SCROLL NOMINAL WATER FLOW RATE
COMPRESSOR HEATPUMP I/s/m3/hr 0.78 / 2.80 1.03 / 3.70 1.25 / 4.50 1.67 / 6.00 1.89 / 6.80
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 100% 0 - 100% 0 - 100% 0 - 100%
TYPE THREAED COMPRESSOR TYPE SCROLL
STAGE OF CAPACITY CONTROL 0 - 100% 0 - 50 -100% 0 - 50 -100% 0 - 50 -100% 0 - 50 -100%
PIPING CONNECTION mm 25.4
TYPE THREAED
HEAD COOLING kPa 94 93 117 93 110 CONNECTION mm 25.4 31.75
CAPACITY / VOLUME L 22 40 PIPING
COOLING kPa 110 263 193 188 172
TANK HEAD HEATPUMP 170 170 172
MATERIAL MULTISTAGE END SUCTION kPa 87 188

ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
MODEL UAP080C UAP100C UAP120C UAP150C ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT)
Btu/h 80,000 90,000 115,000 137,000
NOMINAL COOLING CAPACITY TEMPERATURE COOLING HEATING
W 23,450 26,380 33,730 40,150
NORMAL TOTAL INPUT POWER (COOLING) W 9,430 11,210 12,170 14,970 ENTERING 12°C 40°C
NORMAL RUNNING CURRENT (COOLING) A 18.00 19.22 26.50 33.00 EVAPORATOR
EER W/W 2.49 2.35 2.77 2.68 LEAVING 7°C 45°C
CONDENSOR AMBIENT 35°C 7°C / 6°C
REFRIGERANT CONTROL (EXPENSION DEVICE) TXV
REFRIGERANT CHARGE kg 3.90 x 2 3.80 x 2 5.60 x 2 6.00 x 2
POWER SOURCE (OUTDOOR)
REFRIGERANT TYPE
V/Ph/Hz 380-415/3/50
R407C
R410A AIR COOLED MINI CHILLER SPECIFICATION
SOUND PRESSURE LEVEL dBA 63 63 67 67
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 1,245 x 1,500 x 900 1,245 x 1,800 x 1,150 R410A HEATPUMP MODEL
PACKING HEIGHT X WIDTH X DEPTH mm 1,452 x 1,732 x 1,032 1,452 x 2,032 x 1,282
UNIT WEIGHT kg 340 340 480 560 MODEL UAQ020CR UAQ025CR UAQ030CR UAQ040CR UAQ050CR UAQ055CR
INDOOR UNIT

NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 1.14 / 4.10 1.25 / 4.50 1.67 / 6.00 2.00 / 7.20 Btu/h 15,700 21,000 24,800 34,000 41,600 45,000
NOMINAL COOLING CAPACITY
TYPE SCROLL W 4,600 6,150 7,270 10,000 12,200 13,200
COMPRESSOR Btu/h 21,500 25,000 32,500 43,000 48,000 55,000
STAGE OF CAPACITY CONTROL 0 - 50 - 100% 0 - 50 - 100% 0 - 50 - 100% 0 - 50 - 100% NOMINAL HEATPUMP CAPACITY
TYPE THREAED W 6,300 7,330 9,530 12,600 14,070 16,120
(COOLING) W 2,620 2,760 3,830 5,000 5,310 5,490
PIPING CONNECTION mm 31.75 NORMAL TOTAL INPUT POWER
(HEATPUMP) W 2,590 2,790 3,630 4,650 5,150 5,440
HEAD COOLING kPa 229 229 188 157 (COOLING) A 11.76 12.70 16.88 7.44 7.90 8.18
NORMAL RUNNING CURRENT
(HEATPUMP) A 11.93 12.90 16.32 7.20 7.83 8.38
ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE EER W/W 1.76 2.23 1.90 2.00 2.30 2.40
ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT) COP W/W 2.43 2.63 2.62 2.71 2.73 2.96
REFRIGERANT CONTROL (EXPENSION DEVICE) CAPILLARY TUBE
TEMPERATURE COOLING HEATING REFRIGERANT CHARGE kg 1.20 1.725 2.20 4.30 4.20 4.30
POWER SOURCE (OUTDOOR) V/Ph/Hz 220-240/1/50 380-415/3/50
ENTERING 12°C 40°C REFRIGERANT TYPE R410A
EVAPORATOR
LEAVING 7°C 45°C SOUND PRESSURE LEVEL dBA 58 59 57 59 59 61
UNIT DIMENSION HEIGHT X WIDTH X DEPTH mm 790 x 1,160 x 460 1,140 x 1,160 x 460
CONDENSOR AMBIENT 35°C 7°C / 6°C PACKING HEIGHT X WIDTH X DEPTH mm 920 x 1,270 x 570 1,551 x 1,270 x 570
UNIT WEIGHT kg 128 128 128 195 195 195

INDOOR UNIT
NOMINAL WATER FLOW RATE COOLING I/s/m3/hr 0.24 / 0.86 0.28 / 1.00 0.42 / 1.50 0.50 / 1.80 0.60 / 2.15 0.75 / 2.70
HEATPUMP I/s/m3/hr 0.32 / 1.16 0.35 / 1.25 0.42 / 1.50 0.50 / 1.80 0.60 / 2.15 0.75 / 2.70
TYPE ROTARY TANDEM ROTARY
COMPRESSOR STAGE OF CAPACITY CONTROL 0-100% 0-100% 0-50-100% 0-40-60-100% 0-40-60-100% 0-50-100%
TYPE THREADED
CONNECTION mm 25.4
PIPING
COOLING kPa 90 98 93 90 74 70
HEAD
HEATPUMP kPa 73 90 80 71 64 53
CAPACITY / VOLUME L 22 40
TANK
MATERIAL MILD STEEL WITH ZINC

ALL SPECIFICATION ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE
ALL UNIT ARE BEING TESTED AND COMPLY TO ISO 5151 (NON-DUCTED UNIT) OR ISO 13253 (DUCTED UNIT)

TEMPERATURE COOLING HEATING


ENTERING 12°C 40°C
EVAPORATOR
LEAVING 7°C 45°C
CONDENSOR AMBIENT 35°C 7°C / 6°C

11 12
DISPLAY UP TO 46 TYPES OF CHILLER FAULT /
SMART MANAGER CONTROLLER ALARM AND 6 TYPES OF FCU FAULT / ALARM
By adopting the Daikin chilled water system, the comfort in residential and light commercial Whenever a fault occurred in either the chiller or fan coil unit,
buildings such as offices, hospital, restaurant, hotel and shopping complex can be controlled and a signal will be sent to Smart Manager and an alarm message will (Ch 0)
appear on the LCD, showing type of alarm, alarm occured time,
managed from just one point, that is through the Smart Manager. Alarm 1
date and unit.
The Smart Manager is acting as a central command to manage the operation of both the chilled Comp 1 overload
This will greatly ease the troubleshooting process and thus
water fan coil units and the chillers. reduce the valuable time of service technicians.
01/01/00 12.00am
Besides allowing the user to have customized control for each connected unit, the Smart As soon as the fault is solved, the alarm will automatically
Manager is also able to manage the overall system operating mode of all units based on the air dissolve from the LCD.
conditioning system load demand of the building.

Fan Coil Network BUS Chiller Network BUS ENERGY SAVING PROGRAMMABLE TIMER
The operation of the chiller and each fan
coil unit can be preset to operate and to
stop at different time schedule and at FWC

different day of a week. Taking consideration FWK

of the fact that certain rooms in a building

Unit
FWE 2

will be empty at certain period of the day, FWE 1

setting timer to On and to Off the operation FWW

of units in those areas will greatly reduce


SUPPORTED UP TO 50 CHILLERS & 120 FAN COIL UNITS the energy cost of the building.
8.00
am
9.00
am
10.00
am
11.00 12.00
am am
1.00
pm
2.00
pm
3.00
pm
4.00
pm
5.00
pm
6.00
pm
7.00
pm

Time
Through the versatile Smart Manager controller, the operation of each equipments in the Daikin chilled
water system connected through the chiller Bus and Daikin own proprietary NIM BUS can be managed At the same time, Smart Manager allows
and controlled. setting of up to five sets of 7 days programmable operation schedules (2 On/Off timer per day) for each
fan coil unit

CHILLER CHILLER CHILLER


PANEL PANEL PANEL

CHILLER CHILLER CHILLER

Up to
A
B 50 units
Smart Manager Controller CHILLER BUS
of Chiller

NIM BUS Up to
A
B 120 units
of FCUs
NIM NIM NIM

FCU FCU FCU WIRED


CONTROLLER

13 14
THRESHOLD VALUE SETTING
If the priority setting is being preset to fan coil unit, the
FWC
operating mode of the complete Daikin chilled water
system can be synchronized to operate under one same
mode. This is achievable through the unique feature called
“Threshold Value Setting”

FWK Smart Manager can command chiller operating mode to


FWE 2
switch from current operating mode if the threshold value
is meet.

FWE 1
FWW
Example,
In a network of 10 fan coil units that is currently operating
in COOL mode and a threshold of 60% was set for COOL
mode and threshold of 50% was set for HEAT mode. Should
6 of the fan coil units are requesting for HEAT mode then
the threshold for HEAT is crossed. Signal will be sent by
Smart Manager to chiller BUS to switch the operating
mode of all chillers to HEAT mode. Requirement of users
will be met.

• Heat Treshold •

Chiller to operate at
PASSWORD PROTECTION FOR ADVANCED HOLIDAY SETTING
Heat Mode
PARAMETER SETTINGS (CHILLER) While designing the Smart Manager, the practical aspects of
A Daikin chilled water product system with key equipment application were always the key points to be
0 1 2 3 4 5 6 7 8 9 10 parameters that were set by personnel to optimize considered. Thus resulting in the creation of “Holiday
Chiller to operate at operating conditions will need to be protected against Setting” feature.
Cool Mode any unauthorized disturbance or changes. The built in
“Password Settings” feature will prevent the losing of In this feature, users are allowed to set up to 10 holiday
key parameter settings in the Smart Manager timers with each timer can last for duration of 99 days.
• Cool Treshold • controller as well as the chiller panel
During the duration of Holiday Timer set earlier, all fan coil
units and chiller will automatically be turned Off.

PRIORITY SETTING MEMORY BACKUP (EEPROM),


Depending on the application requirement, ALARM MEMORY FOR CHILLER AND FCU KEY PARAMETER DISPLAY HOLIDAY SETTINGS
Smart Manager controller offers the flexibility to For easy serviceability and maintenance, Smart Holiday 1
allow user to set the priority on the operation of When there is power failure occurs during operation, Manager Controller's is able to display the key Holiday 2
fan coil unit and Chiller in a complete Daikin Smart Manager Controller will load the last state memory parameter such as defrost and compressor discharge
from EEPROM after power On reset. Holiday 3
chilled water product system. sensor temperature, water in/out temperature, status
Holiday 4
of compressor On/Off, Cool/Heat mode water in
Besides, extra memory space inside the Smart Manager Holiday 5
If priority is set to fan coil unit, the chiller will be temperature, etc. Thus, it reduces the cumbersome of
forced to OFF if all fan coil units are OFF. If controller will allow user to view the previous alarm requiring the service technicians to physically go to site
records even though its have been dissolved. This useful Set Holiday 1
Chiller Priority is being set, all fan coil units will of chiller installation to do the troubleshooting
be OFF if chillers are OFF. information will benefit the service technician to view the process. Month : 1
history of maintenance record done to the unit. Day : 1
Duration : Disable