514842400.doc Profibus Settings: Profibus Address Table - Incoming Data
514842400.doc Profibus Settings: Profibus Address Table - Incoming Data
doc
Profibus settings
18.03.2021
PROFIBUS
In total 16 bytes are received from the Bus. Analog value data is to be in the data form "signed word"
which should be limited to a value range in-between -10 000 to +10 000. The first two words are
reserved for the set-points for drive 1 and drive 2. The following 4 words are selectable analog inputs.
Digital signals are represented by one bit, in total for 24 inputs, 3 bytes.
The analog values are in "signed word" data format. Negative numbers are the 2's complement of the
positive ones. Below is a table with some examples
The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.
Hägglunds Drives AB. S-890 42 Mellansel, SWEDEN 1(6)
514842400.doc
Profibus settings
18.03.2021
The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.
Hägglunds Drives AB. S-890 42 Mellansel, SWEDEN 2(6)
514842400.doc
Profibus settings
18.03.2021
The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.
Hägglunds Drives AB. S-890 42 Mellansel, SWEDEN 3(6)
514842400.doc
Profibus settings
18.03.2021
20:0 Start1 21:0 P1HiCa 22:0 Forw2 23:0 ShBlck2 24:0 Ready2 25:0 Dummy
20:1 Remote1 21:1 P1CAct 22:1 Rev2 23:1 A1 24:1 EMotD1 25:1 Dummy
20:2 Auto1 21:2 PLim 22:2 Reg2 23:2 A2 24:2 EMotD2 25:2 Dummy
20:3 PLim1 21:3 ShBlck1 22:3 CZero 23:3 W1 24:3 CoolCon 25:3 Dummy
20:4 Forw1 21:4 Start2 22:4 Synchro 23:4 W2 24:4 HeatCon 25:4 Dummy
20:5 Rev1 21:5 Remote2 22:5 P2LoCa 23:5 Int1 24:5 Dummy 25:5 Dummy
20:6 Reg1 21:6 Auto2 22:6 P2HiCa 23:6 Int2 24:6 Dummy 25:6 Dummy
20:7 P1LoCa 21:7 PLim2 22:7 P2CAct 23:7 Ready1 24:7 Dummy 25:7 Dummy
DB20 to DB25 are signals to be found in the list of available functions for the digital relay outputs,
described in the Engineering manual for Spider, AS6.10.
DB26 to DB37 are partly signals to be found in the list of available functions for the digital inputs,
described in the Engineering manual for Spider, AS6.9.
Note. A short explanation is included (of most of the signals), see next page.
The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.
Hägglunds Drives AB. S-890 42 Mellansel, SWEDEN 4(6)
514842400.doc
Profibus settings
18.03.2021
The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.
Hägglunds Drives AB. S-890 42 Mellansel, SWEDEN 5(6)
514842400.doc
Profibus settings
18.03.2021
The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.
Hägglunds Drives AB. S-890 42 Mellansel, SWEDEN 6(6)