Design Data:
𝑄= 650𝑀𝑇/ℎ𝑟 𝑥 1ℎ𝑟/3600
1. Discharge Pressure at Pier = 7Bar.
Design Data:
𝑄= 250𝑀𝑇/ℎ𝑟 𝑥 1
Convert of Mass Flowrate to Volume Flowrate, Q (m3/s)
Q= 0.038 m3/s
V = 4.5953461 m/s
Re = 36027.21
Calculate for Friction Factor, f
f= 0.020
f= 0.0240
f= 0.0236
f= 0.0237
HL = 244.45903 m
P = 347.34033 Psi
Design Data:
𝑄= 300𝑀𝑇/ℎ𝑟 𝑥 1
Convert of Mass Flowrate to Volume Flowrate, Q (m3/s)
Q= 0.045 m3/s
V= 5.514 m/s
Re = 43232.65
Calculate for Friction Factor, f
f= 0.020
f= 0.0231
f= 0.0228
f= 0.0229
HL = 340.13844 m
P = 483.28669 Psi
Design Data:
𝑄= 400𝑀𝑇/ℎ𝑟 𝑥 1
Convert of Mass Flowrate to Volume Flowrate, Q (m3/s)
Q= 0.060 m3/s
V= 7.353 m/s
Re = 57643.53
Calculate for Friction Factor, f
f= 0.020
f= 0.0219
f= 0.0217
f= 0.0218
HL = 576.6477 m
P = 819.33157 Psi
Design Data:
𝑄= 600𝑀𝑇/ℎ𝑟 𝑥 1
Convert of Mass Flowrate to Volume Flowrate, Q (m3/s)
Q= 0.091 m3/s
V= 11.029 m/s
Re = 86465.30
Calculate for Friction Factor, f
f= 0.0200
f= 0.0205
f= 0.0205
f= 0.0205
HL = 1217.6659 m
P= 1730.12 Psi
Design Data:
𝑄= 750𝑀𝑇/ℎ𝑟 𝑥 1
Convert of Mass Flowrate to Volume Flowrate, Q (m3/s)
Q= 0.113 m3/s
V= 13.786 m/s
Re = 108081.62
Calculate for Friction Factor, f
f= 0.020
f= 0.0198
f= 0.0198
f= 0.0199
HL = 1844.4898 m
P = 2620.7487 Psi
Design Data:
𝑄= 650𝑀𝑇/ℎ𝑟 𝑥 1ℎ
Convert of Mass Flowrate to Volume Flowrate, Q (m3/s)
Q= 0.12 m3/s
V = 3.655533 m/s
Re = 15118.90
Calculate for Friction Factor, f
f= 0.02775
HL = 132.238 m
P = 187.8907 Psi