Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

1.

Application
SMGQ2 series new type dual power automatic transfer switch (ATS) integrating switch with

logical control and realizing mechatronics, is mainly used in the industrial and enterprise

distribution equipment of AC 50Hz, rated voltage up to 440V and conventional thermal current up

to 3200A to auto transfer between main power and backup power of distribution system or auto

transfer and safely insolation between two load equipments.

The switch rapidly connects, breaks and transfers the circuit through the operation mechanism

of main switch body driven by the motor which is controlled by kinds of logical demand from the

control circuit board, to obviously realize safe isolation.

The switch has the operations of full automation compulsory “ 0 ” , remote control and

emergent manual. It is equipped with functions of phase loss inspection, communication interface,

electro-mechanical interlock, generator (oil machine). It is the best choice among similar products.

2. Model Meaning
SMG Q 2 - □ / □ □
--

Control Type: 0-Full Automatic


1-Full Automatic + Compulsory “0”
2- Full Automatic + Remote
Pole NO.: 3P 4P
Rated Current: 16A-3200A
PC Grade
Dual Power Automatic Transfer Switch
Company Code

3. Structure
3.1 Electric Key lock: Control the internal control circuit power of switch, if it is unlocked, the switch

can be full automatic, remote, and compulsory “0”; if it is locked, it can be only operated by manual.

3.2 Handle: The electrical lock must be locked before manual operation with it.

3.3 Mechanical Padlock: Specified for examine and repair. When examine and repair, turn the switch

to Position “0”, pull out the padlock mechanism and then put on the padlock to avoid any incidents

(pulling out the padlock can cut off the internal control power)

3.4 Indicator: “I”---main power connected, “II”---backup power connected, “0” -both power break
Operating Handle

Body Ⅰ (Main Power)

Body Ⅱ (Backup Power)

Control Part

Inlet Terminal

Nameplate

Indicator

Electric Key Lock

Mechanical Padlock

Outlet Terminal

4. Main Technical Parameter


4.1 Standards: IEC 60947-6-1 GB 14048.00-2008

4.2 Rated Working Voltage (Ue): AC440V

4.3 Rated Connecting Capacity (A Rms): 10Ie

4.4 Rated Breaking Capacity (A Rms): 8Ie

4.5 Control Power Voltage: DC24V, 48V, 110V, AC220V


Rated Thermal
100 160 250 400 630 1000 1250 1600 2000 2500 3200
Current (A)
Rated Insulation
750V 1000V
Voltage (V)
Rated Impulse
8kV 12kV
Withstand Voltage
Rated AC-31 100 160 250 400 630 1000 1250 1600 2000 2500 3200
Working AC-35 100 160 250 400 630 1000 1250 1600 2000 2500 3200
Current AC-33 100 160 250 400 630 1000 1250 1600 2000 2500 3200
Rated Short Time
7kA 9kA 13kA 50kA 55kA
Withstand Current
Rated Limit Short
100kA 70kA 100kA 120kA 80kA
Circuit Current
Control Power
DC24V, 48V, 110V, AC220V
Voltage
Transfer Time (S) 0.5 1 1.1 1.2 1.25 2.45
5. Wiring Diagram
Backup Power Ⅱ
Main Power Ⅰ

(must be connected) (must be connected)

Padlock

Load Side

6. Functions
6.1 Full Automatic Function: Self Charge Self Recovery. . When main power is powered off or phase

loss, the switch will auto transfer to backup power; when main power recovers, the switch will auto

back to main power.

6.2 Compulsory “0” Function: When emergency or maintenance, motivate compulsory “0” self lock

button, the switch will auto transfer to “0” to cut off the two powers.
6.3 Remote Control Function: Far distance control. Press “Ⅰ” button, the main power works; press

“Ⅱ” button, backup power works; press “0” button, cut off the both powers.

6.4 Choose the switch function according to requirement and connect the wire correspondingly.

6.5 Please specify the switch model, current, and function demanded when ordering.

7. Outline and Installation Dimensions

Handle Rotating Range (Max.)

Electrical Control Connection


Specification Outline and Installation Dimensions
In A A1 B B1 C E G J K L N P R S T U W ΦX Y Y1
100A/3 235 232 106 105 134 133 115 221.5 84 7 74.5 30 14 18 2.5 105 126 6 36 86
100A/4 247 244 106 105 134 133 115 233.5 84 7 74.5 30 14 18 2.5 105 125 6 36 86
125A/3 292 270 135 128 230 189 145 254 102 7 91 36 20 25 3.5 127 158 9 55 125
125A/4 322 300 135 128 230 189 145 284 102 7 91 36 20 25 3.5 127 158 9 55 125
160A/3 292 270 135 128 230 189 145 254 102 7 91 36 20 25 3.5 127 158 9 55 125
160A/4 322 300 135 128 230 189 145 284 102 7 91 36 20 25 3.5 127 158 9 55 125
250A/3 356 312 170 142 261 208 145 293 102 7 91 50 25 30 3.5 142 168 11 60 145
250A/4 406 362 170 142 261 208 145 343 102 7 91 50 25 30 3.5 142 168 11 60 145
400A/3 487 368 260 222 284 273 189 351 180 9 93 65 32 40 5 222 203 11 83 139
400A/4 552 433 260 222 284 273 189 416 180 9 93 65 32 40 5 222 203 11 83 193
630A/3 487 368 260 222 284 273 189 351 180 9 93 65 40 50 6 222 203 12 83 193
630A/4 552 433 260 222 284 273 189 416 180 9 93 65 40 50 6 222 203 12 83 193
800A/3 646 519 357 250 363 350 443 499 220 11 87 120 60 69 8 250 207 12.5 109 254
800A/4 760 633 357 250 363 350 443 613 220 11 87 120 60 69 8 250 207 12.5 109 254
1000A/3 646 519 357 250 363 350 443 499 220 11 87 120 60 69 8 250 207 12.5 109 254
1000A/4 760 633 357 250 363 350 443 613 220 11 87 120 60 69 8 250 207 12.5 109 254
1250A/3 646 519 357 250 363 350 443 499 220 11 87 120 80 69 8 250 207 13 110 255
1250A/4 760 633 357 250 363 350 443 613 220 11 87 120 80 69 8 250 207 13 110 255
1600A/3 646 519 357 250 363 350 443 449 220 11 87 120 80 69 10 250 207 13 110 255
1600A/4 760 633 357 250 363 350 443 613 220 11 87 120 80 69 10 250 207 13 110 255
2000A 800 633 460 542 447 610 84.5 80 120 10 169
2500A 800 633 460 542 447 610 84.5 80 125 15 174
3200A 800 633 460 542 447 610 84.5 80 130 20 179
8. External Terminal Wiring Diagram
8.1 Typical Wiring
Control Electrical Apparatus

Main Power Backup Power

8.2 Full Automatic Wiring

Ⅰ 0 Ⅱ
220V~0V Output 220V~0V Output Close Break Close
Control Manual
~220V Power Output
Auto
Main Power Backup Power

Full Automatic Short Connection


Compulsory “0” Contact (Passive Source)

Full Automatic Control Wiring Diagram

 HL1: Main Power Indicator

 HL2: Backup Power Indicator


Start Generator
 HD1: Close Indicator of Main Power
~220V Input
 HD2: Close Indicator of Backup Power

 FU1-FU2: 2A Fuse

 NO.1 Terminal is already sampled internally


8.3 Full Automatic + Compulsory “0” (Two Powers are Cut OFF) Wiring

Main Power Backup Power

Auto/Manual Mechanical Lock

Indicator Indicator

(Passive Source) (Passive Source)

External Wiring Indicator (Passive Source)

Compulsory “0” Contact (Passive Source)

8.4 Generator Wiring


8.5 Full Automatic + Manual (Remote) Wiring

Main Power Backup Power

Auto/Manual Mechanical Lock

Indicator Indicator

(Passive Source) (Passive Source)

External Wiring Indicator (Passive Source)


Auto Manual (Remote)

8.5 Generator Wiring


Main Power Backup Power

Auto/Manual Mechanical Lock

Indicator Indicator

(Passive Source) (Passive Source)

External Wiring Indicator (Passive Source)

1) HL1, HL2 is respectively the power on indicator of main power and backup power; HD1, HD2 is

respectively the charge indicator of main power and backup power; FU1 and FU2 are 2A fuses.

2) 302-305 are FATSD switch terminal

3) 101-106, 201-206, 301-306 are FATSD switch terminal


4) 401-406, 501-506 are switch terminal optional

5) SA is switch to choose auto/manual function

6) SB1, SB2 is respectively the manual charge button (passive contact) of main power and backup

power

7) 1QF is main circuit (main power) protection switch alarm contact, 1KT is power delay (0-180s),

2KT is power off delay (0-180s)

9. DC24V/DC48V Wiring Diagram


9.1 Basic Wiring

DC24V/DC48V Input

9.2 Other Wiring

Switch Status Indicator


220V Input

External Wiring Indicator (Passive Source) Auto/Manual Mechanical Lock

Indicator Indicator

(Passive Source) (Passive Source)

Note Note: In dash frame is the internal auxiliary contact of FATSD


switch