Instruction Manual

(Input Conversion)

DC1010/1020
1030/1040

Rev 4
Contents

1. Input Change (TC & Linear  RTD) ......................................................................................3


2. Wiring Distinction between TC& Linear .....................................................................................4
3. Linear Input H/W Setting .........................................................................................................5
4. To view the ANL1, ANH1 parameters. .......................................................................................7
4-1. Unlock the protection.....................................................................................................7
4-2. Show the parameters.....................................................................................................7
4-3. Calibration ....................................................................................................................8
4-4. Procedure of Calibration .................................................................................................9
1. Input Change (TC & Linear  RTD)
To change the input type from TC to RTD or RTD to TC,Move a jumper.
For Linear type, it’s same as that of TC.

1) DC1010

TC

RTD

2) DC1020/DC1030/1040

TC

RTD

* No Calibration or Adjustment Required


While Input Conversion between TC & RTD.
2. Wiring Distinction between TC& Linear
1) DC1010
Input Wiring

Linear TC
7 7 Set Input Code in Level 3
for TC or Linear Input after Profer Wiring
8 8

9 9

10 10

2) DC1030
Input Wiring

Linear TC
11 11
Set Input Code in Level 3
for TC or Linear Input after Profer Wiring
12 12

13 13

14 14

3) DC1020/1040
Input Wiring

Linear TC
17 17
Set Input Code in Level 3
for TC or Linear Input after Profer Wiring
18 18

19 19

20 20
3. Linear Input H/W Setting
For jumper, please see ‘1. Input Changes’ section.
1) DC1010

R1
R4 R2
S1 S4 R5 R3
S2
S3
S5

7 8 9 10

Input Code S1 to S5
Input Type R1 to R5
AN 4 AN 5 Jumper Status
0~20 mA
mA R3 = 100  R5 = 2.4  S3 & S5 Short
4~20 mA
0~1 V R1 = 2 K S1 & S4 Short
V 0~5 V 1~5 V R2 = 10 K R4 = 100  S2 & S4 Short
0~10 V 2~10 V R3 = 22 K S3 & S4 Short
mV 0~100mV 20~100mV - - S3 & S4 Short

2) DC1030

R1
R4 R2
S1 S4 R5 R3
S2
S3
S5

11 12 13 14

Input Code S1 to S5
Input Type R1 to R5
AN 4 AN 5 Jumper Status
0~20 mA
mA R3 = 100  R5 = 2.4  S3 & S5 Short
4~20 mA
0~1 V R1 = 2 K S1 & S4 Short
V 0~5 V 1~5 V R2 = 10 K R4 = 100  S2 & S4 Short
0~10 V 2~10 V R3 = 22 K S3 & S4 Short
mV 0~100mV 20~100mV - - S3 & S4 Short
3) DC1020/1040
R1
R4 R2
S1 S4 R5 R3
S2
S3 S5

17 18 19 20

Input Code S1 to S5
Input Type R1 to R5
AN 4 AN 5 Jumper Status
0~20 mA
mA R3 = 100  R5 = 2.4  S3 & S5 Short
4~20 mA
0~1 V R1 = 2 K S1 & S4 Short
V 0~5 V 1~5 V R2 = 10 K R4 = 100  S2 & S4 Short
0~10 V 2~10 V R3 = 22 K S3 & S4 Short
mV 0~100mV 20~100mV - - S3 & S4 Short

Input Code
Input Type
AN 1 AN 2 AN 3 AN 4 AN 5
mV -10~10mV 0~10mV 0~20mV 0~50mV 10~50mV
4. Calibration Procedure
Check if it shows the ANL1 and ANH1 on CONFIGURATION2. (Go to step 4-3.)
If the parameters are not shown, go to below steps.
4-1. Unlock the protection
Go to ‘LCK’ parameter on CONFIGURATION 1.
(1-1) Press the SET key for 5 seconds. It will show P1 on CONFIGURATION 1.

5seconds

5seconds

Step (1-4)
(1-2) Press the SET key until it will show LCK parameter.
(1-3) Input ‘1111’ to LCK parameter by using up/down and shift key.
(1-4) Press the SET and shift key for 5 seconds at ‘step (1-3)’. It shows ‘SET1’ of Step (2-1).
4-2. Show the parameters
Modify parameter of ‘CONFIGURATION 3’
SET2.4
SET2.3
SET2.2
SET2.1

Step (2-3)
(2-1) Press the SET key just one time until it will shows ‘SET2’.
(2-2) Change the first value of left side to 1. (SET2.2 = 1)
In case of RSP(Input2), SET2.4=1.(It shows ANL2, ANH2.)
(2-3) Press the SET and shift key for 5 seconds and return to OPERATION.
4-3. How to Calibrate
(3-1) Preparation of sources
- DC Current source : DC 0~20mA or 4~20mA
- DC voltage source : DC 0~1V, 0~5V, 0~10V, 1~5V, 2~10V
(3-2) Press the SET and shift key for 5 seconds, it will show ‘INP1’ of Configuration2.
Set INP1 to ‘AN5’ in case of DC 4~20mA.(Refer to INPUT CODE of ‘Linear input H/W setting’)

(3-3) Press the SET key just one time to show ANL1 parameter.
(3-4) Connect input source with INP1 terminals according to wiring diagram.
(3-5) Adjust the calibration values for Lower side(ANL1) and Upper side(ANH1).

In case of RSP(Input2), execute the calibration for each ANL2, ANH2.


(3-6) Refer to procedures as followings.
4-4. Procedure of Calibration
(Range of PV : 0~3000, Input : 4~20mA)
Set ‘INP1 = AN5’ Set INP1(Level 3), 4~20mA : AN5
(Refer to ‘3. Linear Input H/W
‘SET 2.2 = 1’ Setting’)
In case of Linear input model,
(To activate the steps of ANL1 & The default is ‘SET2.2 = 1’
ANH1 )

Set ‘DP=0000’ DP : Decimal Point


Set Decimal point place

Define LSPL & USPL in Level 3 Assuming LSPL = 0, USPL = 3000

Input ‘Lower Limit signal’ In case of 4~20mA, input 4mA

Go to ‘ANL1’ step in Level 3

PV
Adjust SP, until ‘PV=LSPL’
Press ‘ ’ key, adjust ‘ANL1’
SP (In case of this, PV=0)

Input ‘Upper Limit signal’ In case of 4~20mA, input 20mA

Go to ‘ANH1’ step in Level 3

Adjust SP, until ‘PV=USPL’


PV
(In case of this, PV=3000)
Press ‘ ’ key, adjust ‘ANH1’
SP

No Check LSPL, USPL if right value


Check, ‘OK’ ?
(Input Lower/Upper Limit signal, Check)
Yes
END