MR Tarek Tawfeek Villa (AC Load Anlysis) (M.soliman)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Design Cooling and Heating Load Analysis Suppliers Cooling and Heating Load Analysis

Carrier
Selected Cooling Selected Heating Daikin Selected Daikin Selected LG Selected LG Selected Carrier Selected
Area Height Selected
Space Load Load Cooling Load Heating Load Cooling Load Heating Load Heating Load
(SQ.M) (M) Cooling Load
(KW) (KW) (KW) (KW) (KW) (KW) (KW)
(KW)
BS DRIVER&GUARD 25 4 5.3 5.6 3.2 (Under size) 4 (Under size) Missing Missing Missing Missing
BS GYM+LIVING+KITCHENETTE 70.5 4 14.0 14.0 7.8 (Under size 10 (Under size 8.8 (Under size) 8.8 (Under size) 8.8 (Under size) 9.1 (Under size)
BS HARD KITCHEN 34 4 7.0 6.9 9.8 (Over size) 12.5 (Over size) 7 8.2 7 6.9
BS LAUNDRY 16.5 4 3.5 3.7 Missing Missing Missing Missing Missing Missing
BS STORAGE +CLOAK ROOM STORAGE 27 4 5.3 5.6 6.2 (Over size) 8 (Over size) Missing Missing Missing Missing
BS GUEST ROOM 23 4 5.3 5.6 9.8 (Over size) 12.5 (Over size) Missing Missing Missing Missing
BS MAID ROOM 14.5 4 3.5 3.7 3.9 (Over size) 5 (Over size) 7 (Over size) 8.2 (Over size) 7 (Over size) 6.9 (Over size)
BS MAIN LOBBY 22 4 5.3 5.6 Missing Missing 5.3 6.1 Missing Missing
BS OFFICE+KITCHENTTE 31 4 7.0 6.9 7.9 (Over size) 10 (Over size) 8.8 (Over size) 8.8 (Over size) Missing Missing
GR BEDROOM1 27 4 5.3 5.6 9.8 (Over size) 12.5 (Over size) 7 (Over size) 8.2 (Over size) 7 (Over size) 6.9 (Over size)
GR BEDROOM3 37 4 7.0 6.9 9.8 (Over size) 12.5 (Over size) 8.8 (Over size) 8.8 (Over size) 8.8 (Over size) 9.1 (Over size)
GR BEDROOM2 27 4 5.3 5.6 9.8 (Over size) 12.5 (Over size) 8.8 (Over size) 8.8 (Over size) 8.8 (Over size) 9.1 (Over size)
GR MAIN LOBBY 51 4 8.8 9.1 14.1 (Over size) 18 (Over size) 7 (Under size) 8.2 (Under size) 8.8 9.1
GR KITCHENETTE AND DINNING 75 4 14.0 14.0 28.2 (Over size) 36 (Over size) 7 (Over size) 8.2 (Over size) Missing Missing
GR MASTER BEDROOM 26 4 5.3 5.6 9.8 (Over size) 12.5 (Over size) 7 (Over size) 8.2 (Over size) Missing Missing
GR HER DRESSING ROOM 17 4 3.5 3.7 Missing Missing 8.8 (Over size) 8.8 (Over size) 8.8 9.1
GR HIS DRESSING ROOM 20 4 3.5 3.7 Missing Missing 5.3 (Over size) 6.1 (Over size) Missing Missing
GR LIVING ROOM & SEATING AREA 83 4 17.6 18.2 7.9 (Under size) 10 (Under size) 7 (Under size) 8.2 (Under size) 12.2 (Under size) 11 (Under size)
Total Cost EGP - 1,395,000 391,450 256,000

Conclusion
1. VRV system (Daikin) is technically not applicable due to the oversizing of all system components which affects the cots of the system itself in addition to the electrical cost to feed it.
2. DX split units (LG and Carrier) are technically applicable as system. However, the selected units by the suppliers are oversized affects the cots of the system itself in addition to the electrical cost to feed it.
3. All suppliers are missing many spaces in the villa that shall be air conditioned during summer and winter either by mistake or by combining more than one space to be served by the same unit which will
affect the individual control of each space.
4. DX split units (LG and Carrier) are not considering the actual routes of refrigerant pipes allover the villa which will affect the cost.

Recommendations
1. All spaces in the villa shall be air conditioned through traditional DX split units on the basis of the estimated cooling and heating loads during the design stage after being coordinated with the architecture
and interior design. Both Carrier and LG and technically accepted in principal subject to comply with the final design package unit capcities and financial budget.
2. VRV system (Daikin) is not matching the cooling and heating load requirements of the different space in the villa. Moreover, the cost is overestimated for the villa application.