COLD WATER BOOSTER PUMP (Roof Majlis)

Project No :P1120800 Date: 27.10.09


Project : Majlis for HHS Ahmed @ Zabeel 2 .

COLD WATER BOOSTER PUMP


Item Water Flow Pump Head Speed Power Input Remark
1 ON Duty 3.3 L/s 30M 2900 Rpm 3 Kw,3ph
1 Assists 3.3 L/s 30M 2900 Rpm 3 Kw,3ph
1 ON Stand By 3.3 L/s 30M 2900 Rpm 3 Kw,3ph
Pressure Vessel 200 Lt Capacity

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
Elbow 65 0.065 0.00331663 3.3 0.0033 0.050458709217 1.2 0.06055 3 0.1816513532
NRV 65 0.065 0.00331663 3.3 0.0033 0.050458709217 131 0.082241361226036 1 0.0822413612
1
Valve 65 0.065 0.00331663 3.3 0.0033 0.050458709217 360 0.01089 1 0.010890000
Tee 65 0.065 0.00331663 3.3 0.0033 0.050458709217 0.5 0.025229 4 0.1009174184
Tee 50 0.05 0.0019625 2.65 0.00265 0.092933739757 0.5 0.046467 1 0.0464668699
2
Elbow 50 0.05 0.0019625 2.65 0.00265 0.092933739757 1.2 0.11152 3 0.3345614631
Tee 25 0.025 0.00049063 0.6 0.0006 0.076226178854 0.5 0.038113 3 0.1143392683
3
Elbow 25 0.025 0.00049063 0.6 0.0006 0.076226178854 1.2 0.091471 1 0.0914714146
Tee 15 0.015 0.00017663 0.3 0.0003 0.147041240073 0.5 0.073521 1 0.07352062
4
Valve 15 0.015 0.00017663 0.3 0.0003 0.147041240073 14 0.059510204081633 2 0.1190204082
1.155080177
2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 50 0.05 5 10.665 0.0033 2.53681E-05 10718.1791487 4.599E-07 0.274419
2 150 0.05 37 10.665 0.00265 1.68986E-05 10718.1791487 4.599E-07 1.352727
3 150 0.025 27 10.665 0.0006 1.07928E-06 10718.1791487 1.572E-08 1.844905
3.4721

1. Frict. Losses of Valve and Fitting = 1.16 M


2. Frict. Losses of Piping = 3.47 M
4.63 M
3. Safety Factor 20% 0.93
Sub Total 5.55 M
4. Atmosferic Press 10.00 M
Total 15.55

5.UV Sterlizer, line & Sand Filter 10.00


So Total Head required 25.55

NOTE:
K and Kv values are taken from PPR pipe supplier catalogue.
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v /2g = ( Q/A )2x1/2g
2

Formula used for ffriction loss in pipe = Hazen - Williams Equation


Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec

Calculated by: Mohammad Murshedul Islam Rubel


COLD WATER TRANSFER PUMP
Project No :P1120800 Date: 15/02/ 2010
Project :

COLD WATER TRANSFER PUMP


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 2.75 L/s 40M 2900 Rpm 3 Kw,3ph
1 Stand by 2.75 L/s 40 M 2900 Rpm 3 Kw,3ph

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
1 STAINER 50 0.05 0.0019625 2.75 0.00275 0.100079944025 68 0.211959342560554 1 0.2119593426
2 NRV 50 0.05 0.0019625 2.75 0.00275 0.100079944025 112.24 0.077799189599316 1 0.0777991896
3 GATE Valve 50 0.05 0.0019625 2.75 0.00275 0.100079944025 43.04 0.529085505313636 1 0.5290855053
4 Elbow 50 0.05 0.0019625 2.75 0.00275 0.100079944025 1.2 0.120096 10 1.2009593283
5 GATE Valve 50 0.05 0.0019625 2.75 0.00275 0.100079944025 43.04 0.529085505313636 1 0.5290855053
2.5488888711

2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 50 0.05 110 10.665 0.00275 1.80986E-05 10718.1791487 4.59921E-07 4.307188
4.3072

1. Static Head 12 M
2. Frict. Losses of Valve and Fittings = 2.55 M
3. Frict. Losses of Pipes = 4.31 M
4. Atmospheric pressure 10.00 M
x 28.86 M
3. Adding Safety Factor 20% 5.7712153
Total 34.63

So Total Head required 35.00

Available Head= 40 mtrs

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v2/2g = ( Q/A )2x1/2g
Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec
COLD WATER BOOSTER PUMP (SERVICE YARD)
Project No :P1120800 Date: 15/02/ 2010
Project :

COLD WATER BOOSTER PUMP (CWBP-3)


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 2.0 L/s 65 M 2900 Rpm 3.5 Kw,3ph
1 Stand by 2.0 L/s 65 M 2900 Rpm 3.5 Kw,3ph
Pressure Vessel 100 Litres Capacity

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
1 STAINER 76 0.076 0.00453416 2 0.002 0.00991670298 131 0.030208029835091 1 0.0302080298
2 GATE VALVE 76 0.076 0.00453416 2 0.002 0.00991670298 411.3 0.003064414960091 1 0.003064415
3 NRV 76 0.076 0.00453416 2 0.002 0.00991670298 254.05 0.008032053533389 1 0.0080320535
4 ELBOW 76 0.076 0.00453416 2 0.002 0.00991670298 1.2 0.0119 1 0.0119000436
5 ELBOW 76 0.076 0.00453416 2 0.002 0.00991670298 1.2 0.0119 1 0.0119000436
6 TEE 76 0.076 0.00453416 2 0.002 0.00991670298 0.5 0.004958 1 0.0049583515
7 GATEVALVE 76 0.076 0.00453416 2 0.002 0.00991670298 131 0.030208029835091 1 0.0302080298
8 GATEVALVE 76 0.076 0.00453416 2 0.002 0.00991670298 131 0.030208029835091 1 0.0302080298
9 TEE 76 0.076 0.00453416 2 0.002 0.00991670298 0.5 0.004958 1 0.0049583515
10 TEE 76 0.076 0.00453416 1.8 0.0018 0.008032529414 0.5 0.004016 1 0.0040162647
11 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
12 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
13 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
14 TEE 40 0.04 0.001256 1 0.001 0.032308866227 0.5 0.016154 1 0.0161544331
15 TEE 40 0.04 0.001256 1 0.001 0.032308866227 0.5 0.016154 1 0.0161544331
16 TEE 40 0.04 0.001256 0.8 0.0008 0.020677674385 0.5 0.010339 1 0.0103388372
17 ELBOW 25 0.025 0.000490625 0.5 0.0005 0.052934846426 1.2 0.063522 1 0.0635218157
18 TEE 25 0.025 0.000490625 0.5 0.0005 0.052934846426 0.5 0.026467 1 0.0264674232
19 GATEVALVE 25 0.025 0.000490625 0.5 0.0005 0.052934846426 65.69 0.007508384188539 1 0.0075083842
20 NRV 25 0.025 0.000490625 0.5 0.0005 0.052934846426 26.27 0.046948839820267 1 0.0469488398
21 STAINER 25 0.025 0.000490625 0.5 0.0005 0.052934846426 16.1 0.124995177655183 1 0.1249951777
22 GATEVALVE 32 0.032 0.00080384 0.5 0.0005 0.019719766984 116.23 0.002398327761527 1 0.0023983278
23 ELBOW 32 0.032 0.00080384 0.5 0.0005 0.019719766984 1.2 0.023664 1 0.0236637204
24 ELBOW 32 0.032 0.00080384 0.5 0.0005 0.019719766984 1.2 0.023664 1 0.0236637204
25 ELBOW 32 0.032 0.00080384 0.5 0.0005 0.019719766984 1.2 0.023664 1 0.0236637204
26 ELBOW 32 0.032 0.00080384 0.5 0.0005 0.019719766984 1.2 0.023664 1 0.0236637204
27 ELBOW 32 0.032 0.00080384 0.5 0.0005 0.019719766984 1.2 0.023664 1 0.0236637204
28 TEE 32 0.032 0.00080384 0.5 0.0005 0.019719766984 0.5 0.00986 1 0.0098598835
29 TEE 32 0.032 0.00080384 0.5 0.0005 0.019719766984 0.5 0.00986 1 0.0098598835
30 TEE 32 0.032 0.00080384 0.5 0.0005 0.019719766984 0.5 0.00986 1 0.0098598835
31 TEE 32 0.032 0.00080384 0.5 0.0005 0.019719766984 0.5 0.00986 1 0.0098598835
32 ELBOW 25 0.025 0.000490625 0.4 0.0004 0.033878301713 1.2 0.040654 1 0.0406539621
33 ELBOW 25 0.025 0.000490625 0.3 0.0003 0.019056544713 1.2 0.022868 1 0.0228678537
34 TEE 25 0.025 0.000490625 0.5 0.0005 0.052934846426 0.5 0.026467 1 0.0264674232
35 TEE 25 0.025 0.000490625 0.5 0.0005 0.052934846426 0.5 0.026467 1 0.0264674232
36 TEE 20 0.02 0.000314 0.5 0.0005 0.129235464908 0.5 0.064618 1 0.0646177325
37 ELBOW 15 0.015 0.000176625 0.2 0.0002 0.065351662255 1.2 0.078422 1 0.0784219947
38 GATEVALVE 15 0.015 0.000176625 0.2 0.0002 0.065351662255 21.32 0.011404876640771 1.2 0.078422 1 0.0784219947
39 ELBOW 15 0.015 0.000176625 0.1 0.0001 0.016337915564 1.2 0.019605 1 0.0196054987
40 ELBOW 15 0.015 0.000176625 0.1 0.0001 0.016337915564 1.2 0.019605 1 0.0196054987
1.1051407203
2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 76 0.076 8 10.665 0.002 1.00348E-05 10718.1791487 3.5354E-06 0.022594
2 150 40 0.04 122 10.665 0.0018 8.2559E-06 10718.1791487 1.5511E-07 6.461452
3 150 32 0.032 20 10.665 0.0005 7.70003E-07 10718.1791487 5.231E-08 0.292939
4 150 25 0.025 10 10.665 0.0005 7.70003E-07 10718.1791487 1.5717E-08 0.487491
5 150 20 0.02 2 10.665 0.0005 7.70003E-07 10718.1791487 5.3005E-09 0.289098
6 150 15 0.015 3 10.665 0.0002 1.41094E-07 10718.1791487 1.3054E-09 0.322647
7.8762

1. Static Head 8M
2. Frict. Losses of Valve and Fittings = 1.11 M
3. Frict. Losses of Pipes = 7.88 M
4. Atmospheric pressure 10.00 M
5. Pressure loss across the PRV (0.1 bar) = 1.00 M
6. Pressure loss across the calorifier (0.3 bar) = 3.00 M
7. Pressure at Remote Fixture 15M
M
Sub Total 45.98 M
3. Adding Safety Factor 20% 9.1962724
Total 55.18

So Total Head required 56.00 M

Available Head= 65mtrs

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v / 2g
2

Z = v2/2g = ( Q/A )2x1/2g


Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec
COLD WATER BOOSTER PUMP (SERVICE YARD)
Project No :P1120800 Date: 15/02/ 2010
Project :

COLD WATER BOOSTER PUMP (CWBP-2)


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 3.0 L/s 45 M 2900 Rpm 3.5 Kw,3ph
1 Stand by 3.0 L/s 45 M 2900 Rpm 3.5 Kw,3ph
Pressure Vessel 100 Lt Capacity

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
1 STAINER 76 0.076 0.00453416 2 0.002 0.00991670298 131 0.030208029835091 1 0.0302080298
2 GATE VALVE 76 0.076 0.00453416 2 0.002 0.00991670298 411.3 0.003064414960091 1 0.003064415
3 NRV 76 0.076 0.00453416 2 0.002 0.00991670298 254.05 0.008032053533389 1 0.0080320535
4 ELBOW 76 0.076 0.00453416 2 0.002 0.00991670298 1.2 0.0119 1 0.0119000436
5 ELBOW 76 0.076 0.00453416 2 0.002 0.00991670298 1.2 0.0119 1 0.0119000436
6 TEE 76 0.076 0.00453416 2 0.002 0.00991670298 0.5 0.004958 1 0.0049583515
7 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
8 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
9 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
10 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
11 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
12 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
13 ELBOW 40 0.04 0.001256 1 0.001 0.032308866227 1.2 0.038771 1 0.0387706395
14 TEE 40 0.04 0.001256 1 0.001 0.032308866227 0.5 0.016154 1 0.0161544331
15 TEE 40 0.04 0.001256 1 0.001 0.032308866227 0.5 0.016154 1 0.0161544331
16 TEE 32 0.032 0.00080384 0.8 0.0008 0.05048260348 0.5 0.025241 1 0.0252413017
17 TEE 32 0.032 0.00080384 0.8 0.0008 0.05048260348 0.5 0.025241 1 0.0252413017
18 ELBOW 25 0.025 0.000490625 0.4 0.0004 0.033878301713 1.2 0.040654 1 0.0406539621
19 ELBOW 25 0.025 0.000490625 0.4 0.0004 0.033878301713 1.2 0.040654 1 0.0406539621
20 TEE 25 0.025 0.000490625 0.4 0.0004 0.033878301713 0.5 0.016939 1 0.0169391509
21 TEE 25 0.025 0.000490625 0.4 0.0004 0.033878301713 0.5 0.016939 1 0.0169391509
22 TEE 20 0.02 0.000314 0.3 0.0003 0.046524767367 0.5 0.023262 1 0.0232623837
23 TEE 20 0.02 0.000314 0.3 0.0003 0.046524767367 0.5 0.023262 1 0.0232623837
24 ELBOW 15 0.015 0.000176625 0.2 0.0002 0.065351662255 1.2 0.078422 1 0.0784219947
25 GATE VALVE 15 0.015 0.000176625 0.2 0.0002 0.065351662255 21.32 0.011404876640771 1 0.0114048766
26 ELBOW 15 0.015 0.000176625 0.1 0.0001 0.016337915564 1.2 0.019605 1 0.0196054987
27 ELBOW 15 0.015 0.000176625 0.1 0.0001 0.016337915564 1.2 0.019605 1 0.0196054987

0.7149977449

2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 76 0.076 8 10.665 0.003 2.12632E-05 10718.1791487 3.5354E-06 0.047876
2 150 40 0.04 150 10.665 0.001 2.779713E-06 10718.1791487 1.5511E-07 2.674834
3 150 32 0.032 5 10.665 0.0008 1.83875E-06 10718.1791487 5.231E-08 0.174883
4 150 25 0.025 10 10.665 0.0004 5.093486E-07 10718.1791487 1.5717E-08 0.32247
5 150 20 0.02 2 10.665 0.0003 2.989707E-07
6 150 15 0.015 3 10.665 0.0002 1.410937E-07 10718.1791487 1.3054E-09 0.322647
0.1749
1. Static Head 8
M
2. Frict. Losses of Valve and Fittings = 0.71M
3. Frict. Losses of Pipes = 0.17M
4. Atmospheric pressure 10.00M
7. Pressure at Remote Fixture 15.00
M
M
Sub Total 33.89 M
3. Adding Safety Factor 20% 6.7779761
Total 40.67

So Total Head required 41.00 M

Available Head= 45mtrs

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v2/2g = ( Q/A )2x1/2g
Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec
COLD WATER BOOSTER PUMP (Majlis ROOF)
Project No :P1120800 Date: 15/02/ 2010
Project :

COLD WATER BOOSTER PUMP (CWBP-1)


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 3.3 L/s 30 M 2900 Rpm 3 Kw,3ph
1 Assist 3.3 L/s 30 M 2901 Rpm 4 Kw,3ph
1 Stand by 3.3 L/s 30 M 2900 Rpm 3 Kw,3ph

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
1 STAINER 65 0.065 0.003316625 3.3 0.0033 0.050458709217 91 0.170431590387634 1 0.1704315904
2 GATE VALVE 65 0.065 0.003316625 3.3 0.0033 0.050458709217 411.3 0.008342869728847 1 0.0083428697
3 NRV 65 0.065 0.003316625 3.3 0.0033 0.050458709217 164.53 0.052136597587194 1 0.0521365976
4 TEE 50 0.05 0.0019625 3.3 0.0033 0.144115119396 0.5 0.072058 1 0.0720575597
5 TEE 50 0.05 0.0019625 3.3 0.0033 0.144115119396 0.5 0.072058 1 0.0720575597
6 TEE 50 0.05 0.0019625 2.3 0.0023 0.070006334399 0.5 0.035003 1 0.0350031672
7 ELBOW 50 0.05 0.0019625 1.8 0.0018 0.042877225605 1.2 0.051453 1 0.0514526707
8 TEE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 0.5 0.021439 1 0.0214386128
9 GATE VALVE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 280.6 0.005333038001757 1 0.005333038
10 TEE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 0.5 0.021439 1 0.0214386128
11 ELBOW 50 0.05 0.0019625 1.8 0.0018 0.042877225605 1.2 0.051453 1 0.0514526707
12 TEE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 0.5 0.021439 1 0.0214386128
13 ELBOW 50 0.05 0.0019625 1.8 0.0018 0.042877225605 1.2 0.051453 1 0.0514526707
14 ELBOW 50 0.05 0.0019625 1.8 0.0018 0.042877225605 1.2 0.051453 1 0.0514526707
15 TEE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 0.5 0.021439 1 0.0214386128
16 GATE VALVE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 280.6 0.005333038001757 1 0.005333038
17 TEE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 0.5 0.021439 1 0.0214386128
18 GATE VALVE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 280.6 0.005333038001757 1 0.005333038
19 TEE 50 0.05 0.0019625 1.8 0.0018 0.042877225605 0.5 0.021439 1 0.0214386128
20 TEE 50 0.05 0.0019625 1.2 0.0012 0.019056544713 0.5 0.009528 1 0.0095282724
20 TEE 40 0.04 0.001256 0.6 0.0006 0.011631191842 0.5 0.005816 1 0.0058155959
21 ELBOW 32 0.032 0.00080384 0.35 0.00035 0.009662685822 1.2 0.011595 1 0.011595223
22 TEE 32 0.032 0.00080384 0.35 0.00035 0.009662685822 0.5 0.004831 1 0.0048313429
23 ELBOW 22 0.022 0.00037994 0.15 0.00015 0.00794426053 1.2 0.009533 1 0.0095331126
24 ELBOW 22 0.022 0.00037994 0.15 0.00015 0.00794426053 1.2 0.009533 1 0.0095331126
25 ELBOW 22 0.022 0.00037994 0.15 0.00015 0.00794426053 1.2 0.009533 1 0.0095331126
26 ELBOW 22 0.022 0.00037994 0.15 0.00015 0.00794426053 1.2 0.009533 1 0.0095331126
27 GBV 22 0.022 0.00037994 0.15 0.00015 0.00794426053 5.96 0.08209089680645 1 0.0820908968
28 TEE 22 0.022 0.00037994 0.15 0.00015 0.00794426053 0.5 0.003972 1 0.0039721303
29 TEE 22 0.022 0.00037994 0.15 0.00015 0.00794426053 0.5 0.003972 1 0.0039721303
30 TEE 22 0.022 0.00037994 0.1 0.0001 0.003530782458 0.5 0.001765 1 0.0017653912
31 ELBOW 15 0.015 0.000176625 0.008 8E-06 0.00010456266 1.2 0.000125 1 0.0001254752

0.9222997265
2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 65 0.065 2 10.665 0.0033 2.53681E-05 10718.1791487 1.6508E-06 0.030581
2 150 50 0.05 65 10.665 0.0033 2.53681E-05 10718.1791487 4.5992E-07 3.567452
3 150 32 0.032 20 10.665 0.00035 3.97754E-07 10718.1791487 5.231E-08 0.151321
5 150 22 0.022 32 10.665 0.00015 8.28173E-08
6 150 15 0.015 2 10.665 8E-05 2.58537E-08 10718.1791487 1.3054E-09 0.039414
0.1513

1. Static Head NA M
2. Frict. Losses of Valve and Fittings = 0.92 M
3. Frict. Losses of Pipes = 0.15 M
5. Pressure loss across the Softner and UV (1 bar) = 10.00 M
7. Pressure at Remote Fixture 15.00 M
M
Sub Total 26.07
Negative Head Available 2.00 M
Total Head Required 24.07
Adding Safety Factor 20% 4.8147241

Total 28.89

So Total Head required 29.00 M

Available Head= 30 mtrs

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v2/2g = ( Q/A )2x1/2g
Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec
HOT WATER CIRCULATION PUMP (MAJLIS PLANT ROOM)
Project No :P1120800 Date: 15/02/ 2010
Project :

HOT WATER CIRCULATION PUMP (HWCP-1)


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 0.23 L/s 7.5 M 2900 Rpm 0.5 Kw
1 Stand by 0.23 L/s 7.5 M 2900 Rpm 0.5 Kw

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
1 STAINER 40 0.04 0.001256 0.23 0.00023 0.001709139023 33 0.006295537190083 1 0.0062955372
2 NRV 40 0.04 0.001256 0.23 0.00023 0.001709139023 64.77 0.001634228873994 1 0.0016342289
3 GATE Valve 40 0.04 0.001256 0.23 0.00023 0.001709139023 161.93 0.000261460472579 1 0.0002614605
4 Elbow 40 0.04 0.001256 0.23 0.00023 0.001709139023 1.2 0.002051 10 0.0205096683
4 Elbow 40 0.04 0.001256 0.23 0.00023 0.001709139023 1.2 0.002051 10 0.0205096683
4 Elbow 40 0.04 0.001256 0.23 0.00023 0.001709139023 1.2 0.002051 10 0.0205096683
6 TEE 40 0.04 0.001256 0.23 0.00023 0.001709139023 0.5 0.000855 1 0.0008545695
4 Elbow 25 0.025 0.000490625 0.115 0.000115 0.002800253376 1.2 0.00336 10 0.0336030405
5 GATE Valve 25 0.025 0.000490625 0.115 0.000115 0.002800253376 65.59 0.000398405587329 1 0.0003984056
0.104576247

2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 40 0.04 4 10.665 0.00275 1.80986E-05 10718.1791487 1.55108E-07 0.464419
1 150 25 0.025 1.5 10.665 0.00275 1.80986E-05 10718.1791487 1.571686E-08 1.718737
2.183156

1. Static Head 2 M
2. Frict. Losses of Valve and Fittings = 0.10 M
3. Frict. Losses of Pipes = 2.18 M
4.29 M
3. Adding Safety Factor 20% 0.8575464
Total 5.15

So Total Head required 5.5 M

Available Head= 7.5 mtrs

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v2/2g = ( Q/A )2x1/2g
Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec
HOT WATER CIRCULATION PUMP (Guest villa /Gym)
Project No :P1120800 Date: 15/02/ 2010
Project :

HOT WATER CIRCULATION PUMP (HWCP-2)


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 0.2 L/s 4M 2900 Rpm 0.5 Kw
1 Stand by 0.2 L/s 4M 2900 Rpm 0.5 Kw

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
1 STAINER 40 0.04 0.001256 0.2 0.0002 0.001292354649 33 0.004760330578512 1 0.0047603306
2 NRV 40 0.04 0.001256 0.2 0.0002 0.001292354649 64.77 0.001235711813984 1 0.0012357118
3 GATE Valve 40 0.04 0.001256 0.2 0.0002 0.001292354649 161.93 0.000197701680589 1 0.0001977017
4 Elbow 40 0.04 0.001256 0.2 0.0002 0.001292354649 1.2 0.001551 10 0.0155082558
4 Elbow 40 0.04 0.001256 0.2 0.0002 0.001292354649 1.2 0.001551 10 0.0155082558
6 TEE 40 0.04 0.001256 0.2 0.0002 0.001292354649 0.5 0.000646 1 0.0006461773
4 Elbow 25 0.025 0.000490625 0.1 0.0001 0.002117393857 1.2 0.002541 10 0.0254087263
5 GATE Valve 25 0.025 0.000490625 0.1 0.0001 0.002117393857 65.59 0.000301251861875 1 0.0003012519
0.0635664111

2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 40 0.04 3 10.665 0.002 1.00348E-05 10718.1791487 1.55108E-07 0.193123
1 150 25 0.025 2 10.665 0.001 2.77971E-06 10718.1791487 1.571686E-08 0.351969
0.545092

1. Static Head 1.5 M


2. Frict. Losses of Valve and Fittings = 0.06 M
3. Frict. Losses of Pipes = 0.55 M
2.11 M
3. Adding Safety Factor 20% 0.4217317
Total 2.53

So Total Head required 3 M

Available Head= 4 mtrs

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v2/2g = ( Q/A )2x1/2g
Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec
COLD WATER CIRCULATION PUMP (MAJLIS ROOF)
Project No :P1120800 Date: 15/02/ 2010
Project :

COLD WATER CIRCULATION PUMP (CWCP-1)


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 0.3 L/s 7.5 M 2900 Rpm 0.5 Kw
1 Stand by 0.3 L/s 7.5 M 2900 Rpm 0.5 Kw

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
1 STAINER 40 0.04 0.001256 0.3 0.0003 0.00290779796 33 0.010710743801653 1 0.0107107438
2 NRV 40 0.04 0.001256 0.3 0.0003 0.00290779796 64.77 0.002780351581464 1 0.0027803516
3 GATE Valve 40 0.04 0.001256 0.3 0.0003 0.00290779796 161.93 0.000444828781325 1 0.0004448288
4 Elbow 40 0.04 0.001256 0.3 0.0003 0.00290779796 1.2 0.003489 10 0.0348935755
4 Elbow 40 0.04 0.001256 0.3 0.0003 0.00290779796 1.2 0.003489 10 0.0348935755
6 TEE 40 0.04 0.001256 0.3 0.0003 0.00290779796 0.5 0.001454 1 0.001453899
4 Elbow 40 0.04 0.001256 0.3 0.0003 0.00290779796 1.2 0.003489 10 0.0348935755
3 GATE Valve 40 0.04 0.001256 0.3 0.0003 0.00290779796 161.93 0.000444828781325 1 0.0004448288
0.1205153785

2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 40 0.04 8 10.665 0.003 2.12632E-05 10718.1791487 1.55108E-07 1.09125
1.09125

1. Static Head 2 M
2. Frict. Losses of Valve and Fittings = 0.12 M
3. Frict. Losses of Pipes = 1.09 M
3.21 M
3. Adding Safety Factor 20% 0.642353
Total 3.85

So Total Head required 4.0 M

Available Head= 7.5mtrs

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v2/2g = ( Q/A )2x1/2g
Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec
COOL COLD WATER SECONDARY CIRCUIT PUMP (MAJLIS ROOF)
Project No :P1120800 Date: 15/02/ 2010
Project :

COOL COLD WATER SECONDARY CIRCUIT PUMP (CWCP-1)


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 0.25 L/s 5M 2900 Rpm 0.3 Kw
1 Stand by 0.25 L/s 5M 2900 Rpm 0.3 Kw

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
1 STAINER 40 0.04 0.001256 0.25 0.00025 0.002019304139 33 0.007438016528926 1 0.0074380165
2 NRV 40 0.04 0.001256 0.25 0.00025 0.002019304139 64.77 0.00193079970935 1 0.0019307997
3 GATE Valve 40 0.04 0.001256 0.25 0.00025 0.002019304139 161.93 0.00030890887592 1 0.0003089089
4 Elbow 40 0.04 0.001256 0.25 0.00025 0.002019304139 1.2 0.002423 10 0.0242316497
6 TEE 40 0.04 0.001256 0.25 0.00025 0.002019304139 0.5 0.00101 1 0.0010096521
4 Elbow 40 0.04 0.001256 0.25 0.00025 0.002019304139 1.2 0.002423 10 0.0242316497
6 TEE 40 0.04 0.001256 0.25 0.00025 0.002019304139 0.5 0.00101 1 0.0010096521
4 Elbow 25 0.025 0.000490625 0.125 0.000125 0.003308427902 1.2 0.00397 10 0.0397011348
4 Elbow 25 0.025 0.000490625 0.125 0.000125 0.003308427902 1.2 0.00397 10 0.0397011348
5 GATE Valve 25 0.025 0.000490625 0.125 0.000125 0.003308427902 65.59 0.000470706034179 1 0.000470706
0.1400333043

2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 40 0.04 7 10.665 0.0025 1.517E-05 10718.1791487 1.55108E-07 0.681222
1 150 25 0.025 3 10.665 0.00125 4.20221E-06 10718.1791487 1.57169E-08 0.798128

1. Static Head 2 M
2. Frict. Losses of Valve and Fittings = 0.14 M
3. Frict. Losses of Pipes = 0.80 M
2.94 M
3. Adding Safety Factor 20% 0.5876323
Total 3.53

So Total Head required 3.5 M

Available Head= 5 mtrs

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v2/2g = ( Q/A )2x1/2g
Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec
SUBMERSIBLE PUMP (EXTERNAL)
Project No :P1120800 Date: 15/02/ 2010
Project :

SUBMERSIBLE PUMP (SP-1)


Item Water Flow Pump Head Speed Power Input Remark
1 Duty 4.0 L/s 17.5 M 2900 Rpm 3.5 Kw,3ph
1 Stand by 4.0 L/s 17.5 M 2900 Rpm 3.5 Kw,3ph

Head Loss calculation :

1. Loss of head due to friction in fittings

Friction Losses of Valve & fittings as per drawing


No Item Size ( mm ) Size ( m ) A ( M2 ) Q( L/ S ) Q( M3/S ) Z Kv values Hf= (36 Q/ Kv)^2*0.1 K Hf =KxZ Qty Total Hf ( M )
4 ELBOW 76 0.076 0.00453416 2 0.002 0.00991670298 1.2 0.0119 1 0.0119000436
3 NRV 76 0.076 0.00453416 2 0.002 0.00991670298 254.05 0.008032053533389 1 0.0080320535
2 SV 76 0.076 0.00453416 2 0.002 0.00991670298 411.3 0.003064414960091 1 0.003064415
4 ELBOW 76 0.076 0.00453416 2 0.002 0.00991670298 1.2 0.0119 1 0.0119000436

0.0149644585

2. Loss of head due to friction in pipe:

Friction Losses of pipe length as per drawing


S.L C Pipe size D,(m) L,(m) Constant Q (m3/sec) Q^1.852 C^1.852 D^4.871 Hf
1 150 76 0.076 6 10.665 0.003 2.12632E-05 10718.1791487 3.5354E-06 0.035907
0.0359

1. Static Head 4.5M


2. Frict. Losses of Valve and Fittings = 0.01 M
3. Frict. Losses of Pipes = 0.04 M
4. Atmospheric pressure 10.00 M
M
Sub Total 14.55 M
3. Adding Safety Factor 20% 2.9101743
Total 17.46

So Total Head required 17.50 M

Available Head= 17.5

NOTE:
Formula used for valves & strainer loss = Hazen - Williams Equation
Hf = (36 Q/ Kv)^2
Formula used for fittings loss = Hazen - Williams Equation
Hf = K.v2/ 2g
Z = v2/2g = ( Q/A )2x1/2g
Formula used for ffriction loss in pipe = Hazen - Williams Equation
Hf = ( 10.665 X L X Q^1.852)/( C^1.852 X D^4.871)

Where,

v = Velocity of water in m/sec


g = Acceleration due to gravity ( 9.81 m/sec2)
K = Fittings loss co efficient, ASHRE book.
Kv= Valve Coefficient = CRANE Valves.
D = Diameter of pipe in m
L = Length of pipe, m
C = hazen-williams roughness coefficient, ( for PPR,Upvc pipes,C = 150, dimensionless)
Q = Flow of water , m3/sec