Professional Documents
Culture Documents
Windmason Technical Specification
Windmason Technical Specification
SPECIFICATIONS SHEET:
A. Product Options: Drawings indicate size, profiles, and dimensional requirements of air‐
to‐air fresh air handling units and are based on the specific system indicated.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA
70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked
for intended use.
Windmason units are tested & designed to comply with the following standards:
1
Unit Capacity : 25 RT
IDEC - Indirect / Direct Evaporative Cooling
Model : ID-10KC
General Specifications
Brand : Supercool
Technical Specifications and data
Cooling Capacity : 25 TR ‐ Nominal
Air Flow : 10000 CFM
EXT. Static Press. 250 Pas.
Input Power : 7 kW
Current : 13 A ‐ 380v/3ph
Power Supply : 220v‐380v/3ph/60hz
Physical Dimensions : 3200 x 2000 x 1920 mm (L x W x H)
Operating Weight : 1500 kg
Net Weight : 1200 kg
Water Consumption : 230 l/h
Supply Air Temp. : Minimum temp. 13° C Maximum temp. 18° C
Weather Conditions : DBT: 46.1° C ‐ WBT : 19.6° C (Riyadh Weather)
Water tank : Fiberglass
Wet areas sides : Fiberglass
Heat Exchanger : Copper tube, Alu fins
Main blowing fan : Backward curve impeller
Cooling tower fan : ABS Cooling tower fan with water proof motor
Air filters : 20 mm Aluminum filter
2
IDEC - Indirect / Direct Evaporative Cooling Unit Capacity : 25 RT
Control panel
Control kit 2-stage IDEC unit control kit
Room temprature control Thermostat
Dry running protection Water Level switch with No water display
Auto drain Adjustable timer Auto drain pump
Hot / Dusty air protection Auto time delay to protect hot air to the room
Room temperature set point Room temperature set point manual adjustable control
3
Indirect / Direct Evaporative Cooling Unit Capacity : 25 RT
Specifications Model : ID-10KC
Indirect water evaporation Stage
Cooling Media Air to Water Heat Exchanger
Heat Exchanger Type Fins & Tube Coil
Overall stage effcincy % 70%
Air in Temp. DB-WB, C 46.1 - 19.6 C (Riyadh weather)
Air out Temp. DB-WB, C 31 - 21 C
45 C in 17 C out
4
IDEC - Indirect / Direct Evaporative Cooling Unit Capacity : 25 RT
Specifications Model : ID-10KC
Primary Fan
Blow through, dry running long life backward impeller fan with direct coupled synchronous motor. The
fan has been mechanically isolated from the main unit frame to avoid transferring of vibrations.
Stepless variable speed DC inverter with Auto temperature control and BMS data outlets has been
provided to control the fan RPM.
A metal guard has been provided on the air inlet to avoid high pressure air suction hazards.
5
Indirect / Direct Evaporative Cooling Unit Capacity : 25 RT
6
FRONT VIEW