Report Date 15,03,2021

Report Number AP 120-21


Sample Date 15,03,2021
PO Number
WATER ANALYSIS REPORT

Project/Location Mayan Yas Island Living Circuit

Contractor/Client ELMACS/ CHOICES

Water Source Chilled Water


Flushing Stage After Passivation
Secondary Line

Main Header near


Parameters unit Control Parameters
Exchanger
(Building return side)
Electrical Conductivity 2850 µS/cm < 3000
pH 10.6 - 8.5–10.5
Suspended Solids (TSS) 6 mg/l < 10
Iron (Fe) 0.29 mg/l < 1.0
Sodium Nitrite (NaNO2) 1320 mg/l >800
Benzotriazole 22 mg/l > 10

“Without any liability on Cooltech for the process completed and/or for any process to be done further.”

Remarks:
 Sample is collected by customer.

 All the tested parameters are in the normal acceptable limits.


Recommendation:
 This report is valid for 48 hours only and maintain the circulation throughout this time.
 Water Samples complies with Cooltech Quality Standards for Final Treatment, and can be used in district cooling
systems.
 The chilled water system must keep under circulation all the time

Prepared By:
Ayub Parambil – CooltechGulf
Service Engineer WQS

CoolTech Energy Water Treatment (L.L.C)


P.O. Box: 49965, Dubai, UAE

Tel: +971 2 5501182

Fax: +971 2 5504878


E-mail: info@cooltechgulf.com www.cooltechgulf.com