Contents
17.5kV VCB for generator
•Rating · ····································································
03
•Structure · ·······························································
04
•Accessories ···························································
04
•Dimensions ····························································
05
•Control circuit diagram ········································
07
•Ordering information ············································
08
•Comparison of distribution breaker and
generator breaker ················································
09
17.5kV VCB for generator
Features
● Rating: 17.5kV 50kA 5000A(Fixed), 4000A(Withdrawable), 50/60Hz
● Maximum interrupting times: 5 cycle
● Rated short-time withstand current: 50kA/4sec
● Rated operating sequence: CO-30min-CO (Short circuit)
O-3min-CO-3min-CO (Load switching)
● S
hort-circuit current
- System-source fault: 50kA
- Generator-source fault: 25kA P Type (Fixed)
● O
ut-of-phase current switching capability: 25kA
● N
o-load mechanical endurance capability: 10,000 operations
● C
ontrol voltage
AC/DC 48V, AC/DC 110V, DC 125V, AC/DC 220V
● V
arious accessories
- VCB part: UVT, Latch Checking S/W, Position S/W, Locking Magnet,
Plug Interlock
- Others: Draw-in/out handle, Lifting hook, UVT Time Delay Controller
Rating
Type VH-17P50D50 VH-17H50D40
Rated voltage Ur (kV) 17.5
Rated normal current Ir (A) 5000A 4000A
Phase distance (mm) 275
Breaker weight (kg) 385 395
Cradle (H Type) weight (kg) - 180
Rated frequency fr (Hz) 50/60
Rated short-circuit current Ik (kA) 50
Rated short-circuit breaking capacity (MVA) 1520
Rated short-time withstand current Ik/tk (kA/s) 50kA/4s
Rated short-circuit making current Ip (kA) 137
Maximum interrupting times (cycle) 5
Rated withstand Power frequency Ud (kV) 50
voltage Impulse Up (kV/1.2×50㎲) 110
Rated operating Short circuit current CO-30min-CO
sequence Load switching current O-3min-CO-3min-CO
Closing coil (V) DC 48, 110, 125, 220 AC 48, 110, 220
Control voltage
Trip coil (V) DC 48, 110, 125, 220 AC 48, 110, 220
Auxiliary contacts 4a4b, 10a10b
Rated opening time (s) ≤ 0.04
No-load closing time (s) ≤ 0.06
Motor operating current (A) ≤ 5 (7:AC/DC48V)
Closing control current (A) ≤ 5 (7:AC/DC48V)
Trip control current (A) ≤ 5 (7:AC/DC48V)
Motor charging time (s) ≤ 12
Generator-source-fault currents (kA) 25
Out-of-phase current switching capability (kA) 25
No. of mechanical enduramce (ops.) 10,000
Installation type P Type (Fixed) H Type (Withdrawable)
Standards IEC/IEEE 62271-37-013:2015
I3
Structure
Fixed electrode
Movable electrode
Breaker (VI)
Accessories
[Ha Cradle]
Breaker Cradle
M otor(M) Latch checking S/W Locking magnet Handle for draw-in and out M
OC (Mechanism operating cell S/W)
AC/DC Coil rectifier Auxiliary contact wire Plug interlock UVT time delay controller TOC (Truck operating cell S/W)
Trip
coil/Closing coil K
eylock Wireless Temp. CTD Earthing S/W & Accessary
Secondary trip coil Button cover/Push bar monitoring sensor
UVT rectifier Button padlock Lifting hook
UVT Position S/W Charge handle
4I
Dimensions
90 4-M12 DP24
77.5
Heli Coil Tap
177.5
286.5
90
573.5
631.6
330
821.3
606
Ø170
286.5
400
994
949
421
864
906 385 150
980 631.6
904
275 275
648.8
702
463.8
554.5
380
Ø164.6
864 343.5
400
Ø120
1002.5
979
451
131.5
Ø19.5
10.3 410 40
22
23.5
906 472.8
53.7 512.8
599.5
I5
Dimensions
275 275
50 M12
50
275
960.6
400
275
180 500 410.8 6-Ø14
(Mounting hole)
Ø120
400
1485
1485
752.5
261.3
20.3 1030.8
1000
1150.8
1183.5
6I
Closing coil monitoring contact Trip coil monitoring contact
Note2)
Note5)
Note1)
Control circuit diagram
Note3)
Note4)
I7
Ordering information
VH 17 H 50 D 40
Basic del name Rated voltage (kV) Version Interrupting current (kA) Phase distance/Compatibility Rated current (A)
VH VH Mecha 17 17.5 P Fixed 50 50 D 275 40 4000
H MCSG type withdrawable 50 5000 (Fixed)
VCL 17 H 50 D 40 A12
Basic model name Rated voltage (kV) Interrupting current (kA) Rated current (A) Other accessories
VCL Susol VCB Cradle 17 17.5 50 50 40 4000 A1 ES(Earthing Switch) without option
ES(Earthing Switch) with
A3
Position S/W (4a4b)
A5 ES(Earthing Switch) with Keylock
AF TOC
Version Phase distance/Compatibility AG MOC
Ha MCSG Cradle type D 275
8I
Comparison of distribution breaker and generator breaker
AA BB
TRTR CB
CB Load
Load
Gen.
Gen. CB
CB TRTR Grid
Grid
~~
Power frequency
38kV @17.5kV 50kV @17.5kV
withstand voltage
Note1) RRRV (Rate of rise of recovery voltage): Indicates the slope of the transient recovery voltage.