Download as pdf or txt
Download as pdf or txt
You are on page 1of 34

NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

NFPA 1981 to connect a Buddy Breath system MSA to Scott, or Survive Air to
Interspiro.
(Log #21) This problem arises in the instance of a down fire fighter and a
1981- 1 - (Entire Document): Accept in Principle rescue is required. All I am asking is for a requirement for high
SUBMITTER: Kurt Collins, Westbrook Fire Department pressure to high pressure and low pressure to low pressure. With
RECOMMENDATION: Revise NFPA 1981 to add a new requirement every manufacturer having different systems we as rescuers have
for an alarm or alert for the user that signals the SCBA cylinder problems rescuing ourselves. Now what’s making it harder is the
pressure/capacity has been depleted to half capacity. This same manufacturers have two different systems.
alert/alarm is in addition to end-of-service-time alarms already COMMITTEE ACTION: Reject.
required. COMMITTEE STATEMENT: Regulator intermediate pressure stages
SUBSTANTIATION: This most recent incident in Worcester has operate on different variations in pressure, not just 2216 and 4500
lead me to believe that we are not thinking properly when it comes to SCBA that are low or high pressure systems.
SCBA. NIOSH does not permit buddy breathing (two persons breathing
Think about it; currently when our alarms go off it is telling us to get from one system). Using SCBA in this manner voids NIOSH approval
out, it took 15 minutes to get where you are and have 5 to 7 minutes and causes the users to be using the SCBA in an unapproved manner.
of air remaining. That math does not add up and that’s what is 1910.156 requires SCBA to be NIOSH approved. NFPA 1500 requires
wrong. SCBA to be compliant with NFPA 1981, and 1981 requires NIOSH
Fire fighters usually are unable to see and read the cylinder pressure approval. Use of EEBSS voids the NIOSH approval. RIC can use
gauge or too busy to think to do it. It shouldn’t be necessary for them other methods for rescue of trapped fire fighters. NIOSH letters in
to read the gauge just as it isn’t necessary for them to do it to tell they effect.
are nearly out of air, the alarm is automatic. ___________________
We need to think about what the notification is for. Time to think
out of the box! (Log #9)
Please reference Fire Engineering, October 1999 issue, on page 99. 1981- 4 - (4-2.5 (New) ): Accept in Principle
I think that helps. We need things to help us stay in the right frame SUBMITTER: Karen E. Strumlock, Intertek Testing Services
of mind and right track and sometimes need to be told to change RECOMMENDATION: Add new paragraph 4-2.5:
tracks because this one is about to end. Where is the point of no “The design of this end-of service-time indicator shall be such that
return? According to current standards, about 1/4 of an air cylinder the wearer of the SCBA can sense the signals.”
ago and we don’t even recognize it. SUBSTANTIATION: The design/location on the EOSTI should be
COMMITTEE ACTION: Accept in Principle. such that the wearer can sense the signal regardless of the location.
See Section 4.3 in Committee Proposal 1981-24 (Log #CP2). We want to avoid signals like a light on the back of the unit or a
COMMITTEE STATEMENT: The committee provided text to whistle that only animals can hear.
include the submitter’s recommendation for an alert of the breathing COMMITTEE ACTION: Accept in Principle.
air cylinder capacity reaching half capacity. COMMITTEE STATEMENT: See Chapters 4, 5, and 6 in Committee
Proposal 1981-24 (Log #CP2) for the new text on EOSTI.
___________________
___________________
(Log #22)
1981- 2 - (Entire Document): Accept in Principle (Log #20)
SUBMITTER: Dave Tibbetts, New Orleans Fire Department 1981- 5 - (5-12 and 6-12 (New) ): Accept
RECOMMENDATION: Revise text to read so that “voice SUBMITTER: Karen E. Strumlock, Intertek Testing Services
amplification” be incorporated in SCBA facepieces. RECOMMENDATION: Add new paragraphs 5-12 and 6-12 to read as
SUBSTANTIATION: A problem exists in communicating through follows:
SCBA facepieces. Fire fighters in New Orleans have used voice 5-12 Redundant End of Service Time Indicator Performance.
amplifiers on a trial basis with great results. Communications is 5-12.1 SCBA shall be tested for airflow resistance as specified in
always a basic problem on the fire ground. Section 6-12, Redundant End of Service Time Indicator Airflow Test,
COMMITTEE ACTION: Accept in Principle. and the SCBA facepiece pressure shall not be less than 0.00 in. (0.00
Revise text as follows: mm) water column and shall not be greater than 3 1/2 in. (89 mm)
6.10.7: (see 6.10.5.2 in Committee Proposal 1981-24 (Log #CP2). water column above ambient pressure from the time the test begins
Change “65-75 dBA” to “75-85 dBA.” until the time the test is concluded.
6.10.9: (see 6.10.4.6 in Committee Proposal 1981-24 (Log #CP2). 5-12.2 After actuation of the unblocked end of service time
Change “60 dB ± 2dB” to “70 dB.” indicator, the indicator shall remain activated for a minimum of 30
COMMITTEE STATEMENT: The submitter and the Committee did cycles of the breathing machine.
not have criteria for what “voice amplification” is, what pass/fail 6-12 Redundant End of Service Time Indicator Test.
requirements should be, and what is the appropriate test method for 6-12.1 This test shall apply to all end of service time indicators
evaluation. The Technical Committee agrees with the submitter that required by Section 4-2.
improved clarity of speech through the facepiece is needed and 6-12.2 One of the end of service time indicator sensing mechanisms
proposed the changes to the communications test to make the test shall be blocked so as to simulate a failure of the end of service time
more demanding. indicator’s sensing mechanism. The blocking method shall be
determined by the testing organization and the manufacturer.
___________________ 6-12.3 With the sensing mechanism blocked as indicated in 6-12.2,
(Log #3) the airflow test in Section 6-1 shall be performed.
1981- 3 - (2-1): Reject 6-12.4 This test shall be repeated for each of the independent end
SUBMITTER: Chris Heger, Liberty Twp. Fire Dept., OH of service time indicators.
RECOMMENDATION: Add new text: SUBSTANTIATION: New performance requirements and test
“Requirement for all Buddy Breath connections to have the same method for performance verification testing of redundant end of
connection no matter what manufacturer.” service time indicators.
SUBSTANTIATION: During training with the different COMMITTEE ACTION: Accept.
manufacturers of Buddy Breath systems I have noticed a problem.
None of the manufacturers connect to one another. There is no way ___________________

466
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

(Log #10) (Log #14)


1981- 6 - (6-1.15): Accept 1981- 10 - (6-5.2): Accept in Principle
SUBMITTER: Karen E. Strumlock, Intertek Testing Services SUBMITTER: Karen E. Strumlock, Intertek Testing Services
RECOMMENDATION: Revise Paragraph 6-1.15 to read as follows: RECOMMENDATION: Add to the end of Paragraph 6-5.2:
“The SCBA being tested shall utilize a fully charged breathing gas “...If the fabric is not available in a 15-in. (381-mm) width specified
cylinder. The air flow performance test shall begin after 5 cycles of in Method 5903.1, the width of the test specimen shall be the widest
the breathing machine and continue to operate through at least 30 width as used on the SCBA, but shall be a minimum of 15 in. (381
cycles of the breathing machine after actuation of each end-of-service- mm) long. Where fabric components are not available in the length
time indicators as specified in Section 4.2.” specified above, the length of the test specimen shall be the longest
SUBSTANTIATION: Inclusion of this wording will clarify that the 30 length as used on the SCBA.”
breaths is measured for all end-of-service-time indicators. SUBSTANTIATION: Some samples are not available in 15 in.
COMMITTEE ACTION: Accept. lengths (for example: head harness material). We must provide a
COMMITTEE STATEMENT: See 6.1.5.2 and 6.1.5.6 in Committee provision for testing these types of materials. In addition, should
Proposal 1981-24 (Log #CP2). each width or just the widest be tested for heat?
COMMITTEE ACTION: Accept in Principle.
___________________ See 6.5.8 and 6.5.9 in in Committee Proposal 1981-24 (Log #CP2).
(Log #11) COMMITTEE STATEMENT: The Committee included the
1981- 7 - (6-2.2): Accept submitter’s recommendations in the rewrite of the heat test.
SUBMITTER: Karen E. Strumlock, Intertek Testing Services
RECOMMENDATION: Revise second and third sentences as follows: ___________________
“A test headform as specified in 6-1.1 chamber shall be equipped
with a thermocouple or other temperature-sensing element to (Log #15)
monitor SCBA test chamber temperature. The thermocouple or 1981- 11 - (6-6.1): Accept
other temperature-sensing element used shall be attached to the test SUBMITTER: Karen E. Strumlock, Intertek Testing Services
headform positioned in a manner in which it will be directly exposed RECOMMENDATION: Revise as follows:
to the chamber atmosphere surrounding the SCBA.” “Three specimens of each different All thread utilized shall be
SUBSTANTIATION: It is not necessary to mount the temprature- tested...”.
sensing device to the headform of the mannequin. As long as the SUBSTANTIATION: The number of specimens to be tested for each
sensing device is in the vicinity of the mannequin the same result will type of thread needs to be identified. Referencing other standards,
be achieved. NFPA 1971 requires three specimens of each thread type to be tested.
COMMITTEE ACTION: Accept. COMMITTEE ACTION: Accept.
COMMITTEE STATEMENT: This is now 6.2.4.1 in tin Committee COMMITTEE STATEMENT: See 6.6.2 in Committee Proposal 1981-
Proposal 1981-24 (Log #CP2). 24 (Log #CP2).

___________________ ___________________

(Log #12) (Log #16)


1981- 8 - (6-4.2): Accept in Principle 1981- 12 - (6-7.1): Accept in Principle
SUBMITTER: Karen E. Strumlock, Intertek Testing Services SUBMITTER: Karen E. Strumlock, Intertek Testing Services
RECOMMENDATION: Add to the end of Section 6-4.2: RECOMMENDATION: Revise as follows:
“If the fabric components are not available in the width specified in “An SCBA with a fully charged breathing gas cylinder, with the
Method 5903.1, the width of the test specimem shall be the widest breathing gas cylinder valve fully closed, shall be tested in accordance
width as used on the SCBA, but shall be a minimum of 12 in. (305 with Method 609.3, Salt Fog, Section II, of MIL STD 810E,
mm) long. If the fabric components are not available in the length Enviromental Test Methods ASTM B117, Standard Test Method for
specified above, the length of the test specimen shall be the longest Salt Spray (Fog) Testing.”
length as used on the SCBA.” SUBSTANTIATION: Other standards in this project have switched
SUBSTANTIATION: Some samples are not available in 12 in. to using the ASTM method for salt spray testing (e.g., 1971, 1977,
lengths (for example: head harness material). We must provide a 1982). This standard does not change the test method, but is a
provision for testing these types of materials. In addition, should standard with an active revision cycle.
each width or just the widest be tested for flame? COMMITTEE ACTION: Accept in Principle.
COMMITTEE ACTION: Accept in Principle. See Section 6.7 in Committee Proposal 1981-24 (Log #CP2).
See 6.4.8 and 6.4.9 in in Committee Proposal 1981-24 (Log #CP2). COMMITTEE STATEMENT: The Technical Committee rewrote the
COMMITTEE STATEMENT: The submitter’s recommendations are entire test method in in Committee Proposal 1981-24 (Log #CP2).
included in the total rewrite of the flame test.
___________________
___________________
(Log #13) (Log #2)
1981- 9 - (6-4.4): Accept in Principle 1981- 13 - (6-8): Accept in Principle
SUBMITTER: Karen E. Strumlock, Intertek Testing Services SUBMITTER: Thomas J. Comerford, Philadelphia Fire Dept.
RECOMMENDATION: Revise last sentence as follows: RECOMMENDATION: Revise text to read as follows:
“Specimens shall be observed for evidence of melting, or dripping, 6-8 Particulate Test. Any whistle that uses ambient air for either
and igniting ignition to determine pass/fail.” activation, or operation of the end-of-service-time indicator be tested
SUBSTANTIATION: Dripping is a pass/fail criteria and should be for particulate activation, and cleaned, separately.
observed. Conjunction should be “and” since all things should be SUBSTANTIATION: Current NIOSH/NFPA Standards allow
looked for, not one or the other. whistles of 80 decibels, activated and/or powered by ambient air, to
COMMITTEE ACTION: Accept in Principle. be the sole warning for firefighters wearing SCBAs and operating in
COMMITTEE STATEMENT: See 6.4.7 in Committee Proposal 1981- hazardous environments. The term Low Air Pressure Warning
24 (Log #CP2). Whistle (LAPWW) is used synonymously with the term End-Of-
Service-Time indicator.
___________________

467
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

The use of a whistle as the sole means of alerting a firefighter Measuring the Intelligibility of Speech over Communication Systems,
wearing an SCBA in a hazardous environment is unacceptable for the in the range of 500 Hz to 3000 Hz.”
following reasons: SUBSTANTIATION: The range in ANSI S3.2, Section 5.3, for
1. Ambient air can interfere with the effective operation of the audiometrically normal hearing is +20dB to -10dB in the frequency
whistle. range of 125 Hz to 8000 Hz. During the revision cycle of NFPA 1982
2. The pitch and tone of the whistle used by Philadelphia is not we determined that firefighters have difficulty hearing in high
compelling. frequency ranges. This requirement is starting to prevent the use of
3. The whistle tone is highly directional. actual firefighters for the communications test since they cannot pass
4. Bunker clothing is highly absorptive. the hearing requirements. By limiting the hearing range, we will still
5. The 80 decibel requirement is inadequate because: be able to utilize firefighters to perform this test, otherwise we will
Routine fireground operational sounds are frequently higher than need to utilize office personnel and other staff who are not as familiar
the NIOSH/NFPA standard of 80 decibels, the original Philadelphia with the use of SCBAs. It would make sense to use actual firefighters
requirement of 92 decibels, and the modified requirement of 102 with the actual hearing conditions as in the field to ensure
decibels. requirements are met.
The BOCA building code allows audible alarm-indicating appliances COMMITTEE ACTION: Accept.
to sound as high as 130 decibels.
6. The hearing loss of firefighters, and the general population, ___________________
corresponds with the tone and pitch of the whistle.
Note: Supporting material is available for review at NFPA (Log #19)
Headquarters. 1981- 16 - (6-10.12.2): Accept
COMMITTEE ACTION: Accept in Principle. SUBMITTER: Karen E. Strumlock, Intertek Testing Services
COMMITTEE STATEMENT: The Technical Committee RECOMMENDATION: Revise calculation as follows:
understands the submitter’s concerns and has looked at the broad

(∑ X)
issue of enf-of-service-time indicators (EOSTI). The Committee has 2
added a new expanded section on EOSTI (see Section 4.2 in the ROP
∑ (x)
2
draft) that requires at least 2 EOSTI for all SCBA that alert different −
human senses. sd = N
The Committee did not feel the current particulate test would
adequately evaluate whistle type EOSTI as that test was selected to N -1
evaluate other SCBA components that are affected by a different
particulate type. SUBSTANTIATION: Calculation for standard deviation is not
In addition, a new document on selection, care, and maintenance of correct; this is the proper formula.
SCBA (NFPA 1852) appears in this Committee report and includes COMMITTEE ACTION: Accept.
requirements for frequent checks of SCBAs, including the proper COMMITTEE STATEMENT: This is now in 6.10.5.8 in Committee
functioning of EOSTI, by the users and appropriate means of Proposal 1981-24 (Log #CP2).
correcting problems, if found.
___________________
___________________
(Log #4)
(Log #1) 1981- 17 - (6-11.2.1): Accept
1981- 14 - (6-10.3): Accept in Principle SUBMITTER: Karen E. Strumlock, Intertek Testing Services
SUBMITTER: Robert W. O’Gorman, ITS/ETL Testing Laboratories, RECOMMENDATION: Revise as follows:
Inc./Rep. ITS “...when tested in accordance with Section 5-2 5-1.1, Thermal
RECOMMENDATION: Replace “audiometrically normal” hearing as Protective Performance Test, of NFPA 1971...”.
defined in Section 5-3 of ANSI S3.2, Method for Measuring the SUBSTANTIATION: In the 2000 edition of NFPA 1971, Section 5-
Intelligibility of Speech over Communications Systems, with “hearing 1.1 is the proper section to reference.
threshold levels that are no higher than +20 db and no lower than - COMMITTEE ACTION: Accept.
10db at any audiometric test frequency 125 Hz through 4000 Hz as COMMITTEE STATEMENT: This is now in 6.11.4.3 in Committee
the threshold is measured by using an audiometer which meets the Proposal 1981-24 (Log #CP2).
American National Standard specification for audiometers, ANSI ___________________
S3.6-1989.”
SUBSTANTIATION: ANSI S3.2 requires hearing levels of up to 8000 (Log #5)
Hz; today’s firefighters are evaluated against NFPA 1582 which allows 1981- 18 - (6-11.2.2): Accept
for significantly lower hearing levels by a firefighter. No data has SUBMITTER: Karen E. Strumlock, Intertek Testing Services
been collected regarding current communications systems vs. 1582 RECOMMENDATION: Revise as follows:
levels, so the number being presented is based upon lab records for “The outer shell shall be one of the following options: (a) 40
test subjects not accepted to partake in conducting evaluations. percent PBI®/60 percent Kevlar® ripstop weave, weighing
COMMITTEE ACTION: Accept in Principle. approximately 7.5 oz/yd2 (255 g/m2), with a water-repellant finish.
COMMITTEE STATEMENT: See Committee Action on Comment Color shall be natural and undyed.
1981-15 (Log #17). (b) 40 percent PBO®/60 percent Technora® plain weave, weighing
approximately 7.5 oz/yd2(255 g/m2), with a water-repellant finish.
___________________ Color shall be natural and undyed.”
SUBSTANTIATION: Changes made to NFPA 1971, the standard
(Log #17) governing turnout coats, has made new and/or improved fabrics
1981- 15 - (6-10.3): Accept more readily available.
SUBMITTER: Karen E. Strumlock, Intertek Testing Services COMMITTEE ACTION: Accept.
RECOMMENDATION: Revise to read as follows: COMMITTEE STATEMENT: This is now in 6.11.4.4 in Committee
“The subjects participating as listeners shall have ‘audiometrically Proposal 1981-24 (Log #CP2).
normal’ hearing as defined in Section 5.3 of ANSI S3.2, Method for
___________________

468
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

(Log #CP1)
(Log #6) 1981- 23 - (Entire Document): Accept
1981- 19 - (6-11.2.3): Accept SUBMITTER: Technical Committee on Respiratory Protection and
SUBMITTER: Karen E. Strumlock, Intertek Testing Services Personal Alarm Equipment
RECOMMENDATION: Add new text to read: RECOMMENDATION: Restructure entire document to comply with
“The thermal liner shall be constructed of a 3.0 oz/yd2 (102 g/m2) the NFPA Manual of Style as follows:
ripstop pajama check or plain weave Nomex®III facecloth...”. 1. Chapter 1 to contain administrative text only.
SUBSTANTIATION: Changes made to NFPA 1971, the standard 2. Chapter 2 to contain only referenced publications cited in the
governing turnout coats, has made new and/or improved fabrics mandatory portions of the document.
more readily available. 3. Chapter 3 to contain only definitions.
COMMITTEE ACTION: Accept. 4. All mandatory sections of the document must be evaluated for
COMMITTEE STATEMENT: This is now in 6.11.4.5 in Committee usability, adoptability, and enforceability language. Generate
Proposal 1981-24 (Log #CP2). necessary committee proposals.
5. All units of measure in the document are converted to SI units
___________________ with inch/pound units in parentheses.
6. Appendices restructured and renamed as “Annexes.”
(Log #7) SUBSTANTIATION: Editorial restructuring, to conform with the
1981- 20 - (6-11.2.4): Accept in Principle 2000 edition of the NFPA Manual of Styoe.
SUBMITTER: Karen E. Strumlock, Intertek Testing Services COMMITTEE ACTION: Accept.
RECOMMENDATION: Revise as follows:
“The moisture barrier shall be constructed of one of the following ___________________
options: (a) approximately 2.25 oz/yd2 (76 g/m2) polyester/cotton
(Log #CP2)
fabric that is coated with approximately 6.5 oz/yd2 (221 g/m2) of 1981- 24 - (Entire Document): Accept
flame-resistant neoprene. TCC NOTE: 1. The TCC is submitting the following text to the
(b) approximately 2.7 oz/yd2 Nomex®/Kevlar E89 cloth laminated Technical Committee to incorporate into Section 1.5, Chapter 2, and
to a breathable film that meets all NFPA 1971 requirements.” Annex A as shown. This text that addresses details related to
SUBSTANTIATION: Changes made to NFPA 1971, the standard certification organization investigations of product malperformance
governing turnout coats, has made new and/or improved fabrics or failure, and manufacturer product safety alert and product recall
more readily available. systems.
COMMITTEE ACTION: Accept in Principle. The TCC also asks the TC to consider adding further guidelines in
COMMITTEE STATEMENT: See the rewrite of Section 6.11 in annex item A.2.2.10.7 for relating specific design features,
Committee Proposal 1981-24 (Log #CP2). performance properties, or attributes to each of the product defect
classes currently proposed. This system of classification is intended
___________________ to assist the certification organization in determining which action is
appropriate upon the investigation or product malperformance or
(Log #8) failure.
1981- 21 - (6-11.2.5): Accept Add two new definitions to Section 1.5 to read:
SUBMITTER: Karen E. Strumlock, Intertek Testing Services 1.5.X Compliant Product(s). A product(s) that is covered by this
RECOMMENDATION: Revise as follows: standard and has been certified as meeting all applicable
“The moisture barrier shall be completely sewn to the thermal liner requirements of this standard that pertain to the product.
at its perimeter with the neoprene cloth side feeling outward from 1.5.X Safety Alert. The action by which a manufacturer identifies a
the thermal liner. All edges shall be sewn together and bound with compliant product or a component of a compliant product, provides
nonwicking moisture barrier material. The liner/moisture barrier notice to the end users, and informs the market place and
shall be no more than 3 in. (76 mm) from The coat hem.” distributors of potential safety concerns regarding the specific
SUBSTANTIATION: Changes to previous sections (if accepted) compliant product or compliant product component.
would require this section to be altered due to the changes of NFPA Add new 2.1.1 to read (renumber the existing paragraphs):
1971. 2.1.1 The certification process for SCBA as being compliant with
COMMITTEE ACTION: Accept. NFPA 1981 shall include the requirements of Section 2.1, General;
COMMITTEE STATEMENT: This is now in 6.11.4.7 in Committee Section 2.2, Certification Program; Section 2.3, Inspection and
Proposal 1981-24 (Log #CP2). Testing; Section 2.4, Recertification; Section 2.5, ISO Registration
for Manufacturers; Section 2.6, Manufacturer’s Investigation of
___________________ Returns and Complaints; and Section 2.7, Manufacturer’s Safety Alert
and Product Recall Systems.
(Log #18) Revise 2.2.10 to read:
1981- 22 - (6-11.5): Accept 2.2.10 The certification organization shall have a program for
SUBMITTER: Karen E. Strumlock, Intertek Testing Services investigating field reports alleging malperformance or failure of
RECOMMENDATION: Change the first sentence to read: listed compliant products.
“The protective hood shall meet the requirements of Section 4-5 Add the following new paragraphs, following 2.2.10, to read:
and 5-5 hood requirements of NFPA 1971, Standard on Protective 2.210.1 The certification organization shall conduct an investigation
Ensemble for Structural Fire Fighting.” when a written, signed complaint is received that alleges a specific
SUBSTANTIATION: To ensure the hood is in complete compliance malperformance or failure of a specific compliant product or
with the standard the entire standard should be referenced, not just component of a compliant product.
sections. 2.210.2 The investigation by the certification organization shall
COMMITTEE ACTION: Accept. include an initial determination of the validity of the complaint and if
COMMITTEE STATEMENT: This is now in 6.11.4.16 in Committee compliant product or compliant product component constitutes a
Proposal 1981-24 (Log #CP2). potential safety risk to end users.
2.2.10.3 If the certification organization determines the complaint
___________________ to be valid and determines that the compliant product or compliant
product component constitutes a potential safety risk to end users,

469
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

then the certification organization shall undertake a more detailed product component can constitute a potential safety risk to end users
investigation that determines the scope and nature of the safety risk, that is possibly subject to a safety alert or product recall, then the
the nature of possible injury or other consequences from using the manufacturer shall immediately contact the certification organization
compliant product in question, and possible causes or circumstances and provide all information about their review to assist the
that led to the compliant product’s or compliant product certification organization with their investigation.
component’s failure or malperformance. 2.7 Manufacturer’s Safety Alert and Product Recall Systems
2.2.10.4 The certification organization’s investigation shall include 2.7.1 The manufacturer shall establish a written safety alert system
but not be limited to the extent and scope of the problem, as it might and a written product recall system that describes the procedures it
apply to other compliant product or compliant product components will use in the event that it decides or is directed by the certification
manufactured by other manufacturers or certified by other organization to either issue a safety alert or conduct a product recall.
certification organizations, and specific testing against the 2.7.2 The manufacturer’s safety alert and product recall system
requirements of the standard to which the compliant product was shall provide:
certified. (1) the establishment of a coordinator and responsibilities by the
2.2.10.5 The certification organization shall also investigate manufacturer for the handling of safety alerts and product recalls;
complaints of malperformance or failure that are not anticipated by (2) a method of notifying all dealers, distributors, purchasers and
the performance requirements of the relevant standard to determine end users, and the NFPA about the safety alert or product recall that
if the malperformance or failure presents a safety alert or product can be initiated within a one week period following the
recall. manufacturer’s decision to issue a safety alert or to conduct a
2.2.10.6 The certification organization shall require the product recall, or after the manufacturer has been directed by the
manufacturer of the compliant product, or the manufacturer of the certification organization to issue a safety alert or conduct a product
compliant product component if applicable, to conduct its own recall;
investigation as specified in Section 2.6. (3) techniques for communicating accurately and understandably
2.2.10.7* The certification organization shall prepare a report with the nature of the safety alert or product recall, in particular the
the findings of its investigation. The report shall provide one of specific hazard or safety issue found to exist;
three conclusions: (4) procedures for removing product that is recalled and for
(1) that no action is required on the part of the certification documenting the effectiveness of the product recall; and
organization, (5) a plan for either repairing, replacing, or compensating
(2) that the manufacturer shall issue a safety alert, or purchasers for returned product.
(3) that the manufacturer shall conduct a recall of the affected Add new A.2.2.10.7 to read:
product. A.2.2.10.7 The determination of the appropriate action for the
2.2.10.8 The certification organization shall provide the report to certification organization to undertake in event that a specific
the organization or individual submitting the complaint and to the problem is identified should be take into consideration the severity
manufacturer of the compliant product or compliant product of the problem and its potential consequences to the safety and
component. Where the report’s findings involve issuing a safety alert health of end users. Testing of affected product against the
or conducting a product recall, the certification organization shall requirements of this standard should be performed to assist in
also provide the report to the NFPA. determining the severity of the problem.
2.2.10.9 Where the certification organization’s findings conclude It is also recognized that safety alerts and product recalls can be
that a recall of the affected compliant product will be conducted the determined necessary for problems or circumstances not anticipated
product manufacturer, the certification organization shall suspend or by the requirements in this standard. As with other bases for issuance
terminate the product manufacturer’s listing of the affected of safety alerts and product recall, the decision to initiate action
compliant product. based on such problems and circumstances should take into
2.2.10.10 Where the certification organization’s findings conclude consideration the specific safety risks to end users by the affected
that a component of compliant product is the basis for recall, the compliant product or compliant product component(s).
certification organization shall suspend or terminate the compliant As a guideline for determining between a safety alert and a product
product manufacturer’s listing for all compliant products from that recall, the following defects affecting compliant product or
particular manufacturer which incorporate the specific component, compliant product component attributes and performance should be
and shall investigate the use of the specific component by other classified among the following categories:
manufacturers. Critical – a defect that judgment and experience indicate is likely to
2.2.10.11 Where the manufacturer of the compliant product does result in a condition immediately hazardous to life or health for
not comply with the certification organization’s findings, then the individuals using or depending upon the compliant product (in this
certification organization shall be obligated to terminate all of the case, an SCBA).
product listings of compliance with this standard by the certification Major A – a defect, other than critical, that is likely to result in
organization for that product manufacturer failure to the degree that the compliant product will not provide
Revise 2.2.11 to read: protection (in this case, an SCBA that will not provide respiratory
2.2.11 The certification organization shall require the manufacturer protection), or a defect that reduces protection and is not detectable by
to have a product safety alert system and a product recall system as the end user.
part of the manufacturer’s quality assurance program. The Major B – a defect, other than critical or Major A, that is likely to
certification organization shall verify that the manufacturer’s product result in reduced protection, and is detectable by the end user.
safety alert and product recall systems meet the requirements Minor – a defect, other than critical, Major A, or Major B, that is not
specified in Section 2.7. likely to materially reduce the usability of the compliant product for
Add new Sections 2.6 and 2.7 to read: its intended purpose, or a defect that is a departure from established
2.6 Manufacturer’s Investigation of Returns and Complaints standards and has little bearing on the effective use or operation of
2.6.1 The manufacturer shall provide corrective action in the compliant product.
accordance with ISO 9001, Quality Systems – Model for Quality The following actions for handling substantiated product defects or
Assurance in Design, Development, Production, Installation, and Servicing, product malperformance are recommended:
for investigating returned products and written complaints. Critical defect: product recall
2.6.2 Manufacturer records of returns and complaints related to Major A defect: product recall or safety alert depending on the
safety issues shall be retained for at least 5 years. nature of the specific defect
2.6.3 Where the manufacturer, during the review of specific returns Major B defect: safety alert or no action, depending on the nature
or complaints, discovers that a compliant product or compliant of the specific defect

470
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

Minor defect: no action established and whether patent considerations were evaluated (where
TCC Statement: The current provisions in NFPA 1981, and all other a company holds patents on facepiece type displays, potentially
product standards within this Project, are insufficient in specifying locking others out of the market).
when a field investigation is conducted by the certification 6. On the Emergency Air Flow System issue, the TCC directs the TC
organization or how the manufacturer is to conduct a product recall to review and revise the design criteria of Section 4.4. The current
when product malperformance or product failure is substantiated. text is too vague and evaluation of the criteria is not possible.
The TCC is providing this text to the TC to provide clear direction The TCC directs the TC to evaluate the NIOSH requirements for
on the necessary procedures for the certification organization such devices and the design requirements used by NIOSH to evaluate
conduct of a field investigation alleging product malperformance or the basis of failure modes and effects analyses criteria that NIOSH
failure, and to establish minimum requirements of a manufacturer’s applies. NIOSH certification applies as a prerequisite to all SCBA
safety alert system and product recall system. It is the intent of the that will be tested for compliance with NFPA 1981.
TCC that this text, or very similar text, will become a part of the TCC Statement: The basis for the requirements of Section 4.4 is
“boilerplate” text of each certification chapter in all product nebulous. Why were only regulators that operate at or below 520 psig
documents within this Project. required to be equipped with an emergency air flow system? Why
2. The TCC directs the TC to add a new paragraph 3.2.9 to read: must all hose withstand full cylinder pressure? This requirement
“3.2.9 The manufacturer shall provide the manufacturers’ specified would seem to require that all hose and regulators be capable of
component service life for breathing air cylinders and for all withstanding 4500 psi. The TCC believes this would add weight and
elastomeric components of the SCBA. This data shall be included at stiffness to the system, possibly compromising safety of the SCBA
least in the maintenance information provided to the users.” user. Currently these hose and regulators are not capable of
TCC Statement: This new paragraph needs to be added, as an withstanding the high pressure, but are protected from failure with a
appropriate cross reference, to assure the information that NFPA relief valve. The relief valve solution creates a safe, time proven,
1852 requires the maintenance personnel to use is provided by the system while maintaining a user-friendly configuration.
manufacturers. The clear and unambiguous evaluation of this component to
3. The TCC directs the TC to review all design criteria in Sections properly perform during SCBA use is essential to the safety of the
4.2, 4.3, and 4.4 and revise the text to assure the design requirements SCBA users. If the design requirements cannot be addressed, then
have definitive specifications without ambiguity that can be the TC is directed to withdraw these items and do whatever work is
effectively evaluated by the certification organization. required for incorporation into a future ROP.
TCC Statement: The TCC strongly believes these components – 7. On the Emergency Air Flow System issue, the TCC directs the TC
EOSTI, HUD, Emergency Air Flow – are important components of to review the performance requirements of Sections 5.1, 5.2, 5.3, 5.7,
the SCBA. The vague design criteria given in Sections 4.2, 4.3, and 5.8, and 5.11 to determine if any or all will be included as
4.4 and the lack of performance requirements causes NFPA 1981 to performance requirements for the emergency air flow system. The
be inconsistent with other documents of the Project and the TC must TC is directed to include pass/fail requirements to each of the
remedy this situation during the ROC. applicable performance requirements for the emergency air flow
The clear and unambiguous evaluation of these components to system. Further, the TC is directed to modify the associated test
properly perform during SCBA use is essential to the safety of the methods to include testing of the emergency air flow system (after
SCBA users. If the design requirements cannot be addressed, then conditioning and environmental testing) with procedures, reporting,
the TC is directed to withdraw these items and do whatever work is and interpretation criteria, as necessary.
required for incorporation into a future ROP. TCC Statement: SCBA with this component must be tested for full
4. On the End-of-Service-Time Indicator (EOSTI) and the Head-Up and proper functioning following the exposures specified in the
Display (HUD) issues, the TCC directs the TC to modify the above noted performance requirements. The standards of this
performance requirements of Sections 5.1, 5.2, 5.3, 5.7, 5.8 and 5.11 Project are based, to the greatest extent possible, on performance
to include pass/fail requirements for EOSTI and HUD as part of the requirements and associated test methods by which the performance
requirements. Further, the TC is directed to modify the associated can be determined. The clear and unambiguous testing of this
test methods to include testing of the EOSTI and HUD (after component to properly perform during SCBA use is essential to the
conditioning and environmental testing) with procedures, reporting, safety of the SCBA users. If the performance requirements cannot
and interpretation criteria, as necessary. be addressed, then the TC is directed to withdraw this item and do
TCC Statement: SCBA with these components must be tested for whatever work is required for incorporation into a future ROP.
full and proper functioning following the exposures specified in the SUBMITTER: Technical Committee on Respiratory Protection and
above noted performance requirements. The standards of this Personal Alarm Equipment
Project are based, to the greatest extent possible, on performance RECOMMENDATION: The Technical Committee on Respiratory
requirements and associated test methods by which the performance Protection and Personal Alarm Equipment proposes a complete
can be determined. The clear and unambiguous testing of these revision to NFPA 1981, Standard on Open-Circuit Self-Contained
components to properly perform during SCBA use is essential to the Breathing Apparatus for the Fire Service, 1997 edition, as shown at
safety of the SCBA users. If the performance requirements cannot the end of this report. The document when adopted will be retitled,
be addressed, then the TC is directed to withdraw these items and do Standard on Open-Circuit Self-Contained Breathing Apparatus for
whatever work is required for incorporation into a future ROP. Fire and Emergency Services.
5. On the Head-Up Display issue, the TCC directs the TC to review SUBSTANTIATION: This revision includes a new breathing test
the HUD requirement in 4.3.6 for use in bright sunlight is machine that is being proposed to replace the current “NFPA 327”
questioned. We know from experiences on other products, that an breathing machine. All air flow tests required by the standard will be
LED in the facepiece creates problems for SCBA wearers, conducted on the machine to determine performance to the
particularly in low light or darkness conditions. LEDs can be blinding requirements of the standard. The vibration test apparatus has been
when the SCBA wearer’s pupils are dilated from trying to see in a modified to change the holding containers for the SCBA and
low/no light environment. components to provide a safer testing procedure and more
TCC Statement: The TCC is concerned whether other display reproducible testing results.
technologies, where vision correction is required to be able to focus Also in this revision, new requirements for end-of-service-time
at a close range, have been fully considered and evaluated. indicators (EOSTI), a head-up display, and facepiece CO2
The TCC is concerned that ambiguous evaluation criteria, combined concentration have been added. Design items will be found in
with these new requirements for inclusion of a facepiece HUD, will Chapter 4, performance requirements will be found in Chapter 5,
result in equipment not ready for the fire or emergency services. and the test methods by which the pass/fail performance is
Additionally, the TCC is concerned with how these criteria were determined will be found in Chapter 6 of this ROP.

471
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

Other changes have been made throughout the document to This ROP is being printed during a transition time for style of NFPA
improve understandability of text, clarify testing procedures and test documents. Prior to final publication of the document, editorial
reporting, and to make a product standard as “user friendly” as changes to the format and chapter subjects will occur. The new
possible for such complicated documents that must be written in very Chapter 1 will contain only the scope, purpose, applicability, and unit
exact and restrictive language. (For product standards such as NFPA statements. The new Chapter 2 will become the referenced
1981, the “users” mentioned are primarily the product manufacturers publications chapter containing the mandatory referenced
who must design and build their product so as to be compliant with documents that are now found in Chapter 7 of this ROP. The new
the standard, and the certification and testing organizations who must Chapter 3 will be definitions. The new Chapter 4 will have the
evaluate the products against the standard to determine the product’s certification requirements found in Chapter 2 of this ROP. The new
compliance or non-compliance. The fire and emergency services are Chapter 5 will have the product labeling and user requirements
also “users” of the standard but generally reference their requirement found in Chapter 3 of this ROP. The new Chapter 6 will have the
that products to be purchased are “certified as compliant” with the design requirements found in Chapter 4 of this ROP. The new
standard in their solicitation for bids and in their purchase Chapter 7 will have the performance requirements found in Chapter
specifications.) 5 of this ROP. The new Chapter 8 will have the test methods found in
Chapter 6 of this ROP. Other editorial changes will reflect the new
style and format for all NFPA codes, standards, recommended
practices, and guides.
COMMITTEE ACTION: Accept.

___________________

472
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
NFPA 1981
1.3.3 This standard shall not apply to open-circuit SCBA
Standard on manufactured according to previous editions of this standard;
however, organizations shall be permitted to have open-circuit SCBA
Open-Circuit Self-Contained Breathing that are certified as compliant with previous editions of this standard
and modified to become compliant with this edition of NFPA 1981.
Apparatus for Fire and Emergency Services
1.3.4 This standard shall not apply to closed-circuit SCBA.
2002 Edition
1.3.5 This standard shall not apply to accessories that can be
attached to any open-circuit SCBA and combination SCBA/SARs
NOTICE: An asterisk (*) following the number or letter designating other than as specifically addressed herein.
a paragraph indicates that explanatory material on the paragraph can
be found in Annex A. 1.3.6 This standard shall not apply to the use of SCBA and
Inforamtion on referenced publications can be found in Chapter 7 combination SCBA/SARs as these requirements are specified in
and Annex B. NFPA 1500, Standard on Fire Department Occupational Safety and Health
Program.
Chapter 1 Administration
1.4 Units.
1.1 Scope.
1.4.1 In this standard, values for measurement are followed by an
1.1.1* This standard shall specify the minimum requirements for the equivalent in parentheses, but only the first stated value shall be
design, performance, testing, and certification of open-circuit self- regarded as the requirement.
contained breathing apparatus (SCBA) and combination open-circuit
self-contained breathing apparatus and supplied air respirators 1.4.2 Equivalent values in parentheses shall not be considered as the
(SCBA/SAR) for fire and emergency services personnel. requirement as these values might be approximate.

1.1.2 This standard shall specify the requirements for SCBA as 1.5 Definitions.
detailed in Section 1.3.
1.5.1 General.
1.1.3 This standard shall not specify requirements for other types of
self-contained breathing apparatus. 1.5.1.1 For the purposes of this standard, the following terms shall
have the meanings stated in 1.5.2 unless modified by specific text
1.1.4 Nothing herein shall restrict any jurisdiction or manufacturer within the mandatory requirements of this standard.
from exceeding these minimum requirements.
1.5.1.2 Where terms are not defined in 1.5.2 those terms shall have
1.2 Purpose. the ordinarily accepted meanings or the meaning that the text
implies.
1.2.1* The purpose of this standard shall be to establish a minimum
safe level of open-circuit SCBA and combination SCBA/SARs for fire 1.5.1.3 Terms used in the present tense shall include the past and
and emergency services personnel from immediately dangerous to future tense, terms used in the masculine gender shall include the
life and health (IDLH) atmospheres. feminine and neuter genders, terms used in the singular shall include
the plural, and terms used in the plural shall include the singular.
1.2.2 The purpose of this standard also shall be to establish
requirements to ensure that accessories do not degrade the 1.5.2 Definition of Terms.
performance of the SCBA.
1.5.2.1 Accessory. An item, provided by the SCBA manufacturer for
1.2.3* Controlled laboratory tests used to determine compliance use with its SCBA, that is attached to the SCBA but is not necessary
with the performance requirements of this standard shall not be for the SCBA to meet the requirements of this standard.
deemed as establishing performance levels for all respiratory
protective situations and IDLH atmospheres to which personnel can 1.5.2.2* Approved. Acceptable to the authority having jurisdiction.
be exposed.
1.5.2.3 Atmosphere-Supplying Respirator. A respirator that supplies
1.2.4 This standard shall not be interpreted or used as a detailed the respirator user with breathing air from a source independent of
manufacturing or purchase specification, but shall be permitted to be the ambient atmosphere and includes self-contained breathing
referenced in purchase specifications as minimum requirements. apparatus (SCBA) and supplied air respirators (SAR). (See also
1.5.2.13, Combination SCBA/SAR, 1.5.2.43, Self-Contained Breathing
1.3 Application. Apparatus, and 1.5.2.47, Supplied Air Respirator.)

1.3.1 This standard shall apply to all open-circuit SCBA and 1.5.2.4* Authority Having Jurisdiction. The organization, office, or
combination SCBA/SARs used by fire and emergency service individual responsible for approving equipment, materials, an
organizations for respiratory protection of its personnel during installation, or a procedure.
operations that include but are not limited to fire fighting, rescue,
and hazardous materials where products of combustion, oxygen
deficiency, particulates, toxic products, or other IDLH atmospheres 1.5.2.5 Basic Plane. The plane through the centers of the external
do exist or could exist at the incident scene. ear openings and the lower edges of the eye sockets.

1.3.2 This standard shall apply to the design, manufacturing, and 1.5.2.6 Breathing Air. See 1.5.2.16, Compressed Breathing Air.
certification of new open-circuit SCBA.

473
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
1.5.2.7 Breathing Air Cylinder. The pressure vessel or vessels that are 1.5.2.20 End-of-Service-Time Indicator (EOSTI). A warning device
an integral part of the SCBA and that contain the breathing gas on an SCBA that warns the user that the end of the service time of
supply; can be configured as a single cylinder or other pressure the SCBA is approaching.
vessel, or as multiple cylinders or pressure vessels.
1.5.2.21 Fabric Component. Any single or combination of natural or
1.5.2.8 Breathing Air/Gas Container. See 1.5.2.8, Breathing Air synthetic material(s) that are pliable and that are made by weaving,
Cylinder. felting, forming, or knitting.

1.5.2.9 Certification/Certified. A system whereby a certification 1.5.2.22 Facepiece. The component of an SCBA that covers the
organization determines that a manufacturer has demonstrated the wearer's nose, mouth, and eyes.
ability to produce a product that complies with the requirements of
this standard, authorizes the manufacturer to use a label on listed 1.5.2.23 Follow-up Program. The sampling, inspections, tests, or
products that comply with the requirements of this standard, and other measures conducted by the certification organization on a
establishes a follow-up program conducted by the certification periodic basis to determine the continued compliance of listed
organization as a check on the methods the manufacturer uses to products that are being produced by the manufacturer to the
determine continued compliance of labeled and listed products with requirements of this standard. (1977:3.1)
the requirements of this standard. (See also 1.5.2.33, NIOSH
Certified.) (1971:3.1) 1.5.2.24 Gas. An aeriform fluid that is in a gaseous state at standard
temperature and pressure.
1.5.2.10 Certification Organization. An independent third-party
organization that determines product compliance with the 1.5.2.25 Haze. Light that is scattered as a result of passing through a
requirements of this standard with a labeling/listing/follow-up transparent object.
program. (1971:3.1)
1.5.2.26 Head Up Display (HUD). Visual display of information and
1.5.2.11 Char. The formation of a brittle residue when material is system condition status visible to the SCBA wearer.
exposed to thermal energy.
1.5.2.27 Identical SCBA. SCBA that are produced to the same
1.5.2.12 Closed-Circuit SCBA. A recirculation-type SCBA in which engineering and manufacturing specifications.
the exhaled gas is rebreathed by the wearer after the carbon dioxide
has been removed from the exhalation gas and the oxygen content 1.5.2.28 Labeled. Equipment or materials to which has been
within the system has been restored from sources such as compressed attached a label, symbol, or other identifying mark of an organization
breathing air, chemical oxygen, and liquid oxygen, or compressed that is acceptable to the authority having jurisdiction and concerned
gaseous oxygen. with product evaluation, that maintains periodic inspection of
production of labeled equipment or materials, and by whose labeling
1.5.2.13 Combination SCBA/SAR. An atmosphere-supplying the manufacturer indicates compliance with appropriate standards or
respirator that supplies a respirable atmosphere to the user from a performance in a specified manner.
combination of two breathing air sources that both are independent
of the ambient environment and consists of (1) an open-circuit SCBA 1.5.2.29* Listed. Equipment, materials, or services included in a list
certified as compliant with NFPA 1981, Standard on Open-Circuit Self- published by an organization that is acceptable to the authority
Contained Breathing Apparatus for Fire and Emergency Services, and having having jurisdiction and concerned with evaluation of products or
a minimum rated service time of 30 minutes; and (2) having a services, that maintains periodic inspection of production of listed
connection for the attachment of an air line that would provide a equipment or materials or periodic evaluation of services, and whose
continuous supply of breathing air independent of the SCBA listing states that either the equipment, material, or service meets
breathing air supply. This definition does not include SARs that are appropriate designated standards or has been tested and found
used in conjunction with an escape self-contained breathing suitable for a specified purpose.
apparatus (ESCBA) where the ESCBA provides less than a minimum
rated service time of 30 minutes. For the purposes of this standard,
combination SCBA/SARs are encompassed by the term SCBA. (See 1.5.2.30 Melt. To change from solid to liquid, or become consumed,
also 1.5.2.3, Atmosphere-Supplying Respirator, 1.5.2.43, Self- by action of heat.
Contained Breathing Apparatus, and 1.5.2.47, Supplied Air
Respirator.) 1.5.2.31 Mid-Sagittal Plane. The plane, perpendicular to the basic
and coronal planes, that bisects the head symmetrically.
1.5.2.14 Compliance/Compliant. Meeting or exceeding all
applicable requirements of this standard. (1971:3.1) 1.5.2.32 Negative Pressure SCBA. An SCBA in which the pressure
inside the facepiece, in relation to the pressure surrounding the
1.5.2.15 Component. Any material, part, or subassembly providing outside of the facepiece, is negative during any part of the inhalation
the required protection that is used in the construction of the SCBA. or exhalation cycle when tested by NIOSH in accordance with 42 CFR
84.
1.5.2.16* Compressed Breathing Air. Oxygen or a respirable gas
mixture stored in a compressed state and supplied to the user in 1.5.2.33* NIOSH Certified. Tested and certified by the National
gaseous form. Institute for Occupational Safety and Health (NIOSH) of the U.S.
Department of Health and Human Services in accordance with the
1.5.2.17 Cylinder. See 1.5.2.7, Breathing Air Cylinder. requirements of 42 CFR 84, Subpart H. (See also 15.2.9,
Certification/Certified.)
1.5.2.18 Demand SCBA. See 1.5.2.32, Negative Pressure SCBA.
1.5.2.34 Open-Circuit SCBA. An SCBA in which exhalation is vented
1.5.2.19 Drip. To run or fall in drops or blobs. to the atmosphere and not rebreathed. There are two types of open-
circuit SCBA: negative pressure or demand type, and positive
pressure or pressure demand type.

474
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
1.5.2.35 Pink Noise. Noise that contains constant energy per octave Chapter 2 Certification
band.
2.1 General.
1.5.2.36 Positive Pressure SCBA. An SCBA in which the pressure
inside the facepiece, in relation to the pressure surrounding the 2.1.1 Prior to certification of SCBA to the requirements of this
outside of the facepiece, is positive during both inhalation and standard, SCBA shall be NIOSH certified.
exhalation when tested by NIOSH in accordance with 42 CFR 84,
Subpart H. 2.1.1.1 SCBA shall have NIOSH certification as positive pressure.

1.5.2.37 Pressure Demand SCBA. See 1.5.2.36, Positive Pressure 2.1.1.2* SCBA shall have a NIOSH-certified rated service time of at
SCBA. least 30 minutes.

1.5.2.38 Product Label. A label or marking affixed to the SCBA by 2.1.1.3 SCBA that are NIOSH certified as positive pressure but
the manufacturer containing general information, care, capable of supplying air to the user in a negative pressure, demand-
maintenance, or similar data. This product label is not the type mode shall not be certified to this standard.
certification organization's label, symbol, or identifying mark;
however, the certification organization's label, symbol, or identifying 2.1.2 All SCBA that are labeled as being compliant with this standard
mark may be attached to it or be part of it. (See also 1.5.2.28, shall meet or exceed all applicable requirements specified in this
Labeled.) standard and shall be certified.

1.5.2.39 Rated Service Time. The period of time, stated on the 2.1.2.1 This certification shall be to the certification program
SCBA’s NIOSH certification label, that the SCBA supplied air to the specified in Section 2.2.
breathing machine when tested to 42 CFR 84, Subpart H.
2.1.2.2 This certification shall be in addition to, and shall not be
1.5.2.40 SAR. An abbreviation for supplied air respirator. See construed to be the same as, the NIOSH certification as specifically
1.5.2.47, Supplied Air Respirator. defined in 1.5.2.33.

1.5.2.41 SCBA. An abbreviation for self-contained breathing 2.1.3 Manufacturers shall not claim compliance with a portion(s) or
apparatus. For the purposes of this standard, where this abbreviation segment(s) of the requirements of this standard and shall not use the
is used without any qualifier, it indicates only open-circuit self- name or identification of this standard in any statements about their
contained breathing apparatus and combination SCBA/SARs. See respective products unless the product is certified to this standard.
1.5.2.13, Combination SCBA/SAR, and 1.5.2.43, Self-Contained
Breathing Apparatus. 2.1.4 All certification to this standard shall be performed by a
certification organization that meets at least the requirements
1.5.2.42 SCBA/SAR. An abbreviation for combination open-circuit specified in Section 2.2, and that is accredited for personal protective
SCBA and supplied air respirator. See 1.5.2.13, Combination equipment in accordance with ANSI Z34.1, American National
SCBA/SAR, 1.5.2.43, Self-Contained Breathing Apparatus, and Standard for Third-Party Certification Programs for Products, Processes, and
1.5.2.47, Supplied Air Respirator. Services.

1.5.2.43 Self-Contained Breathing Apparatus (SCBA). An 2.1.5 All compliant SCBA shall be listed and each compliant SCBA
atmosphere-supplying respirator that supplies a respirable air shall be labeled.
atmosphere to the user from a breathing air source that is
independent of the ambient environment and designed to be carried 2.1.6 Each compliant SCBA shall also have a product label that meets
by the user. For the purposes of this standard, where this term is the requirements specified in Section 3.1
used without any qualifier, it indicates only open-circuit self-
contained breathing apparatus or combination SCBA/SARs. For the 2.1.7 The certification organization’s label, symbol, or identifying
purpose of this standard, combination SCBA/SARs are encompassed mark shall be attached to the product label or shall be part of the
by the terms self-contained breathing apparatus or SCBA. (See also product label.
1.5.2.3, Atmosphere-Supplying Respirator, 1.5.2.13, Combination
SCBA/SAR, and 1.5.2.47, Supplied Air Respirator.) 2.1.8 The certification organization shall not certify any structural
protective ensembles or individual elements of the structural
1.5.2.44 Service Time. See 1.5.2.39, Rated Service Time. protective ensemble to the 1997 edition of NFPA 1971, Standard on
Protective Ensemble for Structural Fire Fighting, on or after September 1,
1.5.2.45 Shall. Indicates a mandatory requirement. 2000.

1.5.2.46 Should. Indicates a recommendation or that which is 2.1.9 The certification organization shall not permit any
advised but not required. manufacturer to label any SCBA as compliant with the 1997 edition
of NFPA 1981 on or after September 1, 2002.
1.5.2.47 Supplied Air Respirator (SAR). An atmosphere-supplying
respirator that supplies a respirable atmosphere to the user from a 2.1.10 The certification organization shall not permit any
combination of two breathing air sources that both are independent manufacturer to label any SCBA as compliant with any edition of
of the ambient environment, one of which is a long duration source NFPA 1981 or NFPA 19B, Standard on Respiratory Protective Equipment
that is not designed to be carried by the user and the second of which for Firefighters, that is dated prior to 1997 on or after the NFPA
is a shorter duration source that is designed to be carried by the user. effective date of this standard.
For the purposes of this document, combination SCBA/SARs are
encompassed by the terms self-contained breathing apparatus or 2.1.11 The certification organization shall require manufacturers to
SCBA. (See also 1.5.2.3, Atmosphere-Supplying Respirator, 1.5.2.13, remove all certification labels and product labels indicating
Combination SCBA/SAR, and 1.5.2.43, Self-Contained Breathing compliance with the 1997 edition of NFPA 1981 from all SCBA that
Apparatus.)

475
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
are under the control of the manufacturer on September 1, 2002 and 2.2.13 The certification organization’s operating procedures shall
shall verify this action is taken. provide a mechanism for the manufacturer to appeal decisions. The
procedures shall include the presentation of information from both
2.2 Certification Program. sides of a controversy to a designated appeals panel.

2.2.1* The certification organization shall not be owned or 2.2.14 The certification organization shall be in a position to use legal
controlled by manufacturers or vendors of the product being means to protect the integrity of its name and label.
certified, shall be primarily engaged in certification work, and shall
not have a monetary interest in the product’s ultimate profitability. 2.2.15 The certification organization’s name and label, symbol, or
identifying mark shall be registered and legally defended.
2.2.2 The certification organization shall refuse to certify products to
this standard that do not comply with all requirements of this 2.3* Inspection and Testing.
standard.
2.3.1 For both certification and recertification of SCBA, the
2.2.3* The contractual provisions between the certification certification organization shall conduct both inspection and testing
organization and the manufacturer shall specify that certification is specified in this section.
contingent upon compliance with all applicable requirements of this
standard. 2.3.2 All inspections, evaluations, conditioning, and testing for
certification or for recertification shall be conducted by the
2.2.4 There shall be no conditional, temporary, or partial certification organization or a facility accredited by the certification
certifications. organization for inspections, evaluations, conditioning, and testing in
accordance with all requirements pertaining to testing laboratories in
2.2.5 Manufacturers shall not be authorized to use any label or ISO Guide 25, General Requirements for the Competence of Calibration and
reference to the certification organization on products that are not Testing Laboratories.
manufactured in compliance with all applicable requirements of this
standard. 2.3.3 All inspections, evaluations, conditioning, or testing conducted
by a product manufacturer shall not be used in the certification or
2.2.6* The certification organization shall have available laboratory recertification process unless the facility for inspections, evaluations,
facilities and equipment for conducting proper tests, a program for conditioning, or testing has been accredited by the certification
calibration of all instruments shall be in place and operating, and organization in accordance with all requirements pertaining to
procedures shall be in use to ensure proper control of all testing. testing laboratories in ISO Guide 25, General Requirements for the
Competence of Calibration and Testing Laboratories.
2.2.7 Good practice shall be followed regarding the use of laboratory
manuals, form data sheets, documented calibration and calibration 2.3.4 Sampling levels for testing and inspection shall be established
routines, performance verification, proficiency testing, and staff by the certification organization and the manufacturer to ensure a
qualification and training programs. reasonable and acceptable reliability at a reasonable and acceptable
confidence level that products certified to this standard are
2.2.8 The certification organization shall require the manufacturer to compliant, unless such sampling levels are specified herein.
establish and maintain a program of production inspection and Information about sampling levels shall be provided to the purchaser
testing that meets the requirements of Section 2.5, and shall ensure upon request.
that the quality assurance program provides continued product
compliance with this standard. 2.3.5 SCBA and SCBA components shall be subjected to the tests
specified Table 2.3.5, for each test series.
2.2.9 The certification organization and the manufacturer shall
evaluate any changes affecting the form, fit, or function of the 2.3.5.1 Four identical SCBA that are to be certified to this standard
certified product to determine its continued certification to this shall be selected from the manufacturer’s production.
standard.
2.3.5.2 The first SCBA shall be subjected to the tests listed in
2.2.10* The certification organization shall have a follow-up Category A, the second SCBA shall be subjected to the tests listed in
inspection program of the manufacturing facilities of the certified Category B, the third SCBA shall be subjected to the tests listed in
product, with at least two random and unannounced visits per 12- Category C, and the fourth SCBA shall be subjected to the tests listed
month period. in Category D, as shown in Table 2.3.5.

2.2.10.1 As part of the follow-up inspection program, the 2.3.5.3 Components from SCBA that are to be certified to this
certification organization shall select sample product at random from standard shall be subjected to the tests specified in Category E of
the manufacturer’s production line, from the manufacturer’s in- Table 2.3.5.
house stock, or from the open market.
2.3.6 SCBA shall be initially tested certification and shall meet the
2.2.10.2 Sample product shall be inspected and tested by the performance requirements of three separate test series of Categories
certification organization to verify the product’s continued A, B, C, and D, as specified in Table 2.3.5. All tests within Categories
compliance. A, B, C, and D shall be conducted in the order specified and are
designed as cumulative damage tests.
2.2.11 The certification organization shall have a program for
investigating field reports alleging malperformance or failure of 2.3.7 SCBA fabric, thread, and lens components shall be initially
listed products. tested for certification and shall meet the performance requirements
of one test series of Category E, as specified in Table 2.3.5.
2.2.12* The certification organization shall require the manufacturer
to have a product recall system as part of the manufacturer’s quality
assurance program.

476
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

Table 2.3.5 Test Series


Test Category A Category B Category C Category D Category E
Order (SCBA #1) (SCBA #2) (SCBA #3) (SCBA #4) (Component — Tests)
1 Air flow Air flow Air flow Air flow Fabric flame resistance
Section 6.1 Section 6.1 Section 6.1 Section 6.1 Section 6.4

2 Communications Accelerated Vibration Heat and flame Fabric heat


performance corrosion resistance resistance resistance resistance
Section 6.10 Section 6.7 Section 6.3 Section 6.11 Section 6.5

3 Environmental Thread heat


temp resistance
Section 6.2 Section 6.6

4 Particulate Facepiece lens


resistance abrasion resistance
Section 6.8 Section 6.9

2.3.8 SCBA component testing in Category E shall be conducted on 2.3.13 Any modifications made to an SCBA, or any accessories
test specimens as specified in each respective test method. provided for an SCBA, by the SCBA manufacturer after certification
shall require the retesting and meeting of the performance
2.3.9 After certification, compliant SCBA and components of requirements of all those individual tests that the certification
compliant SCBA shall be tested annually within 12 months from organization determines could be affected by such changes. This
previous tests and shall meet the performance requirements of one retesting shall be conducted before certifying the modified SCBA as
test series of Categories A, B, C, D, and E, as specified in Table 2.3.5. being compliant with this standard.

2.3.9.1 The requirement specified in 2.3.9 shall be waived every fifth 2.3.14 Inspection and evaluation by the certification organization for
year when the testing required by 2.3.9.2 is conducted. determining compliance with the design requirements specified in
Chapter 4 shall be performed on whole and complete products
2.3.9.2 Compliant SCBA shall be tested and shall meet the unless otherwise specified within this standard.
performance requirements of three separate test series of Categories
A, B, C, and D, as specified in Table 2.3.5, every fifth year from the 2.3.15 The certification organization shall report on the compliance
date of the initial certification testing specified in 2.3.6. of SCBA to each design requirement specified in Chapter 4.

2.3.10 The certification organization shall not allow any 2.3.16 Inspection by the certification organization shall include a
modifications, pretreatment, conditioning, or other such special review of all product labels to ensure that all required label
processes of the product or any product component prior to the attachments, compliance statements, certification statements, and
product’s submission for evaluation and testing by the certification other information are at least as specified in Section 3.1.
organization.
2.3.17 Inspection by the certification organization shall include a
2.3.10.1 The certification organization shall accept from the review of any graphic representations used on product labels, as
manufacturer for evaluation and testing for certification only product permitted by 3.1.5, to ensure that the symbols are consistent with the
or product components that are the same in every respect to the worded statements, readily understood, and clearly communicate the
actual final product or product component. intended message.

2.3.10.2 The certification organization shall not allow the 2.3.18 Inspection by the certification organization shall include a
substitution, repair, or modification, other than as specifically review of the user information required by Section 3.2 to ensure that
permitted herein, of any product or any product component during the information has been developed and is available.
testing.
2.3.19 Inspection by the certification organization for determining
2.3.11 No adjustment, repair, or replacement of parts shall be compliance with the design requirements specified in Chapter 4 shall
permitted to any SCBA being tested in accordance with this standard; be performed on whole or complete products.
however, breathing air cylinders shall be permitted to be filled as
required. 2.4 Recertification.

2.3.12 After completion of these tests for a specific model SCBA or its 2.4.1 All SCBA models that are labeled as being compliant with this
variant, only those tests on other similar SCBA models or variants standard shall undergo recertification on an annual basis.
shall be required where, in the determination of the certification
organization, the SCBA’s test results can be affected by any 2.4.2 Recertification shall include inspection and evaluation to all
components or accessories that are different from those on the design requirements and testing to all performance requirements as
original SCBA tested. required by 2.3.4 and 2.3.7 on all manufacturer models and
components.

477
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
2.4.3 The manufacturer shall maintain all design and performance (4) Serial number
inspection and test data from the certification organization used in (5) Lot number, if applicable
the recertification of manufacturer models and components and (6) Hydrostatic test dates and results, if applicable
shall provide such data, upon request, to the purchaser or authority
having jurisdiction. 3.2.3 Information or training materials regarding pre-use shall be
provided at least on the following areas:
2.5 ISO Registration for Manufacturers.
(1) Safety considerations
2.5.1 The manufacturer shall provide and operate a quality assurance (2) Limitations of use
program that meets the requirements of this section and that (3) Charging breathing gas cylinders
includes a product recall system as specified in 2.2.12. (4) Breathing gas quality
(5) Marking recommendations and restrictions
2.5.2 The manufacturer shall be registered to ISO 9001, Quality (6) Warranty information
Systems — Model for Quality Assurance in Design, Development, Production, (7) Recommended storage practices
Installation, and Servicing. (8) Mounting on/in vehicles or fire apparatus

Chapter 3 Labeling and Information 3.2.4 Information or training materials regarding periodic
inspections shall be provided at least on inspection frequency and
3.1 Product Label Requirements. details.

3.1.1 In addition to the NIOSH certification label, each SCBA shall 3.2.5 Information or training materials regarding donning and
have a product label permanently and conspicuously attached to the doffing shall be provided at least on the following areas:
SCBA.
(1) Donning and doffing procedures
3.1.2 Multiple label pieces shall be permitted in order to carry all (2) Adjustment procedures
statements and information required to be on the product label; (3) Interface issues
however, all label pieces comprising the product label shall be
located adjacent to each other. 3.2.6 Information or training materials regarding use shall be
provided at least on the following areas:
3.1.3 The certification organization’s label, symbol, or identifying
mark shall be attached to the product label or be part of the product (1) Pre-use checks
label and shall be placed in a conspicuous location. All letters shall (2) Proper use consistent with NFPA 1500, Standard on Fire
be at least 2.5 mm in height and the label, symbol, or identifying Department Occupational Safety and Health Program
mark shall be at least 6 mm in height. (3) Recharging breathing gas cylinders

3.1.4 All worded portions of the required product label shall be at 3.2.7* Information or training materials regarding periodic
least in English. maintenance and cleaning shall be provided at least on the following
areas:
3.1.5 Symbols and other pictorial graphic representations shall be
permitted to be used to supplement worded statements on the (1) Cleaning instructions and precautions
product label(s). (2) Disinfecting procedures
(3) Maintenance frequency and details
3.1.6 The following compliance statement shall be legibly printed on (4) Methods of repair, where applicable
the product label, and all letters and numbers shall be at least 2 mm
in height: 3.2.8 Information or training materials regarding retirement shall be
provided at least on replacement/retirement considerations.
THIS SCBA MEETS THE REQUIREMENTS OF NFPA 1981,
STANDARD ON OPEN-CIRCUIT SELF-CONTAINED BREATHING Chapter 4 Design Requirements
APPARATUS FOR FIRE AND EMERGENCY SERVICES, 2002
EDITION. 4.1 General.

3.1.7 SCBA components, as listed on the NIOSH certification labels, 4.1.1 SCBA shall have at least the applicable design requirements
shall be marked directly on the component with either the lot specified in this chapter where inspected by the certification
number, serial number, or year and month of manufacture. organization as specified in Section 2.3.

3.2 User Information. 4.1.2 All SCBA shall be equipped with a full facepiece that covers, as
a minimum, the wearer’s eyes, nose, and mouth.
3.2.1 The SCBA manufacturer shall provide at least the training
material and user instructions specified within this section with each 4.1.3 In order to label or otherwise represent an SCBA as compliant
SCBA. with this standard, the SCBA manufacturer shall have available not
less than three separate and distinct facepieces sizes for each model
3.2.2 Upon request at the time of purchase, the manufacturer shall of compliant SCBA.
provide to the purchaser an information sheet with each SCBA that
documents at least the following: 4.1.4 All electric circuits integral to an SCBA, or to any SCBA
accessories, shall meet the requirements for Class I, Division I
(1) Manufacturing performance tests conducted at time of hazardous locations specified in ANSI/UL 913, Standard for
manufacture, and the results Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II,
(2) Date of manufacture and III, Division I Hazardous Locations.
(3) Model number

478
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
4.1.5 All hardware, brackets, and snaps or other fasteners of SCBA or 4.3.6 While the SCBA is activated, the heads-up display shall be
any accessories shall be free of rough spots, burrs, or sharp edges. visible to the wearer in darkness, smoke, and bright sunlight.

4.2 End-of-Service-Time Indicator (EOSTI). 4.3.7 All heads-up display visual alert signals shall be easily
distinguishable by the SCBA wearer from any other visual alert
4.2.1 All SCBA shall be equipped with a minimum of two signal(s) provided on the heads-up display or on the SCBA.
independent EOSTI.
4.3.8 The heads-up display shall show cylinder pressure in one of the
4.2.2 Each EOSTI shall be activated with no further procedures than following:
those required to activate the SCBA breathing system.
(1) Pounds per square inch
4.2.3 Each EOSTI shall meet the activation requirements of NIOSH (2) Bars
certification as specified in 42 CFR 84. (3) Fractions of total cylinder capacity
(4) Any combination of the above
4.2.4 Each EOSTI shall at least consist of an independent sensing
mechanism and a signaling device. 4.3.9 The heads-up display shall show a visual alert signal when the
breathing air in the SCBA cylinder has reduced to 50 percent of full
4.2.4.1 The EOSTI independent sensing mechanism shall activate cylinder capacity.
the signaling device(s).
4.3.10 The heads-up display shall continuously show the visual alert
4.2.4.2 The EOSTI signaling devices shall provide notification to the signal specified in 4.3.8 from 50 percent of full cylinder capacity
SCBA user of the activation of the EOSTI by stimulating one or more down to at least 20 percent of full cylinder capacity.
human senses.
4.3.11 Where the heads-up display is operated by battery power, a
4.2.4.3 Each EOSTI shall be permitted to have more than one visual alert signal to indicate low battery condition shall show on the
signaling device and each signaling device shall be permitted to heads-up display.
stimulate more than one human sense.
4.4 Emergency Air Flow System.
4.2.4.4 Each of the two EOSTI specified in 4.2.1 shall have a
signaling device that stimulates a different human sense than is 4.4.1 All SCBA that are provided with a regulator that operates with
stimulated by the other signaling device. an inlet pressure at or below 35 bar (520 psi) shall be equipped with
an emergency air flow system.
4.2.5 The design of EOSTI shall be such that the failure of one
EOSTI shall not affect the activation and operation of other EOSTI. 4.4.2 The system shall provide breathing air flow to the user in the
event that the SCBA regulator fails in either the closed mode, where
4.2.5.1 A failure mode and effects analysis shall be provided to the air is prevented from flowing through the regulator at more than 100
certification organization for each EOSTI. L/min, ±3 L/min; or fails in open mode, where air flows without
control through the regulator.
4.2.5.2 The failure mode and effects analysis shall identify each
potential failure mode for each component necessary for the EOSTI 4.4.3 The system shall have a user-operated control to isolate the
to function. SCBA regulator in the event of a fail-open mode.

4.2.5.3 The failure mode and effects analysis shall demonstrate that 4.4.3.1 The user-operated control shall be located so that it is easily
the activation and operation of both EOSTI specified in 4.2.1 is not accessible by the SCBA wearer and shall be located on the SCBA in a
affected by any of the potential failure modes, as identified in position that places the control on the front or side of the SCBA
accordance with 4.2.5.2, of all other EOSTI. wearer’s upper body when the SCBA is properly donned in
accordance with the manufacturer’s instructions.
4.2.5.4 For purposes of the failure mode and effects analysis, power
sources other than the air from the SCBA cylinder shall be 4.4.3.2 The user-operated control shall not be located in a position
considered as part of the EOSTI. that would place it in excess of 150 mm (6 in.) below the SCBA
wearer’s waist.
4.3 Facepiece Heads-Up Display.
4.4.3.3 The user-operated control shall be capable of being operated
4.3.1 All SCBA facepieces shall be equipped with at least one heads- while the SCBA wearer is wearing gloves that are certified as
up display. compliant with NFPA 1971, Standard on Protective Ensemble for Structural
Fire Fighting.
4.3.2 The heads-up display shall be activated with no further
procedures than those required to activate the SCBA breathing 4.4.4 The system in the full-open position shall be capable of
system. providing breathing air to the SCBA wearer between a maximum flow
of 250 L/min and a minimum of 100 L/min.
4.3.3 The heads-up display shall provide a visual display of
information and system condition status for at least the cylinder air 4.4.5 All hose and connections leading to the SCBA regulator shall
pressure. withstand the pressure of the SCBA’s fully charged breathing air
cylinder without leakage or failure if any other upstream regulators
4.3.4 The heads-up display shall be located ±125 mm (±5 in.) in any fail in the open mode.
direction as measured from the center of the facepiece lens.
4.5 Accessories.
4.3.5 The heads-up display shall be visible to the SCBA wearer
regardless of wearer’s head movement.

479
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
4.5.1 Any accessories attached to SCBA shall not interfere with the 5.6 Thread Heat Resistance Performance. All thread used in SCBA
function of the SCBA or with the function of any of the SCBA’s components shall be tested for heat resistance as specified in Section
component parts. 6.6, Thread Heat Test, and shall not melt or ignite.

4.5.2 Where SCBA are provided with an accessory or accessories that 5.7 Accelerated Corrosion Resistance Performance.
are attached to or integrated with the SCBA, the SCBA, with
accessories installed, shall meet all of the design and performance 5.7.1 SCBA shall be tested for corrosion resistance as specified in
requirements of this standard. In all cases, such accessories shall not Section 6.7, Accelerated Corrosion Test, and any corrosion shall not
degrade the performance of the SCBA. prohibit the proper use and function as specified in the
manufacturer’s instructions of any control or operating feature of the
Chapter 5 Performance Requirements SCBA.

5.1* Air Flow Performance. SCBA shall be tested for air flow 5.7.2 In addition, the SCBA facepiece pressure shall not be less than
performance as specified in Section 6.1, Air Flow Performance Test, 0.00 mm (0.0 in.) water column and shall not be greater than 89 mm
and the SCBA facepiece pressure shall not be less than 0.0 mm (0.0 (3 ½ in.) water column above ambient pressure from the time the air
in.) water column and shall not be greater than 89 mm (3 ½ in.) flow test begins until the time the test is concluded.
water column above ambient pressure from the time the test begins
until the time the test is concluded. 5.8 Particulate Resistance Performance. SCBA shall be tested for
particulate resistance as specified in Section 6.8, Particulate Test, and
5.2 Environmental Temperature Performance. the SCBA facepiece pressure shall not be less than 0.00 mm (0.0 in.)
water column and shall not be greater than 89 mm (3 ½ in.) water
5.2.1 SCBA shall be tested for environmental temperature column above ambient pressure from the time the air flow test begins
performance as specified in Section 6.2, Environmental Temperature until the time the test is concluded.
Tests.
5.9* Facepiece Lens Abrasion Resistance Performance. SCBA
5.2.1.1 SCBA shall be tested for cold environment as specified in facepiece lenses shall be tested for abrasion resistance as specified in
6.2.5.2, Test 1, and the SCBA facepiece pressure shall not be less than Section 6.9, Facepiece Lens Abrasion Test, and the average value of
0.00 mm (0.0 in.) water column and shall not be greater than 89 mm the tested specimens shall not exhibit a delta haze greater than 14
(3 ½ in.) water column above ambient pressure from the time the air percent.
flow test begins until the time the test is concluded.
5.10* Communications Performance. SCBA incorporating specimens
5.2.1.2 SCBA shall be tested for hot environment as specified in of the SCBA’s primary communication means, as identified by the
6.2.5.3, Test 2, and the SCBA facepiece pressure shall not be less than SCBA manufacturer, shall be tested for communications
0.00 mm (0.0 in.) water column and shall not be greater than 89 mm performance as specified in Section 6.10, Communication Test, and
(3 ½ in.) water column above ambient pressure from the time the air shall have an average calculated value of not less than 72 percent.
flow test begins until the time the test is concluded.
5.11 Heat and Flame Resistance Performance.
5.2.1.3 SCBA shall be tested for hot-to-cold environment as specified
in 6.2.5.4, Test 3, and the SCBA facepiece pressure shall not be less 5.11.1 SCBA shall be tested for heat and flame resistance as specified
than 0.00 mm (0.0 in.) water column and shall not be greater than 89 in Section 6.11, Heat and Flame Test, and the SCBA facepiece
mm (3 ½ in.) water column above ambient pressure from the time pressure shall not be less than 0.00 mm (0.0 in.) water column and
the air flow test begins until the time the test is concluded. shall not be greater than 89 mm (3 ½ in.) water column above
ambient pressure from the time the test begins until the time the test
5.2.1.4 SCBA shall be tested for cold-to-hot environment as specified is concluded.
in 6.2.5.5, Test 4, and the SCBA facepiece pressure shall not be less
than 0.00 mm (0.0 in.) water column and shall not be greater than 89 5.11.2 SCBA and SCBA accessories shall be tested for heat and flame
mm (3 ½ in.) water column above ambient pressure from the time resistance as specified in Section 6.11, Heat and Flame Test, and no
the test begins until the time the air flow test is concluded. components of the SCBA and no accessories shall have an afterflame
of more than 2.2 seconds.
5.3 Vibration Resistance Performance. SCBA shall be tested for
vibration resistance as specified in Section 6.3, Vibration Tests, and 5.11.3 SCBA shall be tested for heat and flame resistance as specified
the SCBA facepiece pressure shall not be less than 0.00 mm (0.0 in.) in Section 6.11, Heat and Flame Test, and no component of the
water column and shall not be greater than 89 mm (3 ½ in.) water SCBA shall separate or fail in such a manner that would cause the
column above ambient pressure from the time the air flow test begins SCBA to be worn and used in a position not specified by the
until the time the test is concluded. manufacturer’s instructions.

5.4 Fabric Flame Resistance Performance. All fabric components of 5.11.4 The SCBA facepiece shall be tested for heat and flame
SCBA that are used to secure the SCBA to the wearer shall be tested resistance as specified in Section 6.11, Heat and Flame Test, and the
for flame resistance as specified in Section 6.4, Fabric Flame Tests, facepiece lens shall not obscure vision below the 20/100 vision
and shall have an average char length of not more than 100 mm (4 criterion.
in.), shall not have an average afterflame of more than 2.0 seconds,
and shall not melt or drip. 5.12 Redundant End of Service Time Indicator Performance.

5.5 Fabric Heat Resistance Performance. All fabric components of 5.12.1 SCBA shall be tested for airflow resistance as specified in
SCBA that are used to secure the SCBA to the wearer shall be tested Section 6.12, Redundant End of Service Time Indicator Airflow Test,
for heat resistance as specified in Section 6.5, Fabric Heat Tests, and and the SCBA facepiece pressure shall not be less than 0.00 mm (0.0
shall not melt or ignite. in.) water column and shall not be greater than 89 mm (3 ½ in.)
water column above ambient pressure from the time the test begins
until the time the test is concluded.

480
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
5.12.2 After actuation of the unblocked end of service time indicator, 6.1.4.5 The open end of the pressure probe shall extend a maximum
the indicator shall remain activated for a minimum of 30 cycles of the of 450 mm (18 in.) and a minimum of 25 mm (1 in.) outward from
breathing machine. the back surface of the test headform.

5.13 Facepiece Carbon Dioxide Content Performance. Specimen 6.1.4.6 A maximum of a 1.5 m (5-ft) length of nominal 5 mm (0.188
SCBA facepieces shall be tested for carbon dioxide content as in.) I.D. flexible smoothbore tubing with a nominal 1.5-mm (0.062-
specified in Section 6.13, Facepiece Carbon Dioxide Content Test, in.) wall thickness shall be permitted to be connected from the open
and the carbon dioxide content of the inhalation air shall not exceed end of the pressure probe to the inlet of the pressure transducer.
an average of 1.5 percent (by volume).
6.1.4.7 A differential pressure transducer having the following
Chapter 6 Test Methods characteristics shall be used:

6.1 Air Flow Performance Test. (a) Range: –125 mm (–5 in.) to 125 mm (5 in.) of water
column
6.1.1 Application. This test method shall apply to complete SCBA. (b) Temperature range: 5°C to 45°C (41°F to 113°F)
(c) Combined error (linearity, hysteresis, repeatability): ±0.25
6.1.2 Specimens. Each specimen to be tested shall be as specified in mm (±0.1 in.) water column
2.3.1. (d) Frequency response: 50 Hz.

6.1.3 Specimen Preparation. 6.1.4.8 The differential pressure transducer shall be connected to a
pressure recording system.
6.1.3.1 Specimens for conditioning shall be complete SCBA.
6.1.4.9 The pressure recording system shall have a frequency
6.1.3.2 Prior to testing, specimens shall be conditioned for a response equivalent to a low pass filter with a 3dB corner frequency
minimum of 4 hours at an ambient temperature of 22°C, ±3°C (72°F, of 5.0 Hz.
±5°F), with a relative humidity (RH) of 50 percent, ±25 percent.
6.1.4.10 The test headform shall be equipped with a breathing
6.1.3.3* The air used in the SCBA breathing air cylinders shall have a passage.
minimum air quality of Grade D as specified in ANSI/CGA G-7.1,
Commodity Specification for Air, and shall have a water content not 6.1.4.10.1 The breathing passage shall lead from the mouth of the
exceeding 24 ppm by volume and shall have a maximum particulate test head to the lung.
3
level of 5 mg/m air.
6.1.4.10.2 The sum of the volumes of the lung, when fully extended
6.1.4 Apparatus. to a 3.4 L tidal volume position, and the breathing passage shall not
exceed 4.0 L.
6.1.4.1 A test head form as specified in Figure 6.1.4.1, or equivalent,
shall be used. 6.1.4.10.3 The breathing passage shall be located on the centerline of
the mouth and shall be flush with the test headform.
R3.0

6.1.4.11 The breathing passage shall extend a minimum of 200 mm


0.25 (8 in.) and a maximum of 450 mm (18 in.).

6.1.4.12 Where flexible smoothbore tubing is used from the metal


13.7
breathing tube to the inlet connection of the breathing machine, it
shall have a maximum length of 1.2 m (4 ft) and a 19-mm (¾-in.) I.D.
with nominal 3-mm (1/8-in.) wall thickness.
01.50

6.1.4.13 The breathing machine shown in Figure 6.1.4.13 shall be


used.
09.8 01.6

6.1.4.13.1 The breathing machine shall consist of a flexible bellows


material attached at one end to a fixed plate and at the other end by
Figure 6.1.4.1 Test headform. a free plate constrained to two degrees of freedom.

6.1.4.2 A pressure probe shall be attached to the test headform to 6.1.4.13.2 The free plate shall be connected to a rotating shaft by
monitor facepiece pressure. The pressure probe shall be a 6.5 mm (¼ means of a connecting rod, vibration dampener, and bell crank
in.) O.D. with a 1.6-mm (0.062-in.) wall thickness metal tube having mechanism.
one open end and one closed end. The closed end shall have four
equally spaced holes, each 1.5 mm ±0.1 mm (0.062 in. ±0.005 in.), 6.1.4.13.3 The bell crank mechanism shall have a center to center
and each shall be positioned 6.5 mm ±0.4 mm (¼ in. ±0.02 in.) from distance of 57 mm ±0.005 mm (2¼ in. ±0.01 in.).
the end of the pressure probe.
6.1.4.13.4 The connecting rod shall have a center to center free plate
6.1.4.3 The closed end of the pressure probe shall extend through distance of 133 mm ±0.005mm (5¼ in. ±0.01 in.).
the test head form, exiting out the center of the left eye.
6.1.4.13.5 The vibration dampener shall be a rubber to metal bonded
6.1.4.4 The pressure probe shall extend 13 mm +1.5/-0 mm (½ in. anti-vibration mounting with a mounting flange hole spacing of 50
+0.06/-0.0 in.) outward from the surface of the center of the left eye. mm ±5 mm (2 in. ±0.2 in.) and an overall height of 20 mm ±2 mm
(0.8 in. ±0.08 in.) and have a static force/displacement curve with a
slope of 11.5 N/mm ±0.5 N/mm.

481
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.1.4.13.12 Switching between the two work rates shall be performed
within 10 seconds.
Test head form
6.1.4.13.13 The construction of the breathing machine shall be such
that the respiration rate, tidal volume, peak flow, and facepiece
Static pitot tube
pressure measurement system accuracy is unaffected by temperature
changes caused by the environmental air flow performance tests as
specified in Section 6.2.

Table 6.1.4.13.11(a) Lung Breathing Waveforms for 103 L/min


Breathing Volume Work Rate
passages Step # Time (sec) Inspire/Expire Volume (L) Volume change (L)
+/- 0.1 +/- 5%

0 0.00 — -1.7 -0.012


1 0.02 Inspire -1.688 0.012
2 0.04 Inspire -1.662 0.025
3 0.06 Inspire -1.626 0.036
4 0.08 Inspire -1.581 0.045
5 0.10 Inspire -1.529 0.052
Fixed plate 6 0.12 Inspire -1.471 0.058
7 0.14 Inspire -1.409 0.062
Bellows material
8 0.16 Inspire -1.345 0.064
9 0.18 Inspire -1.277 0.068
10 0.20 Inspire -1.207 0.07
11 0.22 Inspire -1.134 0.073
Free plate 12 0.24 Inspire -1.059 0.075
13 0.26 Inspire -0.984 0.076
Connecting rod
14 0.28 Inspire -0.906 0.077
15 0.30 Inspire -0.828 0.079
Bellows crank
mechanism 16 0.32 Inspire -0.748 0.08

Figure 6.1.4.13 Breathing machine. 17 0.34 Inspire -0.667 0.081


18 0.36 Inspire -0.586 0.081
6.1.4.13.6 The bellows material shall consist of neoprene 19 0.38 Inspire -0.504 0.082
impregnated nylon fabric convoluted tubing.
20 0.40 Inspire -0.421 0.083
6.1.4.13.6.1 The tubing shall have an inner diameter of 203 mm 21 0.42 Inspire -0.337 0.084
±0.05 mm (8 in. ±0.2 in.) and an outer diameter of 250 mm ±0.05 22 0.44 Inspire -0.254 0.084
mm (10 in. ±0.2 in.).
23 0.46 Inspire -0.169 0.085
6.1.4.13.6.2 The nominal wall thickness of the tubing shall be 0.014 24 0.48 Inspire -0.085 0.085
mm ±0.0013 mm (0.055 in. ±0.005 in.). 25 0.50 Inspire 0 0.085
26 0.52 Inspire 0.085 0.085
6.1.4.13.7 The breathing machine shall conduct breathing resistance
testing at 40 L/min ±1.0 L/min and 103 L/min ±3.0 L/min minute 27 0.54 Inspire 0.169 0.085
liter. 28 0.56 Inspire 0.254 0.085
29 0.58 Inspire 0.337 0.084
6.1.4.13.8 The tidal volume of the lung shall determine the volume
of air moved during each inhalation/exhalation cycle. 30 0.60 Inspire 0.421 0.084
31 0.62 Inspire 0.504 0.083
6.1.4.13.9 The air flow shall be determined by three factors, the
32 0.64 Inspire 0.586 0.082
number of inhalation/exhalation cycles per minute, the tidal volume
of the lung, and the breathing waveform. 33 0.66 Inspire 0.667 0.081
34 0.68 Inspire 0.748 0.081
6.1.4.13.10 The breathing waveforms shall be produced by reciprocal 35 0.70 Inspire 0.828 0.08
action of the shaft.
36 0.72 Inspire 0.906 0.079
6.1.4.13.11 Inspired and expired volumes as a function of time shall 37 0.74 Inspire 0.984 0.077
be in accordance with the values given in Tables 6.1.4.13.11(a) and 38 0.76 Inspire 1.059 0.076
6.1.4.13.11(b), which list the linear displacement of the bellows free
plate as a function of time for 103 L/min volume and 40 L/min 39 0.78 Inspire 1.134 0.075
volume work rates. 40 0.80 Inspire 1.207 0.073
41 0.82 Inspire 1.277 0.07

482
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
Step # Time (sec) Inspire/Expire Volume (L) Volume change (L) Step # Time (sec) Inspire/Expire Volume (L) Volume change (L)
+/- 0.1 +/- 5% +/- 0.1 +/- 5%

42 0.84 Inspire 1.345 0.068 92 1.84 Expire -1.345 -0.068


43 0.86 Inspire 1.409 0.064 93 1.86 Expire -1.409 -0.064
44 0.88 Inspire 1.471 0.062 94 1.88 Expire -1.471 -0.062
45 0.90 Inspire 1.529 0.058 95 1.90 Expire -1.529 -0.058
46 0.92 Inspire 1.581 0.052 96 1.92 Expire -1.581 -0.052
47 0.94 Inspire 1.626 0.045 97 1.94 Expire -1.626 -0.045
48 0.96 Inspire 1.662 0.036 98 1.96 Expire -1.662 -0.036
49 0.98 Inspire 1.688 0.025 99 1.98 Expire -1.688 -0.025
50 1.00 — 1.7 0.012
51 1.02 Expire 1.688 -0.012
52 1.04 Expire 1.662 -0.025
Table 6.1.4.13.11(b) Lung Breathing Waveforms for 40 L/min Volume Work
53 1.06 Expire 1.626 -0.036 Rate
54 1.08 Expire 1.581 -0.045 Step # Time (sec) Inspire/Expire Volume (L) Volume change (L)
+/- 0.1 +/- 5%
55 1.10 Expire 1.529 -0.052

56 1.12 Expire 1.471 -0.058 0 0 -0.833 0.001
Inspire
57 1.14 Expire 1.409 -0.062 1 0.025 -0.831 0.002
Inspire
58 1.16 Expire 1.345 -0.064 2 0.050 -0.825 0.005
Inspire
59 1.18 Expire 1.277 -0.068 3 0.075 -0.816 0.009
Inspire
60 1.20 Expire 1.207 -0.07 4 0.100 -0.803 0.013
Inspire
61 1.22 Expire 1.134 -0.073 5 0.125 -0.787 0.016
Inspire
62 1.24 Expire 1.059 -0.075 6 0.150 -0.768 0.019
Inspire
63 1.26 Expire 0.984 -0.076 7 0.175 -0.745 0.022
64 1.28 Expire 0.906 -0.077 Inspire
8 0.200 -0.720 0.025
65 1.30 Expire 0.828 -0.079 Inspire
9 0.225 -0.692 0.028
66 1.32 Expire 0.748 -0.08 Inspire
10 0.250 -0.661 0.031
67 1.34 Expire 0.667 -0.081 Inspire
11 0.275 -0.628 0.033
68 1.36 Expire 0.586 -0.081 Inspire
12 0.300 -0.592 0.035
69 1.38 Expire 0.504 -0.082 Inspire
13 0.325 -0.555 0.038
70 1.40 Expire 0.421 -0.083 Inspire
14 0.350 -0.515 0.039
71 1.42 Expire 0.337 -0.084 Inspire
15 0.375 -0.474 0.041
72 1.44 Expire 0.254 -0.084 Inspire
16 0.400 -0.431 0.043
73 1.46 Expire 0.169 -0.085 Inspire
17 0.425 -0.387 0.044
74 1.48 Expire 0.085 -0.085 Inspire
18 0.450 -0.341 0.046
75 1.50 Expire 0 -0.085 Inspire
19 0.475 -0.295 0.047
76 1.52 Expire -0.085 -0.085 Inspire
20 0.500 -0.247 0.048
77 1.54 Expire -0.169 -0.085 Inspire
21 0.525 -0.198 0.049
78 1.56 Expire -0.254 -0.085 Inspire
22 0.550 -0.149 0.049
79 1.58 Expire -0.337 -0.084 Inspire
23 0.575 -0.100 0.050
80 1.60 Expire -0.421 -0.084 Inspire
24 0.600 -0.050 0.050
81 1.62 Expire -0.504 -0.083 Inspire
25 0.625 0.000 0.050
82 1.64 Expire -0.586 -0.082 Inspire
26 0.650 0.051 0.050
83 1.66 Expire -0.667 -0.081 Inspire
27 0.675 0.100 0.050
84 1.68 Expire -0.748 -0.081 Inspire
28 0.700 0.150 0.050
85 1.70 Expire -0.828 -0.08 Inspire
29 0.725 0.199 0.049
86 1.72 Expire -0.906 -0.079 Inspire
30 0.750 0.248 0.048
87 1.74 Expire -0.984 -0.077 Inspire
31 0.775 0.295 0.048
88 1.76 Expire -1.059 -0.076 Inspire
32 0.800 0.342 0.047
89 1.78 Expire -1.134 -0.075 Inspire
33 0.825 0.388 0.046
90 1.80 Expire -1.207 -0.073 Inspire
34 0.850 0.432 0.044
91 1.82 Expire -1.277 -0.07 Inspire
35 0.875 0.475 0.043

483
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
Step # Time (sec) Inspire/Expire Volume (L) Volume change (L) Step # Time (sec) Inspire/Expire Volume (L) Volume change (L)
+/- 0.1 +/- 5% +/- 0.1 +/- 5%

Inspire Expire
36 0.900 0.516 0.041 85 2.125 -0.475 -0.043
Inspire Expire
37 0.925 0.555 0.039 86 2.150 -0.516 -0.041
Inspire Expire
38 0.950 0.592 0.037 87 2.175 -0.555 -0.039
Inspire Expire
39 0.975 0.628 0.035 88 2.200 -0.592 -0.037
Inspire Expire
40 1.000 0.661 0.033 89 2.225 -0.628 -0.035
Inspire Expire
41 1.025 0.691 0.031 90 2.250 -0.661 -0.033
Inspire Expire
42 1.050 0.719 0.028 91 2.275 -0.691 -0.031
Inspire Expire
43 1.075 0.744 0.025 92 2.300 -0.719 -0.028
Inspire Expire
44 1.100 0.767 0.022 93 2.325 -0.744 -0.025
Inspire Expire
45 1.125 0.786 0.019 94 2.350 -0.767 -0.022
Inspire Expire
46 1.150 0.802 0.016 95 2.375 -0.786 -0.019
Inspire Expire
47 1.175 0.814 0.013 96 2.400 -0.802 -0.016
Inspire Expire
48 1.200 0.823 0.009 97 2.425 -0.814 -0.013
Inspire Expire
49 1.225 0.829 0.005 98 2.450 -0.823 -0.009
— Expire
50 1.250 0.833 0.004 99 2.475 -0.829 -0.005
Expire
51 1.275 0.831 -0.002
Expire 6.1.5 Procedure.
52 1.300 0.825 -0.005
Expire
53 1.325 0.816 -0.009 6.1.5.1* The test setup for conducting the air flow performance test
Expire shall be calibrated at least once each day before conducting tests and
54 1.350 0.803 -0.013
Expire shall be verified at least once each day after testing.
55 1.375 0.787 -0.016
Expire
56 1.400 0.768 -0.019 6.1.5.1.1 The calibration procedure utilized for the differential
Expire pressure transducer shall consist of confirming at least three different
57 1.425 0.745 -0.022
Expire pressures between 0 mm and 125 mm (0 in. and 5 in.) water column.
58 1.450 0.720 -0.025
Expire 6.1.5.1.2 The pressure shall be measured using an incline
59 1.475 0.692 -0.028
Expire manometer or equivalent with a scale measuring in increments of
60 1.500 0.661 -0.031
Expire ±0.5 mm (±0.02 in.) water column or less.
61 1.525 0.628 -0.033
Expire 6.1.5.2 The SCBA being tested shall utilize a fully charged breathing
62 1.550 0.592 -0.035
Expire air cylinder.
63 1.575 0.555 -0.038
Expire
64 1.600 0.515 -0.039 6.1.5.3 The facepiece of the SCBA being tested shall be secured to
Expire the test headform. The facepiece seal to the headform shall assure
65 1.625 0.474 -0.041
Expire that an initial pressure of 25 mm ±2.5 mm (1 in. ±0.1 in.) water
66 1.650 0.431 -0.043
column below ambient shall not decay by more than 5 mm (0.2 in.)
Expire
67 1.675 0.387 -0.044 water column in 5 seconds.
Expire
68 1.700 0.341 -0.046
Expire 6.1.5.4 The remaining components of the SCBA shall be mounted in
69 1.725 0.295 -0.047 accordance with Figure 6.1.5.4 to simulate the proper wearing
Expire
70 1.750 0.247 -0.048 position as specified by the manufacturer’s instructions.
Expire
71 1.775 0.198 -0.049
Expire Existing Figure 6.1.2 (no change)
72 1.800 0.149 -0.049 Figure 6.1.5.4 Typical breathing machine configuration for air flow
Expire
73 1.825 0.100 -0.050 performance test.
Expire
74 1.850 0.050 -0.050
Expire 6.1.5.5 SCBA shall be tested at an ambient temperature of 22°C ±3°C
75 1.875 0.000 -0.050 (72°F ±5°C), RH of 50 percent ±25 percent.
Expire
76 1.900 -0.051 -0.050
Expire 6.1.5.6 The air flow performance test shall begin after five cycles of
77 1.925 -0.100 -0.050
Expire the breathing machine and continue to operate through at least 30
78 1.950 -0.150 -0.050 cycles of the breathing machine after actuation of each end-of-
Expire service-time indicator specified in Section 4.2.
79 1.975 -0.199 -0.049
Expire
80 2.000 -0.248 -0.048
Expire
6.1.6 Report. The facepiece peak inhalation pressure and peak
81 2.025 -0.295 -0.048 exhalation pressure shall be reported for each test.
Expire
82 2.050 -0.342 -0.047
Expire 6.1.7 Interpretation.
83 2.075 -0.388 -0.046
Expire
84 2.100 -0.432 -0.044

484
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.1.7.1 The peak inhalation pressure and peak exhalation pressure 6.2.5.3.2 The SCBA shall then be tested for air flow performance as
shall be used to determine pass/fail performance. specified in Section 6.1 at a chamber air temperature of 160°F ±10°F
(71°C ±5°C).
6.1.7.2 One or more specimens failing this test shall constitute failing
performance. 6.2.5.3.3 The air flow performance test shall commence within 3
minutes after removal from hot soak.
6.2 Environmental Temperature Tests.
6.2.5.4 Test 3.
6.2.1 Application. This test method shall apply to complete SCBA.
6.2.5.4.1 The SCBA shall be hot soaked at 71°C ±1°C (160°F ±2°F)
6.2.2 Specimens. Each specimen to be tested shall be as specified in for a minimum of 12 hours.
2.3.1.
6.2.5.4.2 Immediately following the 12 hour hot soak, the SCBA shall
6.2.3 Sample Preparation. be transferred to a chamber with an air temperature of -32°C ±1°C
(-25°F ±2°F).
6.2.3.1 Specimens for conditioning shall be complete SCBA.
6.2.5.4.3 The SCBA shall then be tested for air flow performance as
6.2.3.2 After performing each test, the SCBA shall be placed in an specified in Section 6.1 at a chamber air temperature of -32°C ±5°C (-
ambient environment of 22°C ±3°C (72°F ±5°F) with a relative 25°F ±10°F).
humidity of 50 percent ±25 percent for a minimum 12-hour dwell
period. 6.2.5.4.4 The air flow performance test shall commence within 3
minutes after removal from hot soak.
6.2.4 Apparatus.
6.2.5.5 Test 4.
6.2.4.1 The SCBA shall be placed in an environmental chamber and
positioned to simulate the normal wearing position of the SCBA on a 6.2.5.5.1 The SCBA shall be cold soaked at -32°C ±1°C (-25°F ±2°F)
fire fighter as specified by the manufacturer. for a minimum of 12 hours.

6.2.4.2 A test headform as specified in 6.1.4 shall be equipped with a 6.2.5.5.2 Immediately following the 12 hour cold soak, the SCBA
thermocouple or other temperature-sensing element to monitor shall be transferred to a chamber with an air temperature of 71°C
SCBA test chamber temperature. ±1°C (160°F ±2°F).

6.2.4.3 The thermocouple or other temperature-sensing element 6.2.5.5.3 The SCBA shall then be tested for air flow performance as
used shall be attached to the test headform in a manner in which it specified in Section 6.1 at a chamber air temperature of 71°C ±1°C
will be directly exposed to the chamber atmosphere. (160°F ±2°F).

6.2.4.4 The test headform shall be connected to the breathing 6.2.5.5.4 The air flow performance test shall commence within 3
machine specified in Section 6.1. minutes after removal from cold soak.

6.2.4.5 The breathing machine shall be permitted to be located 6.2.6 Report. The facepiece peak inhalation pressure and peak
either inside or outside the environmental chamber. exhalation pressure shall be reported for each test condition.

6.2.5 Procedure. 6.2.7 Interpretation.

6.2.5.1 These environmental temperature tests shall be permitted to 6.2.7.1 The peak inhalation and peak exhalation shall be used to
be conducted in any sequence. determine pass or fail performance for each test procedure.

6.2.5.1 The dwell period between environmental temperature tests 6.2.7.2 One or more specimens failing any test procedure shall
shall be used for refilling the breathing air cylinder and visually constitute failing performance.
inspecting the SCBA for any gross damage that could cause unsafe
test conditions. 6.3 Vibration Test.

6.2.5.2 Test 1. 6.3.1 Application. This test method shall apply to complete SCBA.

6.2.5.2.1 The SCBA shall be cold soaked at -32°C ±1°C (-25°F ±2°F) 6.3.2 Specimens. Specimens for conditioning shall be complete
for a minimum of 12 hours. SCBA.

6.2.5.2.2 The SCBA shall then be tested for air flow performance as 6.3.3* Sample Preparation.
specified in Section 6.1 at a chamber air temperature of -32°C ±1°C (-
25°F ±2°F). 6.3.3.1 Each specimen to be tested shall be as specified in 2.3.1.

6.2.5.2.3 The air flow performance test shall commence within 3 6.3.3.2 Prior to testing, specimens shall be conditioned for a
minutes after removal from cold soak. minimum of 4 hours and tested at an ambient temperature of 22°C
±3°C (72°F ±5°F), with a RH of 50 percent ±25 percent.
6.2.5.3 Test 2.
6.3.4 Apparatus.
6.2.5.3.1 The SCBA shall be hot soaked at 71°C ±1°C (160°F ±2°F)
for a minimum of 12 hours.

485
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.3.4.1 SCBA shall be tested on a typical package tester similar to substitute mass. The substitute mass shall consist of a brass rod and
that shown in Figure 6.3.4.1, within the compartments specified in surrounding foam constructed as shown in Figure 6.3.4.8.
6.3.4.2 through 6.3.4.4.
Existing Figure 6-3.3.2 (no change)
(Figure not submitted) Figure 6.3.4.8 Surrogate cylinder.

6.3.4.2 Compartments shall be set up as specified in Figures 6.3.4.8 The surrogate cylinder and cylinder valve with the substitute
6.3.4.2(a) and (b). mass shall have the same total mass, ±5 percent, as the fully
pressurized breathing air cylinder and cylinder valve.

14.5 in. × 14.5 in. 14.5 in. × 14.5 in. 6.3.4.9 The attachment of the cylinder valve shall be permitted to be
(±0.25 in.) (±0.25) in. wrench-tightened prior to the test.
29 in. × 29 in.
(±0.5 in.) 6.3.5 Procedure.
14.5 in. × 14.5 in. 14.5 in. × 14.5 in.
(±0.25 in.)
6.3.5.1 The test items shall be placed unrestrained in the
(±0.25 in.)
compartments specified in 6.3.4.2 and all SCBA adjustment straps
shall be fully extended.

29 in. × 29 in. 6.3.5.2 No special ties downs shall be allowed to be made to the
29 in. × 29 in. (±0.5 in.)
(±0.5 in.) SCBA.

6.3.5.3 The basic movement of the bed of the test table shall be a 25
mm (1 in) orbital path at 5 Hz, such as can be obtained on a standard
Figure 6.3.4.2(a) Vibration table compartments — top view. package tester operating in synchronous mode at 300 rpm.

6.3.5.4 The test duration shall be 3 hours.


14.5 in. (±0.25) 14.5 in. (±0.25) 29 in. × 24 in.
6.3.5.5 After being subjected to the vibration test, the SCBA shall be
× 24 in. (±0.5 in.) × 24 in. (±0.5 in.) (±0.5 in.)
reattached to the breathing air cylinder originally provided with the
SCBA and shall then be tested as specified in Section 6.1.
Vibration table surface
6.3.6 Report. The facepiece peak inhalation pressure and peak
exhalation pressure shall be reported for each test condition.
Figure 6.3.4.2(b) Vibration table compartments — side view.
6.3.7 Interpretation.
6.3.4.2.1 The sides of the compartments shall be constructed of 6 mm
(¼ in.) stainless steel, the bottom of the compartments shall be the 6.3.7.1 The peak inhalation pressure and peak exhalation pressure
surface of the vibration table, and the top of the compartments shall shall be used to determine pass/fail performance.
remain open.
6.3.7.2 One or more specimens failing this test shall constitute failing
6.3.4.2.2 There shall be no burrs, sharp edges, surface discontinuities, performance.
or fasteners on the internal surfaces of the holding boxes.
6.4 Fabric Flame Tests.
6.3.4.3 The large compartments shall encase the complete SCBA.
6.4.1 Application.
6.3.4.3.1 SCBA regulators and hoses shall remain attached to the
complete SCBA. 6.4.1.1 This test method shall apply to each different fabric
component of the SCBA.
6.3.4.3.2 Regulators shall be allowed to be placed in the regulator
holder of the SCBA. 6.4.1.2 Modifications for testing fabrics less than 75 mm (3 in.) wide
shall be as specified in 6.4.8.
6.3.4.3.3 The SCBA facepiece and those components that attached
directly to the facepiece, excluding regulators, shall not be included 6.4.1.3 Modifications for testing fabrics less than 305 mm (12 in.)
in the SCBA compartment. long shall be as specified in 6.4.9.

6.3.4.4 The small compartments shall encase the facepiece and those 6.4.2 Specimens.
components that attach directly to the facepiece, excluding the
regulator and associated hoses. 6.4.2.1 Specimens shall consist of a 75 mm × 305 mm (3 in. × 12 in.)
rectangle.
6.3.4.5 The breathing air cylinder of the SCBA shall be replaced by a
surrogate cylinder. 6.4.2.2 Test specimens shall be cut from a standard production run of
the fabric components used in the SCBA.
6.3.4.6 The surrogate cylinder and cylinder valve shall be of identical
design and construction as the breathing gas cylinder and cylinder 6.4.3 Sample Preparation.
valve of the SCBA to be tested.
6.4.3.1 Five test specimens shall be tested without any conditioning.
6.3.4.7 The mass of the breathing air of a fully pressurized breathing
air cylinder shall be replaced in the surrogate cylinder with a

486
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.4.3.2 The remaining five test specimens shall be conditioned by five Standard frame
cycles of washing and drying in accordance with the procedures
specified in Machine Cycle 1, Wash Temperature V, Drying
Procedure Ai, of AATCC 135, Dimensional Changes in Automatic Home
Laundering of Woven and Knit Fabrics.
Wire lattice
6.4.4 Apparatus.

6.4.4.1 The test apparatus shall be as specified in ASTM D 6413,


Standard Test Method for Flame Resistance of Textiles (Vertical Test).

6.4.4.2 Each specimen shall be examined for evidence of melting or


ignition to determine pass/fail.

6.4.4.3 The char lengths and afterflame shall be recorded, and each Test sample
shall be averaged to determine pass/fail.

6.4.4.4 Specimens shall be observed for evidence of melting or


ignition to determine pass/fail.

6.4.5 Procedure. Specimens shall be tested in accordance with ASTM


Standard frame Wire lattice
D 6413, Standard Test Method for Flame Resistance of Textiles (Vertical
Test). Test sample

6.4.6 Report.

6.4.6.1 Afterflame time and char length shall be reported for each
specimen.

6.4.6.2 The average afterflame time and char length for each material
tested shall be calculated and reported.

6.4.6.3 The afterflame time shall be reported to the nearest 0.2 Figure 6.4.8.2 Wire lattice test frame.
second and the char length to the nearest 3.2 mm (1/8 in).
6.4.9.2 Samples that are not available in the length required in
6.4.6.4 Observations of melting or dripping for each specimen shall 6.4.2.1 shall be positioned such that the bottom edge of the sample is
be reported. positioned at the bottom of the test frame.

6.4.7 Interpretation. 6.4.9.3 Testing shall be performed as specified in 6.4.5.

6.4.7.1 Pass/fail performance shall be based on any observed melting 6.5 Fabric Heat Tests.
or dripping, the average afterflame time, and the average char
length. 6.5.1 Application.

6.4.7.2 One or more specimens failing this test shall constitute failing 6.5.1.1 This test method shall apply to each different fabric
performance. component of the SCBA.

6.4.8 Specific Requirements for Testing Fabrics Less than 75 mm (3 6.5.1.2 Modifications for testing fabrics less than 15 in. wide shall be
in.) Wide. as specified in 6.5.8.

6.4.8.1 If the fabric components are not available in the width 6.5.1.3 Modifications for testing fabrics less than 15 in. long shall be
specified in 6.4.2.1, the width of the test specimen shall be the width as specified in 6.5.9.
as used on the SCBA, but shall be a minimum of 305 mm (12 in.)
long. 6.5.2 Specimens.

6.4.8.2 The test frame in Figure 6.4.8.2 shall be utilized to hold 6.5.2.1 Specimens shall consist of a 380 mm × 380 mm (15 in × 15
samples not available in the width specified in 6.4.2.1. in.) square.

6.4.8.3 Testing shall be performed as specified in 6.4.5. 6.5.2.2 Test specimens shall be cut from a standard production run of
the fabric components used in the SCBA.
6.4.9 Specific Requirements for Testing Fabrics Less than 305 mm
(12 in.) Long. 6.5.3 Sample Preparation.

6.4.9.1 Where the fabric components are not available in the length 6.5.3.1 Five test specimens shall be tested without any conditioning.
specified in 6.4.2.1, the length of the test specimen shall be the
length as used on the SCBA. 6.5.3.2 The remaining five test specimens shall be conditioned by five
cycles of washing and drying in accordance with the procedures
specified in Machine Cycle 1, Wash Temperature V, Drying

487
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
Procedure Ai, of AATCC 135, Dimensional Changes in Automatic Home 6.5.8.2 Testing shall be performed as specified in 6.4.5.
Laundering of Woven and Knit Fabrics.
6.5.9 Specific Requirements for Testing Fabrics Less than 305 mm
6.5.4 Apparatus. (12 in.) Long.

6.5.4.1 The test oven shall be a horizontal flow circulating over with 6.5.9.1 If the fabric components are not available in the length
minimum interior dimensions so that the specimens can be specified in 6.5.2.1, the length of the test specimen shall be the
suspended and are at least 50 mm (2 in.) from any interior oven length as used on the SCBA.
surface or other test specimen.
6.5.9.2 Testing shall be performed as specified in 6.4.5.
6.5.4.2 The test oven shall have an airflow rate of 38 m/min to 76
m/min (125 ft/min to 250 ft/min) at the standard temperature and 6.6 Thread Melting Test.
pressure of 21°C (70°F) at 1 atmosphere measured at the center
point of the oven. 6.6.1 Application. This test shall apply to sewing thread used in
construction of the SCBA.
6.5.4.3 A test thermocouple shall be positioned so that it is level with
the horizontal centerline of a mounted sample specimen. 6.6.2 Specimens. Three 3-mg to 4-mg specimens shall be tested.

6.5.4.3.1 The themocouple shall be equidistant between the vertical 6.6.3 Sample Preparation. Specimens shall be conditioned at 22°C
centerline of a mounted specimen placed in the middle of the oven ±3°C (72°F ±5°F) with a relative humidity of 50 percent ±25 percent
and the oven wall where the airflow enters the test chamber. for a minimum for a minimum of 4 hours prior to testing.

6.5.4.3.2 The thermocouple shall be an exposed bead, Type J or 6.6.4 Apparatus.


Type K, No. 30 AWG thermocouple.
6.6.4.1 An electrically heated stage having a circular depression large
6.5.4.3.3 The test oven shall be heated and the test thermocouple enough to insert a micro cover glass and a variable transformer
stabilized at 260°C +6/-0°C (500°F +10/-0°F) for a period of not less controlling the rate of heat input to the stage shall be used.
than 30 minutes.
6.6.4.2 Two armored stem thermometers shall be used, one with a
6.5.5 Procedure. range of 20°C to 160°C, accurate to ½°C and one with a range from
150°C to 300°C, accurate to 1°C.
6.5.5.1 The test specimen shall be suspended by a metal hook(s) at
the top and centered in the oven so that the entire test specimen is 6.6.4.3 The following items shall be provided for test equipment:
not less than 50 mm (2 in.) from any oven surface or another test
specimen. (1) Low-powered magnifying glass

6.5.5.2 Oven air flow shall be parallel to the plane of the material. (2) Two micro cover glasses

6.5.5.3 The oven door shall not remain open more than 15 seconds. (3) Spatula, pick needle, or other instrument for applying pressure
to the cover glass
6.5.5.3.1 The air circulation shall be shut off while the door is open
and turned on when the door is closed. (4) Soxhlet extraction apparatus

6.5.5.3.2 The total oven recovery time after the door is closed shall (5) Chloroform, U.S.P reagent
not exceed 30 seconds.
6.6.5 Procedure.
6.5.5.4 The specimen, mounted as specified, shall be exposed in the
test oven for 5 minutes +0.15/-0 minutes. 6.6.5.1 Specimens shall be extracted with chloroform for a minimum
of 20 extractions in a Soxhlet extractor and dried.
6.5.5.5 The test exposure time shall begin when the test
thermocouple recovers to the temperature of 260°C +6/-0 °C (500°F 6.6.5.2 The specimen shall then be cut into lengths of 2 mm (1/16 in.)
+10/-0°F). or less.

6.5.5.6 Immediately after the specified exposure, the specimen shall 6.6.5.3 The specimen shall be placed in a small mound on a cover
be removed and examined for evidence of ignition or melting. glass and covered with another cover glass.

6.5.6 Report. Observations of ignition or melting shall be reported 6.6.5.4 The 2 cover glasses shall be pressed together gently but
for each specimen. firmly, and placed in the circular depression on the stage.

6.5.7 Interpretation. Any evidence of ignition or melting on any 6.6.5.5 The temperature of the stage shall be raised with some
specimen shall constitute failing performance. rapidity to 245°C and thereafter at a rate of 3°C to 4°C (5°F to
8°F)per minute until 260°C (500°F) is reached.
6.5.8 Specific Requirements for Testing Fabrics Less than 75 mm (3
in.) Wide. 6.6.5.6 At this rate of temperature rise, a slight pressure shall be
applied on the upper glass cover by pressing with a spatula, pick
6.5.8.1 If the fabric components are not available in the width needle, or other instrument, so that the complete fiber is in contact
specified in 6.5.2.1, the width of the test specimen shall be the width with the cover glass.
as used on the SCBA, but shall be a minimum of 305 mm (12 in.)
long.

488
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.6.5.7 The specimen shall be observed with the aid of a magnifying 6.7.5.8.1 The collectors shall be placed in the proximity of the test
glass at 260°C (500°F), and any melting of the specimens shall be specimens, one nearest to any nozzle and the other farthest from all
reported. nozzles.

6.6.6 Interpretation. Any specimen exhibiting melting at 260°C 6.7.5.8.2 The fog shall be such that for each 80 cm2 (12.4 in.2) of
(500°F) shall constitute failure of this test. horizontal collecting area there will be collected in each collector
from 1.0 mL to 2.0 mL of solution per hour.
6.7 Corrosion Resistance Test.
6.7.5.9 After completion of the salt fog exposure, the SCBA shall then
6.7.1 Application. This test method shall apply to complete SCBA. be stored in an environment of 22°C ±3°C (72°F ±5F°) at 50 percent
±5 percent relative humidity for a minimum of 48 hours.
6.7.2 Specimens. Each specimen to be tested shall be as specified in
2.3.1. 6.7.5.10 The SCBA shall then be tested as specified in Section 6.1 to
determine pass/fail.
6.7.3 Sample Preparation.
6.7.5.11 All controls or operating features of the SCBA shall operate
6.7.3.1 Prior to testing, specimens shall be conditioned for a per the SCBA manufacturer’s instructions to determine pass/fail.
minimum of 4 hours and tested at an ambient temperature of 22°C
±3°C (72°F ±5°F), RH 50 percent ± 25 percent. 6.7.6 Report. The facepiece pressure peak inhalation and peak
exhalation shall be reported for each test condition.
6.7.3.2 Specimens for conditioning shall be complete SCBA.
6.7.7 Interpretation.
6.7.4 Apparatus. A salt fog chamber shall be used for testing and shall
meet the requirements of Section 4 of ASTM B 117, Standard Test 6.7.7.1 The peak inhalation and peak exhalation shall be used to
Method for Salt Spray (Fog) Testing. determine pass or fail performance.

6.7.5 Procedure. 6.7.7.2 One or more specimens failing this test shall constitute failing
performance.
6.7.5.1 The SCBA with a fully charged breathing air cylinder, with the
breathing air cylinder valve fully closed, shall be placed in the test 6.8 Particulate Test.
chamber attached to a mannequin to simulate its typical wearing
position on a fire fighter as specified by the manufacturer. 6.8.1 Application. This test method shall apply to complete SCBA.

6.7.5.2 SCBA shall not contact each other or with the sides of the test 6.8.2 Specimens. Each specimen to be tested shall be as specified in
chamber. 2.3.1.

6.7.5.3 The SCBA shall be placed in the temperature stabilized 6.8.3 Sample Preparation.
chamber for a minimum of 2 hours prior to introduction of the salt
solution. 6.8.3.1 Prior to testing, specimens shall be conditioned for a
minimum of 4 hours and tested at an ambient temperature of 22°C
6.7.5.4 The SCBA shall then be exposed to the salt fog for 48 hours ±3°C (72°F ±5°F), RH 50 percent ± 25 percent.
+15 minutes/-0 minutes.
6.8.3.2 Specimens for conditioning shall be complete SCBA.
6.7.5.5 Specimen SCBA shall be subjected to a 5 percent ±1 percent,
salt solution fog. 6.8.4 Apparatus.

6.7.5.5.1 The salt solution shall be prepared by dissolving 5 ±1 parts 6.8.4.1 The test headform specified in 6.1.4.1 shall be joined to a
by mass of sodium chloride in 95 parts of water. mannequin to simulate its typical wearing position on a fire fighter,
as specified by the manufacturer.
6.7.5.5.2 The salt used shall be sodium chloride substantially free of
nickel and copper and containing on the dry basis not more than 0.1 6.8.4.2 The test headform shall be connected, as specified in Section
percent of sodium iodide and not more than 0.3 percent of total 6.1, to the breathing machine specified in 6.1.4.13 or other
impurities. respiration simulator producing a minute volume of 40 L ±2 L at the
ambient conditions specified in 6.1.3.1, with a minimum tidal volume
6.7.5.5.3 The pH of the salt solution shall be in the range of 6.5 to of 1.6 L per breath at a minimum respiration of 10 breaths per
7.2. minute.

6.7.5.6 The compressed air supply to the nozzle or nozzles for 6.8.4.3 A test facility consisting of a chamber and accessories to
atomizing the salt solution shall be free of oil and dirt and control dust concentration, velocity, temperature, and humidity of
maintained between 69 kPa/m and 172 kPa/m (10 psi and 25 psi). dust-laden air shall be used.

6.7.5.7 The exposure temperature in the chamber shall be 6.8.4.4 In order to provide adequate circulation of the dust laden air,
maintained at 35°C ±1°C (95°F ±2°F) for the duration of the test. no more than 50 percent of the cross-sectional area and 30 percent of
the volume of the test chamber shall be occupied by the test item(s).
6.7.5.8 At least two clean fog collectors shall be placed within the
exposure zone that no drops of solution from the test specimens or 6.8.4.5* The chamber shall be provided with a means of maintaining
any other source shall be collected in. and verifying the dust circulation.

489
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.8.4.6 The dust-laden air shall be introduced into the test space in 6.9.3 Sample Preparation.
such a manner as to allow the air to become laminar in flow before it
strikes the test item. 6.9.3.1 Seven samples shall be chosen from a minimum of four
facepiece lenses.
6.8.4.7* Dust shall be Silicon flour and shall contain 97 percent to 99
percent by weight silicon dioxide (SiO2). 6.9.3.1.1 Four samples shall be taken from the left viewing area, and
three samples shall be taken from the right viewing area.
6.8.4.8 The following size distribution shall apply:
6.9.3.1.2 One of the four samples taken from the left viewing area
(1) One-hundred percent shall pass through a 100 mesh screen. shall be the set-up sample.
(2) Ninety eight percent ±2 percent shall pass through a 140 mesh
screen. 6.9.3.2 The left test samples shall include all of the following criteria:
(3) Ninety percent ±2 percent shall pass through a 200 mesh
screen. (1) The sample shall be a square measuring 50 mm × 50 mm (2
(4) Seventy-five percent ±2 percent shall pass through a 325 mesh in. × 2 in.).
screen. (2) Two edges of the square section shall be parallel within ±2
degrees of the axis of the cylinder or cone in the center of the
6.8.5 Procedure. sample.
(3) At least 38 mm (1 ½ in.) of the 50-mm × 50-mm (2-in. × 2-in.)
6.8.5.1 A fully charged SCBA shall be secured to a test headform and square shall be taken from the left side of the center line of the lens.
mannequin specified in 6.8.4.1 and shall be subjected to the (4) The 50-mm × 50-mm (2-in. × 2-in.) square shall be cut at
following test procedure. approximately eye level.
6.8.5.2 The mannequin, including the test headform, shall be 6.9.3.3 The right test samples shall include all of the following
mounted upright and placed inside the test chamber. criteria:
(1) The sample shall be a square measuring 50 mm × 50 mm (2
6.8.5.3 The temperature of the test chamber shall be adjusted to
in. × 2 in.).
22°C ±3°C (72°F ±5°F) and the relative humidity to less than 30
(2) Two edges of the square section shall be parallel within ±2
percent.
degrees of the axis of the cylinder or cone in the center of the
sample.
6.8.5.4 The air velocity shall be adjusted to 533.4 m/min, ±76.2
m/min (1750 ft/min ± 50 ft/min). (3) At least 38 mm (1 ½ in.) of the 50-mm × 50-mm (2-in. × 2-in.)
square shall be taken from the right side of the center line of the
6.8.5.5 The dust concentration for the blowing dust shall be lens.
maintained at 10.6 ± 7 g/m3 (0.3 ± 0.2 g/ft3). (4) The 50-mm × 50-mm (2-in. × 2-in.) square shall be cut at
approximately eye level.
6.8.5.6 The test duration shall be 1 hour, and the breathing machine
shall be operating throughout the entire test. 6.9.3.4 Each of the samples shall be cleaned in the following manner:

6.8.5.6.1 The test shall be permitted to be interrupted to change the (1) The sample shall be rinsed with clean tap water.
SCBA breathing gas cylinder. (2) The sample shall be washed with a solution of nonionic/low-
phosphate detergent and water using a clean, soft gauze pad.
6.8.5.6.2 Test item configuration and orientation shall be turned (3) The sample shall be rinsed with deionized water.
around its vertical axis 180 degrees midway through the test. (d) The sample shall be blown dry with clean compressed air or
nitrogen.
6.8.5.7 After the completion of the above test, the SCBA shall be
removed from the test compartment. 6.9.4 Apparatus. The test apparatus shall be constructed in
accordance with Figure 6.9.4.
6.8.5.8 The SCBA shall be lightly shaken or brushed free of dust and
then shall be tested as specified in Section 6.1, Air Flow Performance Existing Figure 6.9.1 (no change)
Test, to determine pass/fail. Figure 6.9.4 Lens abrasion tester.

6.8.6 Report. The facepiece pressure peak inhalation and peak 6.9.5 Procedure.
exhalation shall be reported for each test condition.
6.9.5.1 The haze of the sample shall be measured using a haze meter
6.8.7 Interpretation. in accordance with ASTM D 1003, Standard Test Method for Haze and
Luminous Transmittance of Transparent Plastics, and recorded with the
6.8.7.1 The peak inhalation and peak exhalation shall be used to following additions:
determine pass or fail performance.
(1) The haze shall be measured in the middle of the sample ±1.6
6.8.7.2 One or more specimens failing this test shall constitute failing mm (± 1/16 in.).
performance. (2) The sample shall be repositioned to achieve the maximum
haze value within the area defined in (1).
6.9 Facepiece Lens Abrasion Test. (3) The haze meter shall have a specified aperture of 22.4 mm (7/8
in.).
6.9.1 Application. This test method shall apply to facepiece lenses. (4) The haze meter shall have a visual display showing 0.1 percent
resolution.
6.9.2 Specimens. A minimum of four faceshield lenses shall be
tested.

490
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
(5) The haze meter shall be calibrated before and after each day’s 6.9.5.15 The haze of the sample shall be measured following the
use following procedures specified in ASTM D 1003, Standard Test procedure specified in 6.9.5.1.
Method for Haze and Luminous Transmittance of Transparent Plastics.
6.9.5.16 The delta haze shall be calculated by subtracting the initial
6.9.5.2 The set-up sample shall be placed cover side up in the test haze from the final haze.
apparatus sample holder.
6.9.5.17 The testing steps specified in 6.9.3.4 through 6.9.5.16 shall
6.9.5.3 The sample holder shall be configured with a flat surface be repeated five times with a new sample and abrasive disc.
under the lens or with an inner radius support.
6.9.6 Report.
6.9.5.4 The pad holder shall consist of a cylinder 10 mm (3/8 in.) high
and 25 mm (1 in.) in diameter with a radius of curvature equal to the 6.9.6.1 The six delta haze values shall be averaged.
radius of curvature of the outside of the lens in the viewing area ±0.25
diopter. This cylinder shall be rigidly affixed to the stroking arm by a 6.9.6.2 The resultant value shall be compared to the value specified
#10-32 UNF threaded rod. in Section 5.9 to determine pass/fail.

6.9.5.5 The pad shall be a Blue Streak M306M wool felt polishing pad 6.9.7 Interpretation.
15
or equivalent 24 mm( / in.) in diameter.
16 6.9.7.1 The average delta haze shall be used to determine pass or fail
performance.
6.9.5.6 The abrasive disc shall be made from 3M Part Number 7415,
Wood Finishing Pad or equivalent. 6.9.7.2 Failure of the average value shall constitute failure for the
15
entire sample.
6.9.5.6.1 A disc 24 mm( / in.) in diameter shall be cut from the
16
abrasive sheet. 6.10 Communication Test.

6.9.5.6.2 The marked side of the disc shall be placed against the pad. 6.10.1 Application. This test method shall apply to complete SCBA.

6.9.5.6.3 Care shall be exercised to maintain this orientation for each 6.10.2 Specimens. Each specimen to be tested shall be as specified in
abrasive disc throughout the testing. 2.3.1.

6.9.5.7 The pad holder, pad, and abrasive disc shall be installed on 6.10.3 Sample Preparation.
the stroking arm.
6.10.3.1 Prior to testing, specimens shall be conditioned for a
6.9.5.7.1 The stroking arm shall be leveled to ±3 degrees by adjusting minimum of 4 hours and tested at an ambient temperature of 22°C
the threaded pin. ±3°C (72°F ±5°F), RH 50 percent ± 25 percent.

6.9.5.7.2 The pin shall be secured to prevent rotation of the pad 6.10.3.2 Specimens for conditioning shall be complete SCBA.
holder.
6.10.4 Apparatus.
6.9.5.7.3 The axis of curvature of the pad holder shall be coincident
with the axis of curvature of the lens. 6.10.4.1 Testing shall be conducted in a chamber that absorbs a
minimum of 90 percent of all sound from 500 Hz to 5000 Hz.
6.9.5.8 The stroking arm shall be counterbalanced with the pad
holder, pad, and abrasive disc in place. 6.10.4.2 Five listening subjects and five talkers consisting of four
males and one female shall be available for testing.
6.9.5.9 The set-up sample shall be replaced with one of the six
samples to be tested. 6.10.4.3 The subjects participating as listeners shall have “audio
metrically normal” hearing as defined in Section 5.3 of ANSI S3.2,
6.9.5.10 The 1000-g ±5 g (2.2-lb ±0.18 lb) test weight shall be installed Method for Measuring the Intelligibility of Speech over Communication
on the pin above the test sample. Systems, in the range of 500 Hz to 3000 Hz.

6.9.5.11 The test shall be run for 200 cycles ±1 cycle. One cycle shall 6.10.4.4 Talkers and listeners shall be selected and trained according
consist of a complete revolution of the eccentric wheel. to Section 7 of ANSI S3.2.

9 6.10.4.5 The five talkers shall not have facial hair, any unusual facial
6.9.5.12 The length of stroke shall be 14.5 mm ( / in.), producing a characteristics, or any other condition that could cause interference
16
pattern 38 mm (1 ½ in.) long. with the seal of the facepiece.

6.9.5.12.1 The frequency of the stroke shall be 60 cycles ±1 cycle per 6.10.4.6 The talkers shall perform and pass a qualitative facepiece-to-
minute. face fit check per the SCBA manufacturer’s instructions.

6.9.5.12.2 The center of the stroke shall be within ±2 mm (± 1/16 in.) 6.10.4.7 Where the talker is qualified to wear several sizes of
of the center of the sample. facepieces, then the talker shall choose the facepiece that is most
comfortable.
6.9.5.13 The sample shall be removed and cleaned following the
procedure specified in 6.9.3.4. 6.10.4.8 The five talkers shall be trained in the donning and usage of
the SCBA per manufacturer’s instructions.
6.9.5.14 The abrasive disc shall be discarded.

491
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.10.4.9 The five talkers shall have no obvious speech defect or strong 6.10.5.5.1 Listeners’ scores shall be based on the words actually
regional accent. spoken by the talkers.

6.10.4.10 Distance between the talker and listener(s) shall be 1.5 m 6.10.5.5.2 Listeners’ scores shall not be reduced because of speaking
+305/-0 mm (5 ft +1/-0 ft), and they shall be facing each other. mistakes of the talkers or spelling errors that are phonetically correct.

6.10.4.11 The test chamber shall be filled with broadband “pink” 6.10.5.5.3 All of the listeners’ scores without the SCBA used by the
noise with a tolerance of 6 dB per octave band from 400 Hz to 4000 talker shall be averaged and all of the listeners’ scores with the SCBA
Hz. used by the talker shall be averaged.

6.10.4.12 The forward axis of the loudspeaker shall be oriented away 6.10.5.5.4 The average score of the five listeners for the talker using
from the listener group. the SCBA shall be divided by the average score of the five listeners for
the talker without using the SCBA, and the result shall be called the
6.10.4.13 The distance between the loudspeaker and the listeners “score value.” This procedure shall be performed for each of the five
shall be as great as possible so as to create a quasi-uniform sound field talkers.
over the listening group.
6.10.5.6 The average of the score values obtained in 6.10.5.5.3 and
6.10.4.14 More than one loudspeaker shall be permitted to be used 6.10.5.5.4 shall be calculated.
to achieve the desired sound field.
6.10.5.6.1 Where the average of the score values is >72 percent, this
6.10.4.15 The gain of the power amplifier shall be adjusted to achieve average score value shall be used to determine pass/fail as specified
an A-weighted sound level of 70 dB ±2 dB at each listener’s head in Section 5.10.
position, without listeners present.
6.10.5.6.2 Where the average of the score values <72 percent, the
6.10.5 Procedure. sample standard deviation (s.d.) of the score values shall be
calculated in the following manner:
6.10.5.1 The method for measuring word intelligibility shall be as

 ∑ ( x/N ) 2 
specified in ANSI S3.2, Method for Measuring the Intelligibility of Speech

∑ ( x ) −  N - 1 
over Communication Systems, as modified by the above apparatus and 2
the following requirements.

6.10.5.2 The test material shall be the reading of one complete list of s.d . =  
phonetically balanced words as contained in Table 1 of ANSI S3.2, N -1
Method for Measuring the Intelligibility of Speech over Communication
Systems. where:
x = score values
6.10.5.2.1 The words shall be spoken singularly in the following N = sample size (5)
carrier sentence: “Would you write (list word) now?”
6.10.5.6.3 Where the calculated sample standard deviation of the test
6.10.5.2.2 The rate shall be approximately one test word every six score values >10.0, the test shall be invalidated, and the procedures of
seconds. 6.10.5.2 through 6.10.5.12 shall be repeated.

6.10.5.2.3 The talkers shall be trained to talk at 75 dBA to 85 dBA 6.10.5.6.4 Where the calculated sample standard deviation of the test
without an SCBA facepiece, measured at the listener’s ear, placing no score values <10.0, a test statistic T value shall be calculated to
unusual stress on any word. determine if the average of the score values obtained is or is not
equivalent to 72 percent; it shall be calculated in the following
6.10.5.2.4 Training shall include the use of background noise as manner:
defined in 6.10.4.7.
 −
6.10.5.2.5 The talkers shall not vary their voice level from that used
without the facepiece after the facepiece is donned.  µ − X  N
T=
6.10.5.2.6 The listeners shall write each word as they hear it. s .d.
6.10.5.3 The talkers shall conduct two tests in the chamber having an where:
ambient noise field as specified in 6.10.4.11, using a different word
list for each of the following conditions: −

(1) With no SCBA


X = average of the score values
N = sample size (5)
(2) With SCBA worn and operated per the SCBA manufacturer’s µ = 72 percent
instructions s.d. = sample standard deviation

6.10.5.4 Talkers’ speech shall be recorded during the tests to 6.10.5.6.5 For T values •2.13, the score value shall be considered to be
determine if the talkers conform to the word list specified for that equivalent to a score value of 72 percent and shall be used to
test. determine pass/fail as specified in Section 5.10.

6.10.5.5 Each listener’s response form shall be scored as to the 6.10.5.6.6 For T values >2.13, the score value shall be as calculated in
number of correct responses out of the 50 words recited. 6.10.5.6, and this calculated score value shall be used to determine
pass/fail as specified in Section 5.10.

492
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA

6.11.4.2.8 The protective covering shall be stitched with Kevlar®


6.10.6 Report. The average of the score values obtained shall be thread using a minimum of 6.8 stitches per inch (25 mm).
reported.
6.11.4.2.9 All major seams shall be double stitched and felled locked
6.10.7 Interpretation. One or more average score value failing this
test shall constitute failing performance. with all inside seams to be finished with Kevlar® thread.

6.11* Heat and Flame Test. 6.11.4.2.10 All stress points shall be reinforced.

6.11.1 Application. This test method shall apply to complete SCBA. 6.11.4.2.11 No metal shall pass from the outside of the protective
covering through the moisture barrier and liner to cause the transfer
6.11.2 Specimens. Each specimen to be tested shall be as specified in of heat to the mannequin when the protective covering is completely
2.3.1. assembled.

6.11.3 Sample Preparation. 6.11.4.2.12 The protective covering, including the front closure, shall
be constructed in a manner that provides secure and complete
6.11.3.1 Prior to testing, specimens shall be conditioned for a moisture and thermal protection.
minimum of 4 hours and tested at an ambient temperature of 22°C
±3°C (72°F ±5°F), RH 50 percent ±25 percent. 6.11.4.2.13 If nonpositive fasteners, such as snaps or hook-and-pile
tape, are utilized in garment closures, a positive locking fastener,
6.11.3.2 Specimens for conditioning shall be complete SCBA. such as hooks and dees or zippers, shall also be utilized.

6.11.4 Apparatus. 6.11.4.2.14 Pockets and fluorescent retroreflective trim shall not be
installed.
6.11.4.1 A test mannequin meeting the requirements specified in
Figure 6.11.4.1 shall be provided. 6.11.4.2.15 The collar shall be made of four-piece construction
consisting of outer shell material on both the back, or outside, and
Existing Figure 6-11.1 (no change) next to the mannequin neck.
Figure 6.11.4.1 Test mannequin.
6.11.4.2.15.1 The two inner layers shall consist of a thermal liner and
6.11.4.2* The test mannequin shall have a protective covering that moisture barrier.
shall be designed and constructed as follows.
6.11.4.2.15.2 No throat strap shall be attached.
6.11.4.2.1 The assembled protective covering composite consisting of
an outer shell, moisture barrier, and thermal liner shall have an 6.11.4.2.16 Sleeve outside seams shall be felled, while inside seams
average thermal protective performance (TPP) of not less than 35.0 shall be lock stitched.
when tested in accordance with 5.1.1 of NFPA 1971, Standard on
Protective Ensemble for Structural Fire Fighting. 6.11.4.2.17 All protective covers shall measure 890 mm (35 in.) long
when measured from the center of the back collar seam to the hem.
6.11.4.2.2 The outer shell shall be one of the following options:
6.11.4.2.18 The protective cover size shall be 1120-mm (44-in.) chest
(1) 40 percent PBI®/60 percent Kevlar® ripstop weave, weighing 865-mm (34-in.) sleeve.
2 2
nominally 255 g/m (7.5 oz/yd ), with a water-repellent finish and a
natural and undyed color. 6.11.4.2.19 The complete protective covering shall be discarded and
(2) 40 percent PBI®/60 percent Technora® plain weave, weighing shall not be used after three flame exposures of the flame and heat
2 2 test.
nominally 255 g/m (7.5 oz/yd ), with a water-repellent finish and a
natural and undyed color. 6.11.4.3 A test headform meeting the requirements specified in
2 6.1.4.1 shall be used on the test mannequin.
6.11.4.2.3 The thermal liner shall be constructed of a 102-g/m (3.0-
2
oz/yd ) ripstop pajama check or plain weave Nomex® III facecloth 6.11.4.4 The test headform shall be attached to the breathing
quilt-stitched to 100-percent Nomex® III batting of approximately machine specified in Figures 6.1.4.13(a), (b), and (c), with the
2 2 modification that a 19-mm (¾-in.) I.D. breathing hose, not longer
204 g/m (6.0 oz/yd ). than 7.6 m (25 ft), shall be attached to the tee in the breathing
machine and the throat tube of the test mannequin headform.
6.11.4.2.4 The moisture barrier shall be constructed of nominally 76-
2 2
g/m (3-oz/yd ) polyester/cotton fabric that is coated with nominally 6.11.4.5 The test headform shall be covered with an undyed aramid
2 2
221 g/m (6.5 oz/yd ) of flame-resistant neoprene. hood for protection of the headform during testing.

6.11.4.2.5 The moisture barrier shall be completely sewn to the 6.11.4.5.1 The protective hood shall meet the hood requirements of
thermal liner at its perimeter with the cloth side outward from the NFPA 1971, Standard on Protective Ensemble for Structural Fire Fighting.
thermal liner and with all edges sewn together.
6.11.4.5.2 The protective hood, when placed on the test headform,
6.11.4.2.6 The liner/moisture barrier shall be no more than 75 mm shall not affect the seal of the facepiece to the headform.
(3 in.) from the coat hem.
6.11.4.5.3 The protective hood shall not cover or protect any part of
6.11.4.2.7 The moisture barrier and thermal liner shall be completely the facepiece or the facepiece retention system that holds the
detachable from the outer shell. facepiece to the headform.

493
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.11.4.6 The heat and flame test apparatus shall be as specified in 6.11.5.11 At the completion of the 15-minute exposure, the
Figure 6.11.4.6. ventilation rate shall be increased to 103 L/min ±3 L/min, as
specified in 6.1.4.11.
Existing Figure 6-11.9 (no change)
Figure 6.11.4.6 Heat and flame test apparatus. 6.11.5.12 The oven door shall be opened and the SCBA mounted on
the test mannequin shall be moved out of the oven and into the
6.11.4.6.1 The test oven shall be a horizontal forced circulating air center of the burner array.
oven with an internal velocity of 61 m (200 ft) per minute.
6.11.5.13 The SCBA shall then be exposed to direct flame contact for
6.11.4.6.2 The test oven shall have minimum dimensions of 915 m 10 sec +0.25/-0.0 sec.
depth × 915 m width × 1.22 m height (36 in. depth × 36 in. width × 48
in. height). 6.11.5.14 This exposure shall begin within 20 seconds of removal of
the SCBA from the test oven.
6.11.5 Procedure.
6.11.5.15 The SCBA shall be observed for any afterflame, and the
6.11.5.1 The SCBA shall be mounted on the test mannequin to afterflame duration shall be recorded to determine pass/fail as
simulate the correct wearing position on a person as specified by the specified in 5.11.2.
SCBA manufacturer’s instructions.
6.11.5.16 Within 20 seconds after completing the direct flame
6.11.5.2 The facepiece shall be mounted and tested on the test exposure, the SCBA mounted on the test mannequin shall be raised
headform as specified in 6.1.4.1. 150 mm +6/-0 mm (6 in. +1/4/-0 in.) and dropped freely.

6.11.5.3 The test oven shall be calibrated using a 30-gauge exposed 6.11.5.17 The SCBA shall be observed to determine pass/fail as
bead type J iron/constantan wire reference thermocouple that has specified in 5.11.3.
been calibrated to set the 0.0°C (32.0°F) reference point with an ice
bath containing ice and deionized or distilled water. 6.11.5.18 The facepiece pressure during the entire test shall be read
from the strip chart recorder and corrected by adding the value of
6.11.5.3.1 Boiling water shall be used to set the 100°C (212°F) the difference in pressure calculated in 6.11.5.8 to determine
reference value. pass/fail as specified in 5.11.1.

6.11.5.3.2 The reference temperatures shall be corrected to standard 6.11.5.19 Any pressure spike caused by the impact of the drop test
temperatures using a barometric pressure correction. and measured within a duration of three cycles of the breathing
machine after the apparatus drop shall be disregarded.
6.11.5.4 For calibration prior to the heat and flame test, the
calibration mannequin, as specified in Figure 6.11.5.4, shall be 6.11.5.20 The SCBA facepiece shall be removed from the test
exposed to direct flame contact for 10 seconds using the heat and headform and, without touching the lens, shall be donned by a test
flame test apparatus. subject with visual acuity of 20/20 in each eye, uncorrected or
corrected with contact lenses.
6.11.5.4.1 All peak temperature readings shall be within a
temperature range of 815°C to 1150°C (1500°F to 2102°F). The 6.11.5.20.1 The test shall be conducted using a standard 6.1-m (20-ft)
average mean of all peak temperature readings shall be no higher eye chart with normal lighting range of 100 to 150 ft-candles at the
than 950°C (1742°F). chart and with the test subject positioned at a distance of 6.1 m (20
ft) from the chart.
Existing Figure 6-11.12 (no change)
Figure 6.11.5.4 Calibration mannequin. 6.11.5.20.2 The test subject shall then read the standard eye chart at
some point through the nominal center of the lens of the facepiece
6.11.5.5 The test oven recovery time, after the door is closed, shall to determine pass/fail as specified in 5.11.4.
not exceed 1.0 minute.
6.11.5.21 The nominal center of the lens shall be the area bounded
6.11.5.6 The air flow performance test shall be conducted as specified by a line 50 mm (2 in.) above, 50 mm (2 in.) below, 50 mm (2 in.)
in 6.1.5, with modifications to the ventilation rate specified in 6.11.5.8 left, and 50 mm (2 in.) right of the intersection of the basic and
and 6.11.5.9 with test temperatures specified in 6.11.5.4 and 6.11.5.8. midsagittal planes.

6.11.5.7 The air flow performance test shall continue through the 6.11.6 Report.
drop test as specified in 6.11.5.18.
6.11.6.1 The facepiece pressure peak inhalation and peak exhalation
6.11.5.8 The ventilation rate shall be set at 40 L/min ±2 L/min, with shall be reported for each test condition.
a respiratory frequency of 12 ±1 breaths/min, at ambient conditions
as specified in 6.1.3.1. 6.11.6.2 Any afterflame beyond 2.2 seconds shall be reported.

6.11.5.9 The SCBA mounted on the test mannequin shall be placed 6.11.6.3 The facepiece lens vision shall also be reported.
in the test oven that has been preheated to 95°C ±2°C (203°F ±4°F).
6.11.7 Interpretation.
6.11.5.10 After the test oven door is closed and the oven temperature
recovers to 95°C (203°F), the test exposure time of 15 minutes shall 611.7.1 Pass/fail performance shall be based on any observed
begin. afterflame, the peak inhalation and exhalation values, and the
facepiece vision value.

494
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
6.11.7.2 Failure to meet any of the test condition requirements shall 6.13.6.1 The facepiece carbon dioxide content shall be used to
constitute failure of the SCBA. determine pass or fail performance.

6.12 Redundant End of Service Time Indicator Test. 6.13.6.2 One or more specimens failing this test shall constitute
failing performance.
6.12.1 Application. This test method shall apply to all end of service
time indicators required by Section 4.2. Chapter 7 Referenced Publications

6.12.2 Specimens. Each EOSTI system shall be tested. 7.1 The following documents or portions thereof are referenced
within this standard as mandatory requirements and shall be
6.12.3 Sample Preparation. considered part of the requirements of this standard. The edition
indicated for each referenced mandatory document is the current
6.12.3.1 Prior to testing, specimens shall be conditioned for a edition as of the date of the NFPA issuance of this standard. Some of
minimum of 4 hours and tested at an ambient temperature of 22°C these mandatory documents might also be referenced in this
±3°C (72°F ±5°F), with a RH of 50 percent ± 25 percent. standard for specific informational purposes and, therefore, are also
listed in Annex B.
6.12.3.2 Specimens for testing shall be complete EOSTI systems.
7.1.1 NFPA Publications. National Fire Protection Association, 1
6.12.4 Procedure. Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.

6.12.4.1 One of the EOSTI sensing mechanisms shall be blocked so as NFPA 1500, Standard on Fire Department Occupational Safety and
to simulate a failure of EOSTI’s sensing mechanism. Health Program, 1997 edition.

6.12.4.2 The blocking method shall be determined by the testing NFPA 1971, Standard on Protective Ensemble for Structural Fire Fighting,
organization and the manufacturer. 2000 edition.

6.12.4.3 With the sensing mechanism blocked as indicated in Section 7.1.2 AATCC Publication.
6.12.4.1, the airflow test in Section 6.1 shall be performed.
AATCC 135, Dimensional Changes in Automatic Home Laundering of
6.12.4.4 This test shall be repeated for each of the independent Woven and Knit Fabrics, 1989.
EOSTIs.
7.1.3 ANSI Publications. American National Standards Institute, 11
6.12.5 Report. West 42nd Street, New York, NY 10036.

6.12.5.1 The facepiece pressure peak inhalation and peak exhalation ANSI/CGA G-7.1, Commodity Specification for Air, 1989.
shall be reported for each test condition.
ANSI S3.2, Method for Measuring the Intelligibility of Speech over
6.12.5.2 The proper activation of the EOSTI shall also be reported. Communication Systems, 1989.

6.12.6 Interpretation. ANSI/UL 913, Standard for Intrinsically Safe Apparatus and Associated
Apparatus for Use in Class I, II, and III, Division I Hazardous Locations,
6.12.6.1 The peak inhalation, peak exhalation, and proper activation 1988.
of the EOSTI shall be used to determine pass or fail performance.
ANSI Z34.1, American National Standard for Third-Party Certification
6.12.6.2 One or more specimens failing this test shall constitute Programs for Products, Processes, and Services, 1993.
failing performance.
7.1.4 ASTM Publications. American Society for Testing and Materials,
6.13 Facepiece Carbon Dioxide Content Test. 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959.

6.13.1 Application. This test shall apply to all SCBA facepieces. ASTM B 117, Standard Test Method for Salt Spray (Fog) Testing.

6.13.2 Specimens. Each SCBA facepiece model and size shall be ASTM D 1003, Standard Test Method for Haze and Luminous
tested. Transmittance of Transparent Plastics, 1988.

6.13.3 Sample Preparation. Prior to testing, specimens shall be ASTM D 6413, Standard Test Method for Flame Resistance of Textiles
conditioned for a minimum of 4 hours and tested at an ambient (Vertical Test).
temperature of 22°C ±3°C (72°F ±5°F), with a RH of 50 percent ± 25
percent. 7.1.5 ISO Publications. International Standards Organization, 1 rue
de Varembé, Case Postale 56, CH-1211 Genéve 20, Switzerland.
6.13.4 Procedure. Specimens shall be tested as specified in section
8.14 of EN 136, Respiratory Protective Devices — Full face masks — ISO Guide 25, General Requirements for the Competence of Calibration
Requirements, testing, marking. and Testing Laboratories.

6.13.5 Report. The facepiece carbon dioxide content shall be ISO 9001, Quality Systems — Model for Quality Assurance in Design,
reported for each test specimen. Development, Production, Installation, and Servicing, 1994.

6.13.6 Interpretation. 7.1.6 U.S. Government Publication. U.S. Government Printing


Office, Washington, DC 20402.

495
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
Title 42, Code of Federal Regulations, Part 84, Respiratory Protective eliminated. Any retrofits or repairs should be approved by the
Devices, Tests for Permissibility, 8 June 1995. manufacturer whose SCBA complies with this standard.

Annex A Explanatory Material A.1.2.3 Although SCBA that meet this standard have been tested to
more stringent requirements than required for NIOSH certification,
Annex A is not a part of the requirements of this NFPA document but is there is no inherent guarantee against SCBA failure or fire fighter
included for informational purposes only. This annex contains explanatory injury. Even the best-designed SCBA cannot compensate for either
material, numbered to correspond with the applicable text paragraphs. abuse or the lack of a respirator training and maintenance program.
The severity of these tests should not encourage or condone abuse of
A.1.1.1 The use of SCBA by fire fighters is always assumed to be in SCBA in the field.
atmospheres immediately dangerous to life or health (IDLH). There The environmental tests utilized in this standard alone might not
is no way to predetermine hazardous conditions, concentrations of simulate actual field conditions but are devised to put extreme loads
toxic materials, or percentages of oxygen in air in a fire environment, on SCBA in an accurate and reproducible manner by test
during overhaul (salvage) operations, or under other emergency laboratories. However, the selection of the environmental tests was
conditions involving spills or releases of hazardous materials. Thus, based on summary values derived from studies of conditions that
SCBA are required at all times during any fire-fighting, hazardous relate to field use.
materials, or overhaul operations. General use criteria are contained
in NFPA 1500, Standard on Fire Department Occupational Safety and A.1.5.2.2 Approved. The National Fire Protection Association does
Health Program. not approve, inspect, or certify any installations, procedures,
equipment, or materials; nor does it approve or evaluate testing
A.1.2.1 The following is a brief description of selected performance laboratories. In determining the acceptability of installations,
requirements of this standard: procedures, equipment, or materials, the authority having
jurisdiction may base acceptance on compliance with NFPA or other
(a) Air Flow Performance Test. This test increases the current appropriate standards. In the absence of such standards, said
NIOSH breathing machine requirement of 40 L/min to 100 L/min. authority may require evidence of proper installation, procedure, or
The 100 L/min ventilation rate was derived from a review of several use. The authority having jurisdiction may also refer to the listings or
studies indicating that a ventilation rate of 100 standard liters per labeling practices of an organization that is concerned with product
minute encompasses the 98th percentile of all fire fighters studied. evaluations and is thus in a position to determine compliance with
(b) Environmental Temperature Resistance Tests. This series of tests appropriate standards for the current production of listed items.
exposes SCBA to various temperature extremes and temperature
cycles to which SCBA might be exposed during storage conditions
and certain environmental changes. A.1.5.2.4 Authority Having Jurisdiction. The phrase “authority
(c) Particulate Resistance Test. This test exposes SCBA to a having jurisdiction” is used in NFPA documents in a broad manner,
specified concentration of particulate to provide a reasonable level of since jurisdictions and approval agencies vary, as do their
assurance that SCBA are designed to properly function when exposed responsibilities. Where public safety is primary, the authority having
to the dust conditions commonly present during fire-fighting jurisdiction may be a federal, state, local, or other regional
operations. department or individual such as a fire chief; fire marshal; chief of a
(d) Facepiece Lens Abrasion Resistance Test. This test is designed to fire prevention bureau, labor department, or health department;
provide a reasonable level of assurance that the SCBA facepiece lens building official; electrical inspector; or others having statutory
is not easily scratched during fire-fighting operations, thereby authority. For insurance purposes, an insurance inspection
resulting in reduced visibility for the fire fighter. department, rating bureau, or other insurance company
(e) Communications Test. This test is designed to assure that the representative may be the authority having jurisdiction. In many
SCBA facepiece does not significantly reduce a fire fighter’s normal circumstances, the property owner or his or her designated agent
voice communication. assumes the role of the authority having jurisdiction; at government
(f) Accelerated Corrosion Resistance Test. This test is to provide a installations, the commanding officer or departmental official may be
reasonable level of assurance that SCBA are designed to resist the authority having jurisdiction.
corrosion that can form and interfere with SCBA performance and
function.
(g) Vibration Test. A previous requirement for a secured A.1.5.2.16 Compressed Breathing Air. The quality of the compressed
vibration test was eliminated, as it was much less severe than the breathing air used in open-circuit SCBA has a direct effect on the
unsecured vibration test that is still required, and it provided no performance of this equipment. It is therefore imperative that a
additional evaluation of the SCBA. In this unsecured vibration test, breathing air be used that is consistent with the design criteria
the pressurized breathing gas cylinder is now replaced by a surrogate established in this standard to ensure that the SCBA will continue to
cylinder to avoid the potential of catastrophic pressurized breathing meet the performance criteria contained in this standard. It has
gas cylinder failure during this rigorous test. been established through years of experience that Grade D breathing
(h) Fabric Components Test. Flame, heat, and thread tests are air with a maximum moisture content of 24 ppm or dryer [that is, a
added to provide a reasonable level of assurance that the fabric dew point of -54°C (-65°F) or lower] and a maximum particulate level
3
components of a harness assembly used to hold the SCBA to the of 5 mg/m air will meet the needs of both the fire fighter and the
wearer’s body will remain intact during fire-fighting operations. SCBA. (See also 6.1.3.3.)
(i) Heat and Flame Test. This test is intended to provide a
reasonable level of assurance that, when SCBA are exposed to a A.1.5.2.29 Listed. The means for identifying listed equipment may
variety of thermal and physical conditions and breathing rates that vary for each organization concerned with product evaluation; some
simulate the conditions of a flashover accident, the SCBA will organizations do not recognize equipment as listed unless it is also
perform and function properly. labeled. The authority having jurisdiction should utilize the system
Users are cautioned that if more unusual conditions prevail, such employed by the listing organization to identify a listed product.
as higher or lower extremes of temperatures than described herein,
or if there are signs of abuse or damage to the SCBA or its
components, the user’s margin of safety can be reduced or A.1.5.2.33 NIOSH Certified. An SCBA being “NIOSH certified” is
only one part of the certification process to NFPA 1981. SCBA that

496
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
are only NIOSH certified are not compliant with NFPA 1981 and A.2.2.3 The contractual provisions covering certification programs
should not be construed as having certification as compliant with should contain clauses advising the manufacturer that if
NFPA 1981. See Section 2.1 for further details. For the NIOSH requirements change, the product should be brought into
certification to remain in effect, the SCBA must be used and compliance with the new requirements by a stated effective date
maintained in the as approved condition. through a compliance review program involving all currently listed
products.
A.2.1.1.2 SCBA that are certified by NIOSH include a rated service Without these clauses, certifiers would not be able to move quickly
time based on laboratory tests required by NIOSH. The SCBA is to protect their name, marks, or reputation. A product safety
tested using a specified breathing machine with a breathing rate of 40 certification program would be deficient without these contractual
L/min. NIOSH uses this 40 L/min rate because it represents a provisions and the administrative means to back them up.
moderate work rate that an average user can sustain for a period of
time. To attain a rated service time of 30 minutes during this 40 A.2.2.6 Investigative procedures are important elements of an
L/min test, the typical SCBA cylinder must contain 1200 L or more of effective and meaningful product safety certification program. A
3
compressed breathable air. A 45-ft cylinder has a capacity of 1273.5 preliminary review should be carried out on products submitted to
3 the agency before any major testing is undertaken.
L, based on 28.3 L/ft . Because actual work performed by a fire
fighter often results in a ventilation rate that exceeds 40 L/min, fire A.2.2.12 Such inspections should include, in most instances,
fighters will frequently not attain the rated service time of 30 minutes. witnessing of production tests. With certain products the certification
During extreme exertion, for example, actual service time can be organization inspectors should select samples from the production
reduced by 50 percent or more. line and submit them to the main laboratory for countercheck
To ensure proper utilization of equipment in actual situations, testing. With other products, it might be desirable to purchase
after training and instruction, it is recommended that users gain samples in the open market for test purposes.
confidence by actually using the SCBA in a series of tasks For further information and guidance on recall programs, see 21
representing or approximating the physical demands likely to be CFR 7, Subpart C.
encountered.
In addition to the degree of user exertion, other factors that can A.2.3 The testing facility should take suitable precautions to protect
affect the service time of the SCBA include the following: testing personnel and to guard against catastrophic failure that could
result in a high-pressure gas release, fragmentation, and flying parts
(1) The physical condition of the user (see also ANSI Z88.6, and debris. Catastrophic failure can occur because many tests
Respiratory Protection — Respirator Use — Physical Qualifications for specified in Chapter 6 involve compressed gas cylinders containing
Personnel) high pressures, and the tests are rigorous in nature.
(2) Emotional conditions, such as fear or excitement, which can
increase the user’s breathing rate A.3.2.7 Users should be aware that NFPA 1500, Standard on Fire
(3) The degree of training or experience the user has had with Department Occupational Safety and Health Program, requires that all
such equipment SCBA be air flow tested at least annually in accordance with the
(4) Whether or not the cylinder is fully charged at the beginning manufacturer’s instructions. This interval of testing might not be
of use adequate when SCBA are more frequently used. It is recommended
(5) The facepiece fit that air flow testing be based on the number of SCBA uses rather
(6) Use in a pressurized tunnel or caisson [At two atmospheres of than based solely on time intervals.
pressure (29.4 psig), the duration will be one-half the duration
obtained at one atmosphere of pressure (14.7 psig); at three A.5.1 The current NIOSH certification test method, 42 CFR 84, uses a
atmospheres of pressure (44.1 psig), the duration will be one-third ventilation rate of 40 L/min, while NFPA 1981 requires an air flow
the duration obtained at one atmosphere of pressure.] test based on a ventilation rate of 100 L/min. A ventilation rate of
(7) The condition of the SCBA 100 standard L/min encompasses the 98th percentile of all fire
(8) The SCBA effective dead air space (Dead air space is a volume fighters studied. The ability of the SCBA to supply the 100 L/min of
proportional to the CO2 concentration in the inhaled breathing gas.) breathing gas is measured in this air flow performance test by
During normal breathing without a facepiece, carbon dioxide, monitoring the pressure within the facepiece.
which is produced by the body’s metabolism, is released to the Specific response times for both the pressure transducer and
environment with each breath. The facepiece of an SCBA reduces recorder are specified in this standard. It is important to note that if
this environment to a small space around the face. On exhalation, a other types of recording devices, measuring equipment, and testing
portion of the carbon dioxide-rich exhaled breath is trapped in this methods are used, pressure fluctuations might appear in the
space. On inhalation, fresh air from the SCBA cylinder mixes with facepiece as short (millisecond) negative pressure spikes. The
this carbon dioxide-rich air and then enters the lungs. The significance of these spikes to the actual protection afforded the user
concentration of carbon dioxide is dependent on facepiece by the SCBA is not fully understood at this time. Additional studies
configuration, flow characteristics, and ventilation rate. are needed to determine the significance, if any, of these spikes.
The full effect of increased dead air space has not been Because these negative spikes might affect the actual protection
demonstrated. However, the scientific work done in this area shows offered by the SCBA, it is recommended that a facepiece fitting
that an increase of CO2 in the inhalation air leads to increased program be established. Quantitative fitting tests are recognized to be
ventilation and, consequently, shorter service time for a given air the best method for determining the facepiece-to-face seal and
supply. Means to reduce CO2 in the inhalation air by using, for should be performed by the fire service wherever SCBA are used. For
departments that wish to perform quantitative fit testing, a suggested
example, a well-fitting nose cup have been demonstrated to give procedure for conducting such tests can be found in ANSI Z88.2,
longer service time. Contact each manufacturer for specific data. Practices for Respiratory Protection.
A.2.2.1 The certification organization should have sufficient breadth A.5.9 This standard contains an abrasion test that is used to evaluate
of interest and activity so that the loss or award of a specific business the outside surface of the facepiece lens. This standard does not
contract would not be a determining factor in the financial well-being address the abrasion resistance of the interior surface of the
of the agency. facepiece lens. Current facepiece lens interior surfaces can be
uncoated, coated with an antifog agent, coated with an abrasion-

497
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
resistant agent that does not comply with the performance required 1. From the positive peaks on the strip chart recording, count the
in Section 5.9, or coated with an abrasion-resistant coating that does number of exhalations (NE) that were made into the bag or use your
comply with the performance required in Section 5.9. Information own counting method if you are sure it is correct.
regarding coatings on the lens interior surface should be obtained 2. Measure the total distance (in centimeters) between the peaks
from the SCBA manufacturer. of 30 exhalations, which should be approximately 60 cm at a chart
speed of 60 cm/min. (See Detail 5 of Figure A.6.1.14.) If the pressure in
A.5.10 As the communications test is the only test that requires the gas-collection port has not been measured, the operator can use
human subjects, there were variations in the data used to determine another method to accurately measure the breathing machine’s rpm.
the appropriate pass/fail criteria. Therefore, a statistical approach to 3. Calculate rpm.
analyze the data was required to determine whether an individual 4. Determine the TV.
SCBA meets the pass/fail criteria of Section 5.10. A null hypothesis 5. Determine the minute volume (VM).
test utilizing the Student t-distribution is the appropriate method to
do this. NOTE: A record of TV and rpm should be maintained for each
The Student t-distribution of 2.13 results from the following machine. As the seals on the pistons wear, the TV for a given
conditions: rpm might decrease, an indication that the seals should be
Degrees of freedom = 4 replaced.
Confidence level = 95 percent (e) Adjust minute volume.
Refer to any current statistical text for further information. 1. If the VM is between 100 L and 106 L, no adjustment is
A.6.1.3.3 See A.1.5.2.16, Compressed Breathing Air. necessary and the BM is ready to perform the NFPA air flow
performance test at the present rpm setting.
A.6.1.14 The following is the recommended calibration procedure 2. If the VM < 100 L, the rpm must be increased and the VM
for NFPA Model 327-6 breathing machine. recalculated.
3. If the VM > 106 L, the rpm must be decreased and the VM
(a) Set up equipment. recalculated.
1. Remove plug fitting and open valve at side port of the breathing Existing A.6.1.14 (no change)
machine (BM), then close the valve to the test headform. Figure A.6.1.14 Calibration details.
2. Connect a nonreturn two-way valve to the side port. (See Figure
A.6.1.14.) A.6.3.3 Recommended Procedure for Surrogate Cylinder Preparation.
3. Make sure all gas has been expelled from a gas collection bag by (a) Terms used in the procedure are as follows:
rolling the bag up. Connect the bag to the dead-ended gas-collection (1) Free-Air Volume (V). The amount of air in cubic feet at standard
port of a three-way valve. (See Detail 2 of Figure A.6.1.14.) A atmospheric conditions stored in the cylinder.
recommended gas-collection bag is a 120-L meteorological bag or a (2) Water Volume (WV). Internal volume of the test cylinder
150-L Douglas bag. Equivalent or similar collection bags can be determined by calculating water displacement.
substituted. (3) Rated Storage Pressure (P). The nominal storage pressure rating
4. Connect the common port of the three-way valve to the of the cylinder at room temperature.
exhalation port of the nonreturn two-way valve. (See Detail 3 of Figure (b) Determining Mass of Air Stored in Cylinder (M).
A.6.1.14.)
5. Connect a transducer to a pressure tap on the collection side of where:
the three-way valve. The transducer output goes to the recorder. M = mass of air in cylinder (lbm)
(b) Collect gas.
1. With the vent port of the three-way valve open, start BM and V = free air volume in ft3
allow BM to warm up for at least 10 minutes.
2. After the 10-minute warm-up period, adjust the speed to (c) Determining Nominal Design Weight (W). Weight can be estimated
approximately 30 rpm if the machine has not been calibrated within based on the following components:
the last few days. If the machine has recently been calibrated, leave it
at its preset adjustment. where:
3. Set the chart speed on the recorder to 60 cm/min and start the W1 = tare weight of empty cylinder less cylinder valve
recorder. W2 = weight of cylinder valve assembly
4. At the start of an inhalation, turn the three-way valve so that the
air exhaled from the BM goes into the collection bag. (See Detail 4 of (d) Determining Ballast Rod Length (L). The ballast rod length is
Figure A.6.1.14.) determined by measuring the overall length from the neck of the
5. Each exhalation stroke should produce a positive peak on the cylinder to the center of the bottom of the cylinder (L1). The
strip-chart recording, which can be used as a counter. The operator
threaded engagement of the cylinder valve is also measured (L2).
can use a substitute method to count the exhaled tidal volumes (TV)
that go into the bag. The overall length is calculated as follows: (Dimensions are shown
6. After 30 to 35 exhalations, turn the three-way valve at the start in Figure 6.3.3.2.)
of an inhalation so that the gas collection port is closed and the BM
vents to atmosphere. Turn off the recorder. NOTE: Ensure that the ballast rod does not extend beyond the
(c) Measure the volume (liters) of gas collected (VL). cylinder.
1. The recommended method to measure the volume of gas in the
(e) Determining the Nominal Diameter of the Ballast Rod (D).
bag is to transfer the air into a spirometer. Make sure the bag is
The nominal diameter of the ballast rod is calculated as follows:
completely empty by rolling it up.
2. Another method to measure the gas volume in the bag is to
where:
slowly empty the bag through a calibrated dry-gas meter. Ensure that
M = air mass in cylinder (lbm)
a correction factor is applied as required.
(d) Calculate minute volume. V2 = air volume in cylinder (in.3)

498
NFPA 1981 — November 2001 ROP — Copyright 2001, NFPA
where: A.6.8.4.4 Silica flour could present a health hazard. When using
V = free air volume of cylinder (ft3) silica flour, assure that the chamber is functioning properly and not
L = ballast rod length (in.) leaking.

(f) Determining the Necessary Foam Weight (WF). Foam weight is A.6.8.4.5 A means for doing this is by use of a properly calibrated
found by subtracting the ballast rod weight from the total air storage smoke meter and standard light source.
weight as follows:
A.6.11 Complete engineering drawings to construct the heat and
The foam should have a molded density of 5.5 lbf/ft3 and mixed flame test apparatus can be obtained from the NFPA.
in a 50-percent ratio based on weight.
Theoretical amount of each component can be determined as A.6.11.4.2 The protective covering has been selected solely for the
follows: purpose of protecting the flame and heat test mannequin and
The final recommended mixture for each component, measured providing a reproducible exterior configuration to support the SCBA
in grams, is as follows: being tested. The intention of this standard is to test the SCBA and
Component A = 272*WF (g) not the protective covering.
Component B = 272*WF (g)
Annex B Referenced Publications
(g) Cylinder Preparation. Empty the cylinder of air and fully open
the cylinder valve. Remove the cylinder valve from the cylinder. A B.1 The following documents or portions thereof are referenced
means of threading the ballast rod to the cylinder valve must be within this standard for informational purposes only and are thus not
incorporated. This procedure is most readily implemented by considered part of the requirements of this standard unless also listed
removing the “dip-tube” from the cylinder valve and adding a 3/8-16- in Chapter 7. The edition indicated here for each reference is the
UNC female thread on the end of the cylinder valve mounting current edition as of the date of the NFPA issuance of this standard.
thread.
B.1.1 NFPA Publication. National Fire Protection Association, 1
(h) Ballast Rod Machining. The ballast rod is machined from ASTM Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101.
B16 brass, (hard). The machining details are provided in Figure
6.3.3.2. Care should be taken to ensure that the rod does not NFPA 1500, Standard on Fire Department Occupational Safety and
interfere with the cylinder at the valve end. This might require Health Program, 1997 edition.
machining a short thread relief at the cylinder valve end of the ballast
rod, which is indicated in Figure 6.3.3.2. B.1.2 Other Publications.

(i) Cylinder Foam Filling. Once the cylinder valve has been B.1.2.1 ANSI Publications. American National Standards Institute, 11
installed and the ballast rod has been installed and torqued, the West 42nd Street, New York, NY 10036.
cylinder should be positioned vertically with the fill/vent holes
pointing upwards. Commercially available plastic disposable ANSI Z88.2, Practices for Respiratory Protection, 1992.
laboratory funnels should be placed in the two fill/vent holes. Upon
measuring the component A and component B materials, they ANSI Z88.6, Respiratory Protection — Respirator Use — Physical
should be simultaneously poured into the cylinder via the funnels. Qualifications for Personnel, 1984.
Once the material has been poured into the cylinder, the funnels
should be removed. The mixture can be agitated by shaking the B.1.2.2 U.S. Government Publications. U.S. Government Printing
cylinder. The foam will begin to rise in 40 to 50 seconds. The entire Office, Washington, DC 20402.
volume of the cylinder will fill and excess foam will vent out of the
two fill holes. This material should be removed from the external Title 21, Code of Federal Regulations, Part 7, Subpart C.
surface of the cylinder.
Title 42, Code of Federal Regulations, Part 84, Respiratory Protective
(j) Comparison of Total Mass of Surrogate Cylinder to Submitted Devices, Tests for Permissibility, June 8,1995.
Cylinder. The fully pressurized breathing gas cylinder submitted for
testing and the completed surrogate cylinder both should be weighed
separately. The weight of the surrogate cylinder cannot vary from the
weight of the pressurized breathing gas cylinder, which was submitted
for testing, by more than 5 percent.

499

You might also like