Professional Documents
Culture Documents
Electrical System Earthing Design Philosophy: Prelude Floating LNG PROJECT
Electrical System Earthing Design Philosophy: Prelude Floating LNG PROJECT
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 1 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
PRELUDE EPCI
Floating LNG PROJECT
01A 24/11/2011 EPCI - AFD – Approved For Design- For previous JM. BILLARD A. VILLENEUVE/KS. A. TRABELSI
revision refer to document 2000-110-UT01-40000- HONG
EA-7704-00005_03A
Rev Date STATUS WRITTEN BY CHECKED BY APPROVED BY
DD/MM/YYYY (name & visa) (name & visa) (name & visa)
DOCUMENT REVISIONS
Sections changed in last revision are identified by a vertical line in the margin
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 2 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
CONTENTS
1. SCOPE / PURPOSE 4
1.1 Scope 4
1.2 Purpose 4
2. DEFINITIONS / ABREVIATIONS 4
2.2 Abbreviations 6
3.8 Certification 10
4.2 HV systems 11
5.1 General 16
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 3 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 4 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
1. SCOPE / PURPOSE
1.1 Scope
The present project specification sets out the philosophy and basic criteria for the design of the
earthing arrangements for the pFLNG project and covers all part of the facility i.e. the substructure
(hull), the living quarters, the topside modules and the turret.
This document provides practical details for the implementation of:
♦ HV and LV AC systems earthing (neutral earthing methods) as illustrated in the [Electrical
Single Line Diagram]
♦ AC UPS systems earthing as illustrated in the [Electrical Single Line Diagram]
♦ provisions for earthing of exposed conductive parts and bonding of extraneous conductive parts
♦ provisions for protection against static discharge and lightning impact
1.2 Purpose
Earthing and bonding systems are provided to:
♦ facilitate rapid detection and disconnection of faulty equipment and circuits in the event of a
short circuit to earth or resistive earth-fault
♦ minimise hazards to personnel and damage to plant from earth faults on electrical equipment
♦ protect against lightning and static discharges.
♦ minimise the adverse effects of electromagnetic interference in control systems
2. DEFINITIONS / ABREVIATIONS
For the purpose of this specification the following definitions shall hold:
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 5 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 6 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
The following codes are used in this specification to describe earthing arrangements as per IEC
60364-1.
First letter indicates the connection between earth and power supply equipment (e.g. transformers,
generators)
I All live parts isolated from earth, or one point connected
to earth through a high impedance.
T Direct connection of one point to earth
Second letter indicates the connection between earth and the electrical device being supplied
N direct electrical connection of the exposed-conductive-
parts to the earthed point of the power system (in a.c.
systems, the earthed point of the power system is normally
the neutral point or, if a neutral point is not available, a
line conductor)
T Direct electrical connection of exposed-conductive-parts
to earth, independently of the earthing of any point of the
power system
Subsequent letter (if any) are for the arrangement of protective and neutral conductor.
S Protective function provided by a conductor separate from
the neutral conductor or from the earthed line (or, in a.c.
systems, earthed phase) conductor.
2.2 Abbreviations
AC Alternative Current
DC Direct Current
EDG Essential Diesel Generating unit
EMC ElectroMagnetic Compatibility
EMG EMergency diesel Generating unit
EPCI Engineering, Procurement, Construction and Installation
ER Electrical Room
FLNG Floating Liquefied Natural Gas
HV High Voltage (> 1000V)
HVAC Heating, Ventilating, Air Cooling system
LER Local Equipment Room
LV Low Voltage (≤ 1000V)
PEC Parallel Earthing Conductor
STG Steam Turbine Generating unit
UPS Uninterruptible Power Supply
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 7 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 8 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
In the absence of alternate statement, it shall be understood that all requirements in this
specification and related documents are fulfilled without any exception.
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 9 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
Lloyds Register of Shipping is the selected Classification Society which shall provide the
Classification services.
It is mandatory that, during p-FEED and EPCI execution phase, Supplier contact the Lloyds
Register Classification Society for the performance of Classification services to ensure these
equipments are designed, manufactured and tested in accordance with the Lloyd’s Register
Classification Society rules (refer to the Vendor Liaison Document).
Where the earthing arrangements do not meet the Statutory and Classification requirements, it will
be demonstrated that the earthing system has been accepted under the 'Equivalents' provision stated
in Sub Clause 5.1.2. (e) of Part 6-Chapter 2-Section 5 of the Lloyd's Register Rules and
Regulations - for the Classification of Ships, July 2009.
The earthing system shall be designed in compliance with the following International Codes and
Standards:
IEC 61024 Protection of structures against lightning
IEC 60533 Electrical and electronic installations in ships - Electromagnetic
compatibility
IEC 61000-5-2 Electromagnetic Compatibility Part 5 Installation and mitigation
guidelines Section 2 Earthing and Bonding
IEC 60092-201 Electrical Installation in Ships – System Design General
IEC 60092-401 Electrical Installation in Ships – Installation and test of
completed installation
IEC 60092-502 Electrical Installation in Ships – Tankers- Special Features
IEC 60079-14 Explosive atmosphere: electrical installation, design, selection
and erection
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 10 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
Lloyd’s Register is the selected Classification Society for pFEED and shall provide Classification
Services.
Lloyd’s Register’s Rules and Regulations for the Classification of a Floating Offshore Installation
at a Fixed Location 2008 (the FOIFL Rules) shall apply.
3.8 Certification
Certification means an independent review and verification including relevant QC, inspections/
audits, and engineering calculations to assure that the object has been designed, fabricated and/or
installed, as required, to satisfy agreed upon rules stipulated by National and/or International
Regulations. National Regulations are to be understood as Australian Regulations in the present
case.
Lloyd’s Register is the selected Society for pFEED and shall provide Certification services.
System earthing of each part of the power system, operating at a specific voltage, shall be
considered individually. For insulated distribution systems, devices shall be installed to
continuously monitor the insulation to earth and to give an audible and visual alarm at a manned
position in the event of an abnormally low level of insulation resistance and/or high level of
leakage current.
The system neutral earthing connection to a three-phase AC system shall be taken from, or close to,
the star point of the generator or transformer, which constitutes the source of power. Neutral
connections shall be sized for the prospective system fault levels.
At the end of installation, earthing distribution shall be accessible for inspection. For generators,
the arrangement shall allow disconnection of the neutral earthing device from earth for
maintenance purpose.
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 11 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
Earthing materials located outdoors shall be suitable for an offshore location i.e. a highly corrosive
environment.
System earthing of earthed distribution systems shall be effected by means independent of any
earthing arrangements of exposed conductive parts (refer to 4.2).
4.2 HV systems
Common design criteria for HV system earthing are:
♦ Resistance earthing either by:
§ High-voltage resistor
§ Single phase distribution transformer loaded by a resistor on their secondary side
♦ Neutral earthing shall be on the source of supply only. HV systems neutrals shall be resistance
earthed at each source of supply, unless otherwise specified. Each neutral point shall be
individually earthed through a high-voltage resistor.
♦ Parallel earthing conductor shall be laid in parallel to all HV cables in order to provide a
preferred fault current return path.
♦ Where generators are connected to the main switchboard via individual transformers, each
generator neutral point shall be individually earthed through a single phase distribution
transformer loaded with a secondary resistor. The transformer and the resistor shall be rated to
limit the earth fault current supplied by the generator to 10 A, or to 3 x Ico where Ico is the per-
phase capacitive charging current, whichever is the greater (the per-phase capacitive current is
that due to the generator stator windings, machine side transformer winding and main power
cable/connections).
♦ Where generators are directly connected to HV switchboard, each generator neutral point shall
be individually earthed through a high-voltage resistor.
♦ Where HV rotating machines (synchronous or induction machines) are connected to the main
switchboard via individual transformers, the neutral point of the associated transformer (motor
side transformer winding) shall be individually earthed through a high-voltage resistor.
♦ Whenever required by the Classification Society rules or industry standard, HV systems neutrals
shall be isolated from earth (IT distribution system with permanent monitoring of the
distribution system insulation level).
♦ Motors neutral connections may require being accessible (e.g. protective functions such as
differential) but shall not be connected to earth.
♦ Where a switchboard is split into sections operated independently or where there are separate
switchboards, neutral earthing is to be provided for each section or for each switchboard.
Earthing devices shall be designed to operate paralleled whenever feasible: this configuration
avoids any specific control functions or maneuvers of HV switchgear for switching in/out the
earthing device as a function of the network operating configuration.
♦ Earthing devices should be sized to limit, in the most stringent operating case (in general, with
all incomers connected to associated switchboard), the total earth fault current to:
§ a value lower than the maximum short-circuit current withstand capacity of the equipment
including the HV cable screens and,
§ the rated full load current of the equipments,
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 12 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
§ a value sufficiently low to minimize damages to the stator core of directly connected AC
rotating machines in case of internal fault through the insulation (typically 10 to 50 amps
depending on the maximum short-circuit duration selected for design),
However, the final rating of earthing devices shall be selected with due consideration of the
protective scheme design requirements even if this requires waiving some of the above
recommendations:
§ selectivity of the protection system whatever the operating configuration (paralleled earthing
device or not),
§ coverage of at least 50% and preferably 90% of the source equipment windings against
internal fault i.e. any internal fault on a transformer or a generator considering the first 50%
(respectively 90%) of the winding (viewed from phase side) shall be detected. As a
consequence the neutral earthing device, whatever its technology shall be designed to
withstand a permanent current circulation of 55% (respectively 15%) of the maximum fault
current circulating in the neutral conductor of the source equipment.
♦ For a given voltage level, standardisation of earthing device rating shall be applied to the
maximum possible extent.
♦ As per project document [Neutral Earthing Device Specification], each resistor shall be rated to
withstand the respective earth fault currents for duration of not less than 10 s. Longer withstand
times may be required, depending on the earth fault protection system applied.
♦ Multiple parallel earthing points may be anticipated when designing the electrical distribution
system provided that:
§ The minimum magnitude of the earth fault current circulating in earthing device remains
high enough to be detected by the associated protective system.
§ The magnitude of the worst-case earth fault current remains compatible with the current
withstands capacity of the equipment (including the screen of HV cables). The maximum
earth fault current magnitude may be proposed higher than equipment rated full load current
provided it remain lower than the three-phase short-circuit current of the equipment.
§ The earthing point of the paralleled neutral earthing devices shall each be connected locally
to the hull or structure. In addition, paralleled neutral earthing devices shall be connected
together on the structure/hull side of the resistor, whereto also the protective earthing (PE)
conductor of the distribution system shall be connected. Suitable disconnecting links, which
allow for measuring purposes, shall be provided.
The following sub-sections describe the earthing philosophy and criteria applied to each of the HV
sub-systems existing in the anticipated network topology.
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 13 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
resistors shall each be rated so as to limit the single-phase to earth fault current to a maximum of
200 Amps.
The neutral earthing resistors shall be connected between the earth and the neutral star point of the
high-voltage windings of the 33/11.5kV (offload secondary voltage) unit step-up transformer.
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 14 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
To avoid circulating current between the various paralleled neutral earthing paths, the following
provision shall apply:
♦ The impedances; in particular zero sequence impedance of generators operating in parallel shall
be identical as far as practicable (manufacturing tolerance)
♦ the third order harmonic content (triplen harmonic current) of the waveform of the current
supplied by the generators shall be lower than the limits specified is Sub-Section (5.2.4.3.2) of
project document [Electrical Design Manual].
♦ When required, transformers, generators and their neutral earthing devices shall be suitably
design (e.g. de-rating) to cater for the effect of any circulation of triplen order current harmonic
content under the anticipated operating and service conditions (loading, network
configuration…).
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 15 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
All electrical equipment shall be connected to the earthing system such that the earth loop
impedance requirements for the associated protective devices are met.
TNS system could be with separate neutral conductor and protection conductor or with earthed
protection conductor and no distributed neutral conductor particularly when neutral conductor shall
not be used (MCC switchboard), see sketch from IEC 60364-1 in appendix 2.
Earth loop impedances shall be calculated in order to allow correct operation of protective devices
in accordance with dedicated tables of : cables sizing calculation note 2000-110-F001-UT01-
U40000-EA-8380-00005.
The Emergency diesel generating units (EMG) being connected directly to their respective LV
switchboard; their neutral (star connected winding) shall be directly connected to earth.
Common design criteria for LV system earthing are:
♦ Neutral earthing shall be on the source of supply only (generator or transformer neutral lead).
♦ Motors neutral connections may require being accessible (e.g. protective functions such as
differential) but shall not be connected to earth.
♦ Where a switchboard is split into sections operated independently or where there are separate
switchboards, neutral earthing is to be provided for each section or for each switchboard. Means
are to be provided to ensure that the earth connection is not removed when generators are
isolated.
♦ Where a switchboard is split into sections normally operated independently (NO position of the
bus-section circuit breaker), no specific arrangement shall be provided to prevent paralleled
earthing path (TN system multiple source system) when operating procedures anticipates only
temporary (few seconds duration) operation in this configuration.
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 16 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
♦ Where a switchboard is split into sections operated independently or where there are separate
switchboards, neutral earthing is to be provided for each section or for each switchboard. Means
are to be provided to ensure that the earth connection is not removed when generators are
isolated.
5.1 General
The earthing arrangement provided for the substructure (also referred therein as hull structure), the
living quarters, the topside modules and the turret shall be designed to reduce and control voltages
below an acceptable level for:
♦ Electrical safety i.e. to reduce touch and step voltage in case of earth faults
♦ Lightning and static electricity protection (prevention of fire and dangerous touch voltage)
♦ Intrinsic safety i.e. avoiding ignition sources in hazardous areas
♦ EMC i.e. reducing disturbing voltage at the terminal of electronic equipment
In line with the agreed practice for electrical installations in ships, the general mass of the metal
hull of the ship shall be considered as the earth (refer to sub-clause 1.3.8 of IEC 60092-101).
Furthermore, the main and secondary steel structure of the vessel substructure, the living quarters,
the topside modules and the turret steel structures shall be considered as constituting an inherently
very low impedance structure capable of conducting earth fault currents as well as high frequency
disturbing currents (e.g. from lightning strikes) without giving rise to sparks, dangerous touch
voltages or transients that are destructive for electronic equipment.
When welding is used between steelwork such as substructure, sub-frames and/or topside modules,
welds shall be considered as reliable and suitable electrically conducting paths provided that they
are of adequate cross sectional area and volume.
Whenever separate lift, platforms or modules are installed on the vessel without being welded to
the substructure, these shall be bonded to the substructure via at least two adequately sized separate
bonding conductors. The number and location of bonding conductors shall be increased as
necessary to maintain the meshed characteristics of the equipotential bonding system (distance
lower than 10 meters between bonding connections). In the particular case of the turret, bonding
continuity to the substructure shall be ensured via at least two dedicated and adequately sized slip-
rings.
All steel parts of the substructure, topside and turret shall be considered to constitute a satisfactory
equipotential bonding system provided the above mentioned principles are fulfilled.
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 17 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
The horizontal length of the earth bars will depend on the number of connections to be made but
shall include 20% spare capacity. Earth bars, when provided, shall be located in front of equipment
and junction boxes to allow for easy access for usage, inspection and maintenance. All earthing
bars and terminals shall be visible and possible to be checked also after termination of cables.
Separate connections shall be used for each individual earth conductor.
Every switchboard and sub-distribution boards (power distribution) shall be connected to the earth
by at least two earthing connections. Electrical auxiliary boards as well as control panels may be
connected by one earth connection only. Earthing connections shall be designed in compliance with
the requirements stated in sub-section (5.4).
The metallic frame of all electrical equipment such as transformers, rotating machines, etc shall be
provided with two dedicated earth terminals located diametrically opposite each other consisting of
M10 earth studs. The stud shall be supplied complete with anti-vibration spring washer and nuts.
Stud, washer and nuts materials shall be suitably selected with due consideration of the severe
ambient conditions (off-shore and the risk of electrochemical corrosion potential).
Any electrical equipment attached, but not welded, to the structure steelwork, for example to hand
rails, ladders and stairways, shall be bonded to the nearest structural steelwork.
Earthing conductors, required to bond the exposed conductive parts of main electrical equipment
(e.g. HV and LV generators, transformers, reactors, switchboards, motors and UPS units) to the
steelwork, shall be individually identified, and recorded on drawings. Typical detailed arrangement
of exposed conductive parts earthing are provided in project document [Outfitting Practice].
Applicable requirements for earthing of cable armours, cable shields and cable glands are specified
in Sub-Section (5.7).
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 18 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
Metal frames or enclosures of equipment mounted in direct metallic contact with the unit structure
need no supplementary bonding conductor, provided that the surfaces in contact are clean and free
from rust, scale or paint when installed and are firmly bolted together. Where this type of
conductive path is not possible then bonding conductor shall be provided between the equipment
and earth.
Packages, tanks and vessels and more generally all non electrical equipment that are welded to the
structural steelwork will require no additional bonding except where anti-vibration measures isolate
the equipment. Facilities (earth studs) shall be provided to install flexible bonding conductors
across large skid anti-vibration mounts to the equipotential bonding system in at least two
locations.
Packages, equipment skids, tanks and vessels and more generally all non electrical equipments that
require bonding conductors shall be provided with two earth terminals located diametrically
opposite each other. This shall be effected by the provision of M10 earth studs screwed into carbon
steel bosses, fillet welded to the skid base-frame. The stud shall be supplied complete with anti-
vibration spring washer and nuts. Stud, washer and nuts materials shall be suitably selected with
due consideration of the severe ambient conditions (off-shore), the eventual superimposed-current
cathodic protection and the risk of electrochemical corrosion potential.
Electrical continuity shall be maintained between HVAC ducting sections and between ducting and
the main structure.
Cranes shall be provided with a dedicated earth slip ring for connection to the equipotential
bonding system and copper bonding straps across hinged joints. These shall be the responsibility
of the crane Vendor.
Similar requirements shall apply to the turret which shall be provided with adequate slip rings to
ensure equalisation of potential between the turret and the rest of the vessel.
To minimize shock from high-frequency induced voltage, handles, handrails, etc., made of metal
shall be in good electrical connection with the hull or superstructure.
Extraneous conductive parts which are not part of the structure or of the electrical installation, for
example frame of doors or windows, need not be connected to the equipotential bonding system, if
there is no danger of voltage displacement.
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 19 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
Typical detailed arrangement of extraneous conductive parts bonding are provided in [Outfitting
Practice].
Applicable requirements for equipotential bonding of cable racks and cable trays are specified in
Sub-Section (5.8).
The minimum cross-sectional area of earthing and bonding conductors shall comply with the
requirements of IEC 60092-401 which main principles are recalled hereafter:
For purpose of standardisation, the following minimum conductor sizes shall apply for designing
earthing and bonding copper conductors. Earthing and bonding connections made of other
materials shall have a conductance not less than that specified for the copper connections.
Minimum copper
Intended use cross-sectional
area
Earthing of metallic enclosures of HV electrical equipment 70 mm²
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 20 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
Minimum copper
Intended use cross-sectional
area
Earthing of metallic enclosures of LV electrical equipment, having a 70 mm²
supply cable cross-sectional area ≥ 35 mm²
Earthing of metallic enclosures of LV electrical equipment, having a 25 mm²
supply cable cross-sectional area < 35 mm²
Earthing of control panels, marshalling cabinets, etc. 25 mm²
Earthing of reduced-size junction boxes and cubicles 6 mm²
Bonding of non-electrical equipment exposed to lightning, e.g., tanks, 70 mm²
columns and tall structures
Bonding of other non-electrical equipment 25 mm²
The main principles governing earthing of metal coverings of cables are recalled hereafter for
information only. Detailed technical requirements, as specified in the above mentioned project
specifications, may authorize exceptions to the following general rules.
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 21 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 22 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
Specific lightning protection shall be provided for all radio communication antenna installed on the
vessel in accordance with the relevant clause of IEC 60092-502 as supplemented in sub-section (6)
of project document [Instrument and Telecom Earthing Principle].
RESTRICTED 2000-110-F001-UT01-U40000-EA-5680-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 23 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
The following sub-sections define whether or how the requirements stated in the applicable
DEP 33.64.10.33-Gen – [Electromagnetic Compatibility (EMC) Requirements] shall be applied or,
as the case may be, shall be amended in line with the earthing system philosophy developed in the
present specification.. For ease of understanding, the title of these sub-sections recalls the number
of the associated sections of the COMPANY specification as well as being similar.
4.2 Bonding of Concrete and Steel Structures (sub-section 4.2 of DEP 33.64.10.33-Gen.)
4.2.4 Earthing and bonding of pipe racks, flare stacks and mechanical equipment
Requirements for earthing and bonding of pipe racks, flare stacks and mechanical equipment, as
stated in section (4.2.4) of COMPANY specification DEP 33.64.10.33-Gen. – [Electromagnetic
Compatibility (EMC) requirements] do not apply to the project. Earthing and bonding of pipe
racks, flare stacks and mechanical equipment shall be in accordance with the requirements
specified in sub-section (5.3) of the present specification.
RESTRICTED 2000-110-F001-UT01-U40000-EA-7704-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 24 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
4.5 Earthing and Bonding of Field Equipment and Junction Boxes (sub-section 4.5)
The principles governing earthing and bonding of field equipment and junction boxes, as stated in
section (4.5) of COMPANY specification DEP 33.64.10.33-Gen. – [Electromagnetic Compatibility
(EMC) requirements] shall be applied.
Junction boxes for equipment not sensitive to electromagnetic disturbances (e.g. lighting and
convenience power distribution) may be of non-metallic material.
RESTRICTED 2000-110-F001-UT01-U40000-EA-7704-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 25 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
4.6 Cable Entry Frames and Bonding of Metallic Services (sub-section 4.6)
The principles governing selection of cable entry frame and bonding of metallic services, as stated
in sub-section (4.6) of COMPANY specification DEP 33.64.10.33-Gen. – [Electromagnetic
Compatibility (EMC) requirements] shall be applied as adapted to ship environment (cable entry
frame welded to the substructure) and described in project document [Electrical Installation Design
Specification].
Except for sub-sections (5.7) and (5.8.4) which are not applicable, cabling and wiring shall comply
with the principles defined section (5) of COMPANY specification DEP 33.64.10.33-Gen. –
[Electromagnetic Compatibility (EMC) requirements] as amended in present project specification.
RESTRICTED 2000-110-F001-UT01-U40000-EA-7704-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 26 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
RESTRICTED 2000-110-F001-UT01-U40000-EA-7704-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 27 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
RESTRICTED 2000-110-F001-UT01-U40000-EA-7704-00005_01A
TSC Document number
Project n° Area-Unit Code Doc. type Material code Sequential No
ECCN Code EAR99 2000 110 F001 UT01 U40000 EA 5680 00005 01A 28 of 28
Prelude FLNG Project ELECTRICAL SYSTEM EARTHING DESIGN PHILOSOPHY
RESTRICTED 2000-110-F001-UT01-U40000-EA-7704-00005_01A