Automatic Transfer Switch - Zabatt

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Automatic Transfer Switch

Owner’s Manual
ATS Service Entrance
HS Type Transfer Switch

Models: 005036-0, 100 Amp, 250 Volts


and 004945-1, 200 Amp, 250 Volts

This manual should remain with the unit.


IMPORTANT SAFETY INSTRUCTIONS

 followed during installation and maintenance of the generator and batteries.


SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be

 install, operate or service this equipment. Also read the instructions and information on tags, 
SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to

decals, and labels that may be affixed to the transfer switch. Replace any decal or label that
is no longer legible.

 utility shall be by means of suitable transfer equipment so as to isolate the electric system 
DANGER! Connection of a generator to an electrical system normally supplied by an electric

from utility distribution system when the generator is operating (Article 701 Legally Required
Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate
electric system by these means may result in damage to generator and may result in injury
or death to utility workers due to backfeed of electrical energy.

Generac Power Systems, Inc., hereafter referred to as Four commonly used safety symbols accompany the
the “manufacturer”, cannot anticipate every possible DANGER, WARNING and CAUTION blocks. The type
circumstance that might involve a hazard. The warn- of information each indicates follows:
ings in this manual, and on tags and decals affixed
to the unit are, therefore, not all-inclusive. If using  This symbol points out important safety infor-
mation that, if not followed, could endanger
a procedure, work method or operating technique
the manufacturer does not specifically recommend, personal safety and/or property.
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique cho-  This
ard.
symbol points out potential explosion haz-

sen does not render the transfer switch unsafe.


Throughout this publication, and on tags and decals  This symbol points out potential fire hazard.
affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert person-  This symbol points out potential electrical shock
nel to special instructions about a particular opera- hazard.
tion that may be hazardous if performed incorrectly
or carelessly. Observe them carefully. Their defini-
tions are as follows:
 GENERAL HAZARDS 
• Any AC generator that is used for backup power if
DANGER a NORMAL (UTILITY) power source failure occurs,
must be isolated from the NORMAL (UTILITY)
After this heading, read instructions that, if not power source by means of an approved transfer
strictly complied with, will result in personal inju- switch. Failure to properly isolate the NORMAL
ry, including without limitation, death, or property and STANDBY power sources from each other may
damage. result in injury or death to electric utility workers,
due to backfeed of electrical energy.
• Improper or unauthorized installation, operation,
After this heading, read instructions that, if not service or repair of the equipment is extremely
strictly complied with, may result in personal inju- dangerous and may result in death, serious per-
ry or property damage. sonal injury, or damage to equipment and/or per-
sonal property.
• Extremely high and dangerous power voltages are
present inside an installed transfer switch. Any
After this heading, read instructions that, if not contact with high voltage terminals, contacts or
strictly complied with, could result in damage to wires will result in extremely hazardous, and pos-
equipment and/or property. sibly LETHAL, electric shock. DO NOT WORK ON
NOTE: THE TRANSFER SWITCH UNTIL ALL POWER
After this heading, read explanatory statements VOLTAGE SUPPLIES TO THE SWITCH HAVE
that require special emphasis. BEEN POSITIVELY TURNED OFF.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compli-
ance with the special instructions while performing
the service are essential to preventing accidents.
Table of Contents

• Competent, qualified personnel should install, Safety Rules .........................................Inside Front Cover
operate and service this equipment. Adhere strictly Section 1 — General Information ...................................2
to local, state and national electrical and building
1.1 Introduction............................................................. 2
codes. When using this equipment, comply with
regulations the National Electrical Code (NEC), 1.2 Equipment Description ........................................... 2
CSA Standard; C22.1 Canadian Electric Code and 1.2.1 Transfer Switch Mechanism .......................... 2
Occupational Safety and Health Administration 1.2.2 Service Disconnect Circuit Breaker ............... 2
(OSHA) have established. 1.3 Transfer Switch Data Decal ..................................... 2
• Never handle any kind of electrical device while 1.4 Transfer Switch Enclosure ...................................... 3
standing in water, while barefoot, or while hands or 1.5 Safe Use Of Transfer Switch .................................... 3
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT. Section 2 — Installation ....................................................3
• Jewelry conducts electricity and wearing it may 2.1 Introduction to Installation ...................................... 3
cause dangerous electrical shock. Remove all jew- 2.2 Unpacking ............................................................... 3
elry (such as rings, watches, bracelets, etc.) before 2.3 Mounting ................................................................. 3
working on this equipment. 2.4 Connecting Power Source and Load Lines ............... 3
• If work must be done on this equipment while 2.5 Connecting Start Circuit Wires ................................ 4
standing on metal or concrete, place insulative
mats over a dry wood platform. Work on this Section 3 — Operation.......................................................4
equipment only while standing on such insulative 3.1 Functional Tests & Adjustments .............................. 4
mats. 3.2 Manual Operation .................................................... 4
• Never work on this equipment while physically or 3.2.1 Close to Normal Source Side ........................ 5
mentally fatigued. 3.2.2 Close to Emergency Source Side ................... 5
• Keep the transfer switch enclosure door closed 3.2.3 Return to Normal Source Side ...................... 5
and bolted at all times. Only qualified personnel 3.3 Voltage Checks......................................................... 6
should be permitted access to the switch interior.
3.4 Generator Tests Under Load ................................... 6
• In case of an accident caused by electric shock,
immediately shut down the source of electrical Section 4 – Installation Diagram ....................................7
power. If this is not possible, attempt to free the Section 5 – Electrical Data ...............................................8
victim from the live conductor but AVOID DIRECT Section 6 – Exploded Views & Parts Lists ..................12
CONTACT WITH THE VICTIM. Use a nonconduct-
ing implement, such as a dry rope or board, to free Section 7 – Notes .............................................................16
the victim from the live conductor. If the victim is Section 8 – Warranty ...................................... Back Cover
unconscious, apply first aid and get immediate
medical help.
• When an automatic transfer switch is installed for
a standby generator set, the generator engine may
crank and start at any time without warning. To
avoid possible injury that might be caused by such
sudden start-ups, the system’s automatic start cir-
cuit must be disabled before working on or around
the generator or transfer switch. For that purpose,
a SAFETY DISCONNECT is provided inside the
transfer switch. Always set that switch to its OFF
position before working on the equipment. Then
place a “DO NOT OPERATE” tag on the transfer
switch and on the generator. Remove the Negative
(Neg) or (–) battery cable.

For authorized service,


reference the dealer locator
number found in the generator
owner’s manual.

1
Section 1 — General Information
ATS “HS” Type Transfer Switch

1.1 INTRODUCTION Figure 1.1 — Typical ATS Transfer Mechanism


This manual has been prepared especially for the
UTILITY LUGS
purpose of familiarizing personnel with the design,
application, installation, operation and servicing of
the applicable equipment. Read the manual carefully UTILITY
CLOSING
and comply with all instructions. This will help to COIL
prevent accidents or damage to equipment that might
otherwise be caused by carelessness, incorrect appli-
cation, or improper procedures.
Every effort has been expended to make sure that the
contents of this manual are both accurate and cur- GENERATOR
rent. The manufacturer, however, reserves the right LUGS (E1 & E2)
to change, alter or otherwise improve the product at GENERATOR
CLOSING
any time without prior notice. COIL

1.2 EQUIPMENT DESCRIPTION


The automatic transfer switch is used for transfer- LOAD LUGS (T1 & T2)
ring electrical load from a UTILITY (NORMAL) power
source to an EMERGENCY (STANDBY) power source. This transfer switch is for use in optional standby
Such a transfer of electrical loads occurs automati- systems only.
cally when the UTILITY power source has failed or is
substantially reduced and the EMERGENCY source This transfer switch is suitable for use on a circuit
voltage and frequency have reached an acceptable capable of 10,000 rms symmetrical amperes, 240
level. The transfer switch prevents electrical feedback VAC maximum.
between two different power sources (such as the
UTILITY and EMERGENCY sources) and, for that ‹ 1.2.2 SERVICE DISCONNECT CIRCUIT
reason, codes require it in all standby electric system BREAKER
installations.
The service disconnect circuit breaker for the 100
The transfer switch consists of a transfer mecha- amp models are:
nism, service disconnect circuit breaker, a relay
control, fuses, and a terminal strip for connection of • Siemens, Type BQ, 2-pole
sensing wires. • 120/240VAC, 100A
This transfer switch is suitable for use as service • 50/60 Hertz
entrance equipment. • Heating, Air Conditioning and Refrigeration (HACR)
rated
• Wire range: #1 - #8 AWG.
‹ 1.2.1 TRANSFER SWITCH MECHANISM
• The conductor tightening torque is 50 in-lbs.
These switches (Figure 1.1) are used with a single-
phase system, when the single-phase NEUTRAL line The service disconnect circuit breaker for the 200
is to be connected to a Neutral Lug and is not to be amp models are:
switched. • Siemens, Type QN, 2-pole
Solderless, screw-type terminal lugs are standard. • 120/240VAC, 200A
• 50/60 Hertz
Switch Wire Conductor Tightening
• Heating, Air Conditioning and Refrigeration (HACR)
Rating Range Torque
rated
100A #14-1/0 AWG 50 in-lbs.
• Wire range: 300 KCMIL - 4 AWG
200A #6-250 MCM 275 in-lbs.
• The conductor tightening torque is 250 in-lbs.
This transfer switch is suitable for control of motors,
electric discharge lamps, tungsten filament and elec- 1.3 TRANSFER SWITCH DATA DECAL
tric heating equipment where the sum of motor full A DATA DECAL is permanently affixed to the transfer
load ampere ratings and the ampere ratings of other switch enclosure. Use this transfer switch only with
loads do not exceed the ampere rating of the switch the specific limits shown on the DATA DECAL and
and the tungsten load does not exceed 30 percent of on other decals and labels that may be affixed to the
the switch rating. switch. This will prevent damage to equipment and
property.
2
Section 2 — Installation
GTS “HS” Type Transfer Switch

When requesting information or ordering parts for this


equipment, make sure to include all information from
2.3 MOUNTING
Mounting dimensions for the transfer switch enclo-
the DATA DECAL. sure are in this manual. Enclosures are typically
Record the Model and Serial numbers in the space wall-mounted. See “Installation Diagram”, Section 5.
provided below for future reference.

MODEL #
 Handle transfer switches carefully when install-
ing. Do not drop the switch. Protect the switch
SERIAL # against impact at all times, and against construc-
tion grit and metal chips. Never install a transfer
switch that has been damaged.
This transfer switch is mounted in a NEMA 3R enclo-
1.4 TRANSFER SWITCH ENCLOSURE sure. It can be mounted outside or inside and should
The standard switch enclosure is a National be based on the layout of installation, convenience
Electrical Manufacturer’s Association (NEMA) 3R and proximity to the utility supply and load center.
type. NEMA 3R type enclosures primarily provide Install the transfer switch as close as possible to the
a degree of protection against falling rain and sleet electrical loads that are to be connected to it. Mount
and is undamaged by the formation of ice on the the switch vertically to a rigid supporting structure.
enclosure. To prevent switch distortion, level all mounting
points. If necessary, use washers behind mounting
1.5 SAFE USE OF TRANSFER SWITCH holes to level the unit.
Before installing, operating or servicing this equip-
ment, read the SAFETY RULES (inside front cover) 2.4 CONNECTING POWER SOURCE
carefully. Comply strictly with all SAFETY RULES to
prevent accidents and/or damage to the equipment. AND LOAD LINES
The manufacturer recommends that a copy of the
SAFETY RULES are posted near the transfer switch. DANGER
Also, be sure to read all instructions and information
found on tags, labels and decals affixed to the equip-  Make sure to turn OFF both the UTILITY
(NORMAL) and EMERGENCY ( STANDBY) power
ment.
supplies before trying to connect power source
Two publications that outline the safe use of transfer and load lines to the transfer switch. Supply
switches are the following: voltages are extremely high and dangerous.
• NFPA 70; National Electrical Code Contact with such high voltage power sup-
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC ply lines causes extremely hazardous, possibly
TRANSFER SWITCHES lethal, electrical shock.
Wiring diagrams and electrical schematics are pro-
2.1 INTRODUCTION TO INSTALLATION vided in this manual.
This equipment has been wired and tested at the Two suggested installation methods are shown. One
factory. Installing the switch includes the following for new installations and/or retrofit and one for ret-
procedures: rofit.
• Mounting the enclosure. NOTE:
• Connecting power source and load leads.
All installations must comply with national, state
• Connecting the generator sensing and transfer
and local codes. It is the responsibility of the
relay circuits.
installer to perform an installation that will pass
• Connecting any auxiliary contact (if needed) the final electrical inspection.
• Testing functions.
The utility supply connection is made at the circuit
2.2 UNPACKING breaker terminals. The generator supply and custom-
er load connections are made at the transfer switch
Carefully unpack the transfer switch. Inspect closely
for any damage that might have occurred during ship- mechanism, inside the switch enclosure.
ment. The purchaser must file with the carrier any
claims for loss or damage incurred while in transit.
Check that all packing material is completely removed
from the switch prior to installation.
3
Section 3 — Operation
ATS “HS” Type Transfer Switch

Conductor sizes must be adequate to handle the NOTE:


maximum current to which they will be subjected to,
based on the 75°C column of tables, charts, etc. used When this ATS is used with an air-cooled genera-
to size conductors. The installation must comply fully tor, the LOAD 1 and LOAD 2 wires are not used.
with all applicable codes, standards and regulations.
Before connecting wiring cables to terminals, remove 3.1 FUNCTIONAL TESTS AND
any surface oxides from the cable ends with a wire
brush. All power cables must enter the enclosure
ADJUSTMENTS
Following transfer switch installation and inter-
through the knockouts. If not using the knockouts, connection, inspect the entire installation care-
entry must be at or below knockouts. If ALUMINUM
fully. A competent, qualified electrician should
conductors are used, apply corrosion inhibitor to
conductors. Tighten terminal lugs to the torque inspect it. The installation should comply strictly
values as noted in Section 1.2.2, and on the decal with all applicable codes, standards, and regula-
located on the inside of the door. After tightening ter- tions. When absolutely certain the installation is
minal lugs, carefully wipe away any excess corrosion proper and correct, complete a functional test of
inhibitor. the system.

 Use a torque wrench to tighten the conduc-


tors, being sure not to overtighten, or damage
 Perform functional tests in the exact order pre-
sented in this manual, or damage could be done
to the switch base could occur. If not tightened to the switch.
enough, a loose connection would result, caus- IMPORTANT: Before proceeding with functional tests,
ing excess heat which could damage the switch read and make sure all instructions and information
base. in this section are understood. Also read the infor-
Connect power source load conductors to clearly mation and instructions of labels and decals affixed
marked transfer mechanism terminal lugs as fol- to the switch. Note any options or accessories that
lows might be installed and review their operation.
1. Connect UTILITY (NORMAL) power source cables
to circuit breaker. 3.2 MANUAL OPERATION
2. Connect EMERGENCY (STANDBY) source power DANGER
cables to transfer switch terminals E1, E2.
3. Connect customer LOAD leads to switch termi-
nals T1, T2.
 Do NOT manually transfer under load.
Disconnect transfer switch from all power sourc-
Conductors must be properly supported, of approved es by approved means, such as the main circuit
insulative qualities, protected by approved conduit, breaker(s).
and of the correct wire gauge size in accordance with A manual HANDLE is shipped with the transfer
applicable codes. switch. Manual operation must be checked BEFORE
Be sure to maintain proper electrical clearance the transfer switch is operated electrically. To check
between live metal parts and grounded metal. Allow manual operation, proceed as follows:
at least 1/2 inch for 100-400 amp circuits. 1. Turn the generator’s AUTO/OFF/MANUAL switch
to OFF.
2.5 CONNECTING START CIRCUIT 2. Turn OFF both UTILITY (service disconnect cir-
cuit breaker) and EMERGENCY (generator main
WIRES line to circuit breaker) power supplies to the
Control system interconnections consist of N1 and transfer switch.
N2, T1 and T2, and leads 23 and 194. Control system 3. Turn the GENERATOR DISCONNECT SWITCH
interconnection leads must be run in a conduit that to the OFF position.
is separate from the AC power lead. Recommended
4. Note position of transfer mechanism main con-
wire gauge sizes for this wiring depends on the length
tacts by observing the moveable contact carrier
of the wire, as recommended below:
arm. This can be viewed through the long narrow
MAXIMUM WIRE LENGTH RECOMMENDED WIRE slot in the inside cover of the ATS. The top of the
SIZE moveable contact carrier arm is yellow to be eas-
460 feet (140m) No. 18 AWG. ily identified.
461 to 730 feet (223m) No. 16 AWG. • Manual operation handle in the UP position -
731 to 1,160 feet (354m) No. 14 AWG. LOAD terminals (T1, T2) are connected to UTIL-
1,160 to 1,850 feet (565m) No. 12 AWG. ITY terminals (N1, N2).
4
Section 3 — Operation
ATS “HS” Type Transfer Switch

Figure 3.1 — Actuating Transfer Switch

Attach handle to
the moveable contact
carrier arm.

NOTE: Return handle to


storage position in enclosure
when finished with manual transfer.

Move handle UP for the


NORMAL (UTILITY) position.

Move handle DOWN for the


STANDBY (EMERGENCY)
position.

• Manual operation handle in the DOWN posi- ‹ 3.2.2 CLOSE TO EMERGENCY SOURCE SIDE
tion - LOAD terminals (T1, T2) are connected to
EMERGENCY terminals (E1, E2). Before proceeding, verify the position of the switch
by observing the position of the manual operation
handle in Figure 3.1. If the handle is DOWN, the
contacts are closed in the EMERGENCY (STANDBY)
 Do not use excessive force when operating the
transfer switch manually or damage could be
position. No further action is required. If the handle
is UP, proceed with Step 1.
done to the manual handle.
Step 1: With the handle inserted into the moveable
contact carrier arm, move the handle DOWN.
‹ 3.2.1 CLOSE TO NORMAL SOURCE SIDE Be sure to hold on to the handle as it will
Before proceeding, verify the position of the switch by move quickly after the center of travel.
observing the position of manual operation handle in Step 2: Remove manual operating handle from move-
Figure 3.1. If the handle is UP, the contacts are closed able contact carrier arm. Return handle to
in the NORMAL (UTILITY) position, no further action storage bracket.
is required. If the handle is DOWN, proceed with Step
1. ‹ 3.2.3 RETURN TO NORMAL SOURCE SIDE
Step 1: With the handle inserted into the moveable Step 1: Manually actuate switch to return manual
contact carrier arm, move handle UP. Be operating handle to the UP position.
sure to hold on to the handle as it will move
Step 2: Remove manual operating handle from move-
quickly after the center of travel.
able contact carrier arm. Return handle to
Step 2: Remove manual operating handle from move- storage bracket.
able contact carrier arm. Return handle to
storage bracket.
5
Section 3 — Operation
ATS “HS” Type Transfer Switch

3.3 VOLTAGE CHECKS NOTE:


1. Turn ON the UTILITY power supply to the trans- Do NOT proceed until generator AC output volt-
fer switch using the service disconnect circuit age and frequency are correct and within stated
breaker. limits. If the no-load voltage is correct but no-load
frequency is incorrect, the engine governed speed
DANGER may require adjustment. If no-load frequency is
correct but voltage is not, the voltage regulator
 PROCEED WITH CAUTION. THE TRANSFER
SWITCH IS NOW ELECTRICALLY HOT. CONTACT
may require adjustment.
WITH LIVE TERMINALS RESULTS IN EXTREMELY
HAZARDOUS AND POSSIBLY FATAL ELECTRICAL 3.4 GENERATOR TESTS UNDER LOAD
SHOCK. 1. Set the generator's main circuit breaker to its
2. With an accurate AC voltmeter, check for correct OFF or OPEN position.
voltage. Measure across ATS terminal lugs N1 2. Manually actuate the transfer switch main con-
and N2. Also check N1 to NEUTRAL and N2 to tacts to their EMERGENCY (STANDBY) position.
NEUTRAL. Refer to Manual Operation (Section 3.2).
3. When certain that UTILITY supply voltage is cor- 3. To start the generator, set the AUTO/OFF/ MANUAL
rect and compatible with transfer switch ratings, switch to MANUAL. When engine starts, let it sta-
turn OFF the UTILITY supply to the transfer bilize for a few minutes.
switch. 4. Turn the generator's main circuit breaker to its
4. On the generator panel, set the AUTO/OFF/ ON or CLOSED position. The generator now pow-
MANUAL switch to MANUAL position. The gen- ers all LOAD circuits. Check generator operation
erator should crank and start. under load as follows:
5. Let the generator stabilize and warm up at no- • Turn ON electrical loads to the full rated watt-
load for at least five minutes. age/amperage capacity of the generator. DO
6. Turn the GENERATOR DISCONNECT SWITCH NOT OVERLOAD.
to the ON position. • With maximum rated load applied, check
7. Set the generator's main circuit breaker (CB1) to voltage and frequency across transfer switch
its ON or CLOSED position. terminals E1 and E2. Voltage should be
greater than 230VAC and frequency should be
DANGER greater than 59 Hertz.
 PROCEED WITH CAUTION. GENERATOR
OUTPUT VOLTAGE IS NOW BEING DELIVERED
• Let the generator run under rated load for at
least 30 minutes. With unit running, listen for
TO TRANSFER SWITCH TERMINALS. CONTACT unusual noises, vibration, overheating, etc.,
WITH LIVE TERMINALS RESULTS IN EXTREMELY that might indicate a problem.
DANGEROUS AND POSSIBLY FATAL ELECTRICAL 5. When checkout under load is complete, set main
SHOCK. circuit breaker of the generator to its OFF or
8. With an accurate AC voltmeter and frequency OPEN position.
meter, check the no-load, voltage and frequency. 6. Let the generator run at no-load for several
Measure across ATS terminal lugs E1 to E2. Also minutes. Then, shut down by setting the AUTO/
check E1 to NEUTRAL and E2 to NEUTRAL. OFF/MANUAL switch to its OFF position.
a. Frequency ....................................... 60-62 Hertz 7. Move the switch's main contacts back to their
b. Terminals E1 to E2 ........................ 240-246 VAC
UTILITY position. For example, LOAD connect-
ed to UTILITY power supply. Refer to Manual
c. Terminals E1 to NEUTRAL............. 120-123 VAC
Operation (Section 3.2). Handle and operating
d. Terminals E2 to NEUTRAL............. 120-123 VAC lever of transfer switch should be in UP posi-
9. Set the generator’s main circuit breaker (CB1) to tion.
its OFF or OPEN position. 8. Turn on the utility power supply to transfer
10. Set the AUTO/OFF/MANUAL switch to the switch, using whatever means provided (such
OFF position to shut down the generator. as a utility main line circuit breaker). The utility
power source now powers the loads.
9. Set the generator's AUTO/OFF/MANUAL switch to
its AUTO position.
10. Set the GENERATOR DISCONNECT SWITCH to
the ON position. The system is now set for fully
automatic operation.

6
Section 4 — Installation Diagram
ATS “HS” Type Transfer Switch
Drawing No. 0F0016-B

271mm[10.67"] 26.5mm[1.04"]

0A6599tv
MOUNTING HOLES 0A6599tv

Ø6.3mm[Ø0.25"]

597mm[23.50"] 561mm[22.09"

PADLOCK
(CUSTOMER SUPPLIED)
0A
LOCATION

34mm[1.34"]

179.5mm[7.07"] KNOCKOUT SUITABLE


FOR 3/4" & 1" CONDUIT SIZE
KNOCKOUT SUITABLE FOR
1", 1-1/4", 1-1/2" CONDUIT SIZE KNOCKOUT SUITABLE
3 PLACES FOR 1", 1-1/4", 1-1/2" CONDUIT SIZE
324mm[12.76"]

7
IF ATS IS USED AS SERVICE ENTRANCE

8
DEVICE A BONDING JUMPER WILL NEED
TO BE INSTALLED SIZED TO MEET
NATIONAL & LOCAL CODES.

UTILITY
METER
SOCKET

SERVICE DISCONNECT
ATS
Section 5 — Electrical Data
ATS “HS” Type Transfer Switch

T2
E1 NOTE: INSTALLATION TO BE DONE BY A
LICENSED ELECTRICIAN AND MUST
MEET ALL NATIONAL, STATE AND
LOCAL ELECTRICAL CODES.

GROUND BAR

22
33
Transfer Switch Interconnections - Drawing No. 0F0017-A

FROM
ALTERNATOR
11 STATOR
44

E1 E2 GROUND BAR DISCONNECT


BONDING
CONNECTION
N1 IN PANELBOARD
N2
*-WIRES T1 & T2 NOT NEUTRAL BAR
USED ON AIR COOLED UNITS
AND SOME LIQUID COOLED UNITS PANELBOARD
194

NEW INSTALLATION
OR RETROFIT
AC GENERATOR
CONTROL PANEL
Section 5 — Electrical Data
ATS “HS” Type Transfer Switch
Transfer Switch Interconnections - Drawing No. 0F0017-A

IF ATS IS USED AS SERVICE ENTRANCE


DEVICE A BONDING JUMPER WILL NEED
TO BE INSTALLED SIZED TO MEET
NATIONAL & LOCAL CODES.

UTILITY
METER
SOCKET

SERVICE DISCONNECT
ATS

INSULATED SPLICING
CONNECTOR OR
(NEW WIRES CAN BE
PULLED FROM ATS &
PANELBOARD).

E2
T2
E1 NOTE: INSTALLATION TO BE DONE BY A
LICENSED ELECTRICIAN AND MUST
MEET ALL NATIONAL, STATE AND
LOCAL ELECTRICAL CODES.

22
33
FROM
EXISTING WIRES TO ALTERNATOR
11 STATOR
PANELBOARD
44
(SEE ABOVE NOTE)

E1 E2

N1
N2
T1 * *-WIRES T1 & T2 NOT
T2 *
USED ON AIR COOLED UNITS
23 AND SOME LIQUID COOLED UNITS
194
NEUTRAL BAR
DISCONNECT
BONDING
CONNECTION
IN PANELBOARD
RETROFIT
GROUND BAR
AC GENERATOR
PANELBOARD
CONTROL PANEL

9
Section 5 — Electrical Data
ATS “HS” Type Transfer Switch
Wiring Diagram/Schematic - Drawing No. 0F0015-A

10
Section 5 — Electrical Data
ATS “HS” Type Transfer Switch
Wiring Diagram/Schematic - Drawing No. 0F0015-A

11
VIEW SHOWN WITH ITEMS #18 & #19 REMOVED

16 15

12
2 3 33

50 INSIDE RIGHT SIDE TERMINAL TIGHTENING


17 TORQUE 50 INCH-POUNDS
!
6
44

RATING
SWITCH
4 32
22 INSIDE LEFT SIDE

#0C1026 OR #0D8440 0R #0E0117 OR #0E5241A


0A6599tv 0A6599tv

OR ALUUMINUM WIRE OF AT LEAST 75° c RATING


0A6599tv 0A6599tv

ALL TERMINALS LUGS ARE SUITABLE FOR COPPER

SWITCH IS FOR USE WITH CONTROL PANEL ASSEMBLY


22097-S
1/4 STL

22473-S
1-4X20STL 22473-S
1-4X20STL
10
0A9457

0C4449A-RS
MAXIMUM AMPS - 100
MAXIMUM VOLTS - 240
WAUKESHA, WI.
19

TRANSFER SYSTEM DATA


GENERAC POWER SYSTEMS, INC.
47

0F2710

SERIAL NUMBER
MODEL NUMBER
26 46

SYSTEM VOLTAGE
43
11 12 31 31

63378-T
DETAIL A-A
(POWER TERMINAL LUG ASSY)
48
NOTE:
TIGHTEN ITEM #43: 24-30 IN/LBS

TERMINAL TIGHTENING

D2806-E
30A, 600V
18 27 TORQUE 50 INCH-POUNDS
!

D2806-T
30A, 600V
63378-T

TERM. XA1
TERM. XA2
63378-T

Replace with UL SWITCH XA


44
listed fuse of same
type and rating
TERM. XA3

63378-T
600 Volt, 5 amp.
0D3587 A SWITCH LEVER

SWITCH LEVER
TERM. XB3

SWITCH XB

52 A
TERM. XB2 46
TERM. XB1

43

63378-T
53 54
B
DETAIL B-B
(POWER TERMINAL LUG ASSY)
D2806-T
51
ATS “HS” Type Transfer Switch

30A, 600V
E1
NOTE:
TIGHTEN ITEM #43: 24-30 IN/LBS
B
B NOTE:
S-6082D
V006 ,A03
21 ASSEMBLE SENSING WIRE
RING TERMINALS SO

63378-T
CLEARANCE IS GIVEN FOR
11 12 31 63378-T 63378-T
ACCESS TO LOWER LUG
SCREWS.

E-05884
1
47822-T

LISTED
R 5
C US
AUTOMATIC TRANSFER SWITCH
FOR USE IN OPTIONAL
STAND-BY SYSTEMS
64NL

N1
N2
T1
T2
23
194
B 13

(12 VDC)
(12 VDC)

(240 VAC)
(240 VAC)
(240 VAC)
(240 VAC)
NEUTRAL

WIRE
WIRE
WIRE
WIRE
WIRE
WIRE

(OPTIONAL)
WARNING
P/N 0A2595
NOTE WIRE ORIENTATION
CUSTOMER CONNECTIONS
0A6599tv 0A6599tv
8
Section 6 — Exploded Views and Parts List

22097-S
1/4 STL

22473-S
1-4X20STL 22473-S
1-4X20STL

14 30

8 37 37 38
36
QTY. 2 ITEM #37's BELOW SUBPLATE
QTY. 1 ITEM #37 ABOVE SUBPLATE
4 PLACES
100A Transfer Switch Assembly – Drawing No. 0F0466$-D

9 34 35 DECAL DETAILS
TERMINAL TIGHTENING VIEWS SHOWN WITH ITEMS #18 & #19 FULLY ASSEMBLED
TORQUE 45 INCH-POUNDS (NOT TO SCALE)
DETAIL "A"
! 28
24 7

19

34
0E9999

20
0E3485

35
40 41 42

ENCLOSURE
29
INSIDE
DETAIL A OF
0E3484
COVER
(GROUND LUG ASSEMBLY)
23

0C8308

49 45 18
Section 6 — Exploded Views and Parts List
ATS “HS” Type Transfer Switch
100A Transfer Switch Assembly – Drawing No. 0F0466$-D

ITEM PART NO. QTY. DESCRIPTION

1 0C2237 1 TRANSFER SW-HSB 100A 2P 250V


2 0E7886H 1 CB 0100A 2P 240V S BQ2 LB
3 0E7890 1 BRKT CB MTG BACK
4 0E9906 1 BRACKET, DISCONNECT SWITCH 100A
5 063378 8 HOLDER, CABLE TIE
6 0D3728 1 SWITCH TOG SPST 15A @ 125V
7 0E9999 1 DECAL SERVICE DISCONNECT SWITCH
8 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR
9 0E6523 1 GROUND BAR (5)4-14 AWG CONN
10 *** 063617 1 RELAY PNL 12VDC DPDT 10A@240VA
11 *** 0D2806 2 FUSEBLOCK 30A 600V 2POS W/SQ
12 073590A 4 FUSE 5A X BUSS
13 *** 047822 1 BLOCK TERM 20A 7 X 6 X 1100V
14 0A1661 2 RIVET POP .156 X .675 AL
15 0C4449 1 ASS’Y-NTRL BL 150-200A
16 090388 2 SCREW HHTT M6-1.0 X 12 ZINC
17 0E1473 1 WELDMENT TRANSFER SWITCH BOX
18 0E9907 1 COVER INSIDE XFER SWITCH BOX
19 0E1477 1 COVER TRANSFER SWITCH BOX
20 0F0668 1 DECALTRANSFER SWITCH
21 0E3070 1 SUBPLT XFER SW HSB
22 0E9734 REF DECAL SWITCH RATING
23 0E3484 1 DECAL WARN MANUAL OPER HANDLE
24 0E3485 1 DECAL SERVICE DISCONNECT
25 067210A 1 DECAL GROUND LUG (NOT SHOWN)
26 0A9457 1 DECAL NEUTRAL
27 0D3587 1 DECAL FUSE REPLACEMENT
28 0A2595 1 DECAL TERMINAL STRIP
29 0F0776 1 DECAL TEST SEQ. 2P TS HS 3R
30 081221 1 DECAL-UL LIST HSB
31 045764 6 SCREW HHTT M4-0.7 X 8 BP
32 074908 2 SCREW HHTT M5-0.8 X 10 BP
33 066849B 2 SCREW HHTT M5-0.8 X 8 BP
34 0C3992 2 SCREW HHTT M4-0.7 X 16 BP
35 026579 2 WASHER SHAKEPROOF EXT #8 STEEL
36 0E7213 2 SCREW THUMB 1/4-20 X 1/2 W/SHLD
37 022473 8 WASHER FLAT 1/4-M6 ZINC
38 022097 4 WASHER LOCK M6-1/4
39 0E9987 1 WIRE HARNESS HSB (NOT SHOWN)
40 0E6193 1 BRACKET ARM EXTENDER
41 064526 2 SCREW HWHS #6-25 X 3/8 ZNC
42 ** 0E6155 1 ARM EXTENDER PIN
43 036933 6 SCREW PPHM #10-32 X 3/8
44 077033 6 LUG SLDLSS 1/0-#14X9/16 AL/CU
45 0C8308 1 DECAL TERMINAL SHOCK HAZARD
46 022152 6 WASHER LOCK #10
47 0912970085 1 WIRE ASSY 2AWG 100A 2-P T/S N1A
48 0912970086 1 WIRE ASSY 2AWG 100A 2-P T/S N2A
49 095282 1 DECAL LIVE-CIRCUIT
50 0F2710 1 DECAL XFER SWITCH DATA SE 100A
51 066849 4 SCREW HHTT M5-0.8 X 16
52 0E6303 1 WIRE – A
53 0E6303A 1 WIRE – B
54 0E6303C 1 WIRE – E1

*** SUPPLIED WITH WIRE HARNESS ITEM #39


** SUPPLIED WITH TRANSFER SWITCH (ITEM #1)

13
Section 6 — Exploded Views and Parts List
ATS “HS” Type Transfer Switch
200A Transfer Switch Assembly – Drawing No. 0E9801$-F

16 15 31
2 3
55 INSIDE RIGHT SIDE
17
52 53

19 26 NOTE:LOCATE HOLE IN BUSBAR


SWITCH
RATING

SWITCH IS FOR USE WITH CONTROL PANEL ASSEMBLY

UNDER BALL END OF SCREW


ALL TERMINALS LUGS ARE SUITABLE FOR COPPER
#0C1026 OR #0D8440 0R #0E0117 OR #0E5241A

OR ALUUMINUM WIRE OF AT LEAST 75° c RATING

TIGHTENING TORQUE 250 IN-LBS


GENERAC POWER SYSTEMS, INC.

0C4449A-T

33
MAXIMUM AMPS - 200

MAXIMUM VOLTS - 240


TRANSFER SYSTEM DATA

120/240

0A6599tv
0A6599tv

22097-S
1/4 STL
WAUKESHA, WI.

22473-S
1-4X20STL 22473-S
1-4X20STL
0C4449A-RS

0A9457
SYSTEM VOLTAGE
SERIAL NUMBER
MODEL NUMBER

22 INSIDE LEFT SIDE


0F2712

10

11 12 31 31

46
4
7 8 37 38 43
30A, 600V
D2806-E

27
SEE SIDE VIEW FOR HARDWARE DETAIL

30A, 600V
D2806-T
18 TORQUE ITEM #8 TO 12 FT-LBS

63378-T
Replace with UL

63378-T
listed fuse of same 63378-T

type and rating


600 Volt, 5 amp.
0D3587 A 56
UTILITY
(C1 & VR1)

5 6 38 44
22097-S
1/4 STL

22473-S
1-4X20STL

TORQUE ITEM #6
47 TO 72 IN-LBS.
63378-T
5 6 38 45

1
30
D2806-T
30A, 600V
STANDBY E1
(C2 & VR2)
21
B
D2806-S
30A, 600V

63378-T

63378-T

63378-T

63378-T
50
11 12 31
48850-E

47822-T

LISTED
R

C US
AUTOMATIC TRANSFER SWITCH

NOTE WIRE ORIENTATION


FOR USE IN OPTIONAL
STAND-BY SYSTEMS

194

WARNING
N1

N2

64NL
NEUTRAL
T1

T2

23
(OPTIONAL)

(12 VDC)

(12 VDC)
(240 VAC)

(240 VAC)

(240 VAC)

(240 VAC)

P/N 0A2595
WIRE

WIRE

WIRE

WIRE

WIRE

WIRE

32 0A6599tv
CUSTOMER CONNECTIONS
0A6599tv0A6599tv

22097-S
1/4 STL

22473-S
1-4X20STL 22473-S
1-4X20STL

32 37 37 38
36
QTY. 2 ITEM #37's BELOW SUBPLATE
QTY. 1 ITEM #37 ABOVE SUBPLATE
4 PLACES

9 34 35
43 13 28 14 48
DETAIL "A"

38 37

8 7 DECAL DETAILS
VIEWS SHOWN WITH ITEMS #18 & #19 FULLY ASSEMBLED
(NOT TO SCALE)
22097-S
1/4 STL
24
S-37422
LTS02X4-1

BUSBAR
19
SWITCH

BUSBAR HARDWARE
DETAIL AUTOMATIC
20
0E3485
TRANSFER SWITCH
51
34
0E9999 NEMA 3R - INDOOR/OUTDOOR USE

9
40 41 42

35 29
ENCLOSURE INSIDE
OF
COVER
DETAIL A
0E3484

(GROUND LUG ASSEMBLY) 23

0C8308

54 49 18

14
Section 6 — Exploded Views and Parts List
ATS “HS” Type Transfer Switch
200A Transfer Switch Assembly – Drawing No. 0E9801$-F

ITEM PART NO. QTY. DESCRIPTION

1 0D9618 1 TRANSFER SW-HSB 200A 2P 250V


2 0E3628 1 CIRCUIT BREAKER 0200A 2P 120/240V S QN
3 0E3664 1 BASE QN CIRCUIT BREAKER
4 0E3553 2 BUSBAR 200A HSB XFER SW
5 0E3375 4 LUG SLDLSS 250-#6 AL/CU
6 0F1252 4 SCREW BHSC 1/4-20 X 3/8
7 036656 2 SCREW SHC 1/4-20 X 1 G8.8 NZ
8 022127 2 NUT HEX 1/4-20 STEEL
9 0E6523 1 GROUND BAR (5)4-14 AWG CONN
10 063617 1 RELAY PNL 12VDC DPDT 10A@240VA
11 0D2806 2 FUSEBLOCK 30A 600V 2POS W/SQ
12 073590A 4 FUSE 5A X BUSS
13 047822 1 BLOCK TERM 20A 7 X 6 X 1100V
14 0A1661 2 RIVET POP .156 X .675 AL
15 0C4449A 1 ASS’Y-NTRL BL150-200A
16 090388 2 SCREW HHTT M6-1.0 X 12 ZINC
17 0E1473 1 WELDMENT TRANSFER SWITCH BOX
18 0E9989 1 COVER INSIDE XFER SWITCH BOX
19 0E1477 1 COVER TRANSFER SWITCH BOX
20 0F0668 1 DECALTRANSFER SWITCH
21 0E3070 1 SUBPLT XFER SW HSB
22 0E3477 REF DECAL SWITCH RATING
23 0E3484 1 DECAL WARN MANUAL OPER HANDLE
24 0E3485 1 DECAL SERVICE DISCONNECT
25 067210A 1 DECAL GROUND LUG (NOT SHOWN)
26 0A9457 1 DECAL NEUTRAL
27 0D3587 1 DECAL FUSE REPLACEMENT
28 0A2595 1 DECAL TERMINAL STRIP
29 0E7109 1 DECAL TEST SEQ.2P TS HS 3R
30 063378 8 HOLDER CABLE TIE
31 045764 8 SCREW HHTT M4-0.7 X 8 BP
32 049813 5 NUT HEX M6 X 1.0 G8 YEL CHR
33 074908 2 SCREW HHTT M5-0.8 X 10 BP
34 0C3992 2 SCREW HHTT M4-0.7 X 16 BP
35 026579 2 WASHER SHAKEPROOF EXT #8 STEEL
36 0E7213 2 SCREW THUMB 1/4-20 X 1/2 W/SHLD
37 022473 14 WASHER FLAT 1/4-M6 ZINC
38 022097 10 WASHER LOCK M6-1/4
39 0E9987 1 WIRE HARNESS HSB (NOT SHOWN)
40 0E6193 1 BRACKET ARM EXTENDER
41 064526 2 SCREW HWHS #6-25 X 3/8
42 * 0E6155 1 ARM EXTENDER PIN
43 * 0E6032 2 90 DEGREE UP SPADE CONNECTOR
44 * 0E6033 2 90 DEGREE DN SPADE CONNECTOR
45 * 0E6034 2 STRAIGHT SPADE CONNECTOR
46 0E6303 1 WIRE A
47 0E6303A 1 WIRE B
48 0E6303B 1 WIRE E1
49 0C8308 1 DECAL TERMINAL SHOCK HAZARD
50 081221 1 DECAL-UL LIST HSB
51 0E9999 1 DECAL-SERVICE DISCONNECT SWITCH
52 0E9988 1 BRACKET SERVICE SWITCH
53 0D3728 1 TOBBLE SWITCH, SERVICE
54 095282 1 DECAL LIVE-CIRCUIT
55 0F2712 1 DECAL XFER SWITCH DATA SE 200A
56 066849 5 SCREW HHTT M5-0.8 X 16

* SUPPLIED WITH TRANSFER SWITCH ITEM #1

15
Section 7 — Notes
ATS “HS” Type Transfer Switch

16 Generac® Power Systems, Inc.


Section 7 — Notes
ATS “HS” Type Transfer Switch

Generac® Power Systems, Inc. 17


Section 8 — Warranty
ATS “HS” Type Transfer Switch

GENERAC POWER SYSTEMS, INC. WARRANTY/SERVICE


Generac Power Systems, Inc. will warrant that from the date of purchase, our transfer
switch will be free from defects in material and workmanship for the items and periods set
forth in the warranty statement found in the owners manual of the Generac Power Systems
Inc. generator that this transfer switch will be utilized with.

Any equipment that the purchaser/owner claims to be defective must be examined by the
nearest Generac Authorized Warranty Service Dealer by visiting our website at www.gener-
ac.com or by calling the dealer locator number at 1-800-333-1322. Select the prompt that
describes the brand name of the generator.

THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR


IMPLIED, SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
Some states do not allow limitations on how long an implied warranty lasts, so the above
limitation may not apply to you.

GENERAC’S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S)


AS STATED ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS, INC. BE
LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH
DAMAGES ARE A DIRECT RESULT OF GENERAC’S NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential dam-
ages, so the above limitations may not apply to you.

This warranty gives you specific legal rights. You also may have other rights that vary from
state to state.

GENERAC® POWER SYSTEMS, INC.


P.O. BOX 297 • WHITEWATER, WI 53190

Part No. 0E9905 Revision F (07/21/05) Printed in U.S.A.

You might also like