Professional Documents
Culture Documents
Narada BMS Modbus V1.6
Narada BMS Modbus V1.6
-:
,/
/
/
Narada BMS Modbus
1. Communication configuration
1.1 Configuration:
(9600 bit/s, NO parity bit, 8 data bit,1 stop bit)
BMS board dip code range is O,.___, 15. BMS software's base address is 38, so the BMS communication address is
(38+x), x is BMS board dip code. Example: BMS board dip code is 1, the BMS communication address is 39.
1.3Command Format
Notel: MSB is High byte; LSB is Low byte
Note2: One register is include two bytes, if a register only have one byte, put it in LSB.
Note2: One register is include two bytes, if a register only have one byte, put it in LSB.
Register Data Unit Bytes Scale Offset PDU#Value Mio data Maxdata
capacity
Table
Flag Table
Table
nunber
Discharge
Capacity
o
Oxl018 CellV oltage 1 V 2 0.001 o 3000#3.000 o 5
Charge time
Discharge
time 1
Table
Warning Flag
Bit5 Reserved
Bit6 Reserved
Bit7 Reserved
Protection Flag
Bit5 Reserved
Bit6 Reserved
Bit7 Reserved
(Fault) O:None
O:None
O:None
Bit3 Reserved
Bit4 Reserved
Bit5 Reserved
Bit6 Reserved
Bit7 Reserved
O:None
O:None
Cell UV State
Hex,
Software OxOAOA,
2(Fixed) Version( 1 byte)+
Version Ver: Vl0.10
revision( 1 yte)
Hardware Ox010a0b0200
5(Fixed) Hex
Version Ver: VOl.10.11.02.00
Serial
Version
pate ofthe
8 20181220 ASCII
manufacture
1 2 2 3 note
Format SUBID Data Len Datal Data2
New Password
1 (Set Password) 12(2BYTE) U ser Password C 6BYTE)
(6BYTE)
3 C valid
0(2BYTE) / /
communication)
low voltage min; if set
communication timeout
4( set time) 4(2BYTE) timeout time (2 OxFFFF,the funtion
time(2 BYTE)
BYTE) is disabled
2. CRC Check
CRC Check's range is include all bytes before the CRC field, using ofthe 16 bit CRC. The realization ofthe
Reference: ((MODBUS over Serial Line Specification and Implementation Guide Vl.02))