Professional Documents
Culture Documents
General Specifications: Models ANT401, ANT502 Optical ESB Bus Repeater Modules For 5 KM (For N-IO/FIO)
General Specifications: Models ANT401, ANT502 Optical ESB Bus Repeater Modules For 5 KM (For N-IO/FIO)
General Specifications: Models ANT401, ANT502 Optical ESB Bus Repeater Modules For 5 KM (For N-IO/FIO)
[Release 6]
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60F51-01EN July 5, 2018-00
<<Contents>> <<Index>> 3
n EXTERNAL DIMENSION
l Optical ESB Bus Repeater Master Module for 5 km (ANT401)
Unit: mm
CN1 CN1
130
CN2
OPT OPT
OUT OUT
IN IN
ANT401-5E/CU1N ANT401-5E/CU1T
(Connector unit (Connector unit with
for ESB Bus) terminator for ESB Bus)
F01E.ai
Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal
tolerance is ± 1.5 mm.
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60F51-01EN July 5, 2018-00
<<Contents>> <<Index>> 4
l Optical ESB Bus Repeater Slave Module for 5 km (ANT502)
32.8 32.8
Unit: mm
CN1
CN3 CN3
OPT OPT
OUT OUT
IN IN
ANT502-5E/HU1A ANT502-5E/HU1B
(Connector unit with ESB (Connector unit 155.9
Bus connector and HKU I/F) with HKU I/F)
13.4 142.5
32.8 32.8 129
CN1
130
OPT OPT
OUT OUT
IN IN
Nominal Tolerances :
Nominal tolerance is ± 0.8 mm for the dimensions of 0.5 mm or more and 120 mm or less, and the combined nominal
tolerance is ± 1.5 mm.
The nominal tolerance is in accordance with JEM 1459 for the dimensions over 120 mm.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60F51-01EN July 5, 2018-00
<<Contents>> <<Index>> 5
n EXAMPLE OF CONNECTION STRUCTURE
l Example of Chain and Star Connection (In the case of A2FV50/A2FV70 for FCU)
A2FV50D/A2FV70D
ANT401
ANT411
ANT401
ANT401
ANT401
ANT411
EC401
EC401
ANT401(IO1, 2)
:option code “/CU1T”
ANT401(IO3, 4)
:option code “/CU1N”
ANT411(IO5, 6)
:option code “/CU1N”
CN2 (PSU-R)
A2EN501
A2PW50
A2PW50
A2EN501
A2EN501
A2PW50
A2PW50
A2EN501:
optical ESB bus (0~5 km) for uplink
Total max. for uplink optical ESB bus (0~5 km)
length of optical cable; optical ESB bus (5~50 km) for downlink
50 km or less for downlink (A2EN501-S120)
(A2EN501-S120)
N-IO N-IO
Max. length of
optical cable
5 km or less
Max. length of
optical cable
50 km or less
ANB11D
ANB11D
ALR121
ALF111
ALF111
ALR121
ANT512
ANT512
ALR121
ALF111
ALF111
ALR121
ANT502
ANT502
ANB11D
ALR121
ALF111
ALF111
ALR121
ANT411
ANT411
ANT502
ANT502
Total max.
length of optical cable;
50 km or less
ANB11D
ALR121
ALF111
ALF111
ALR121
ANT512
ANT512
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60F51-01EN June 1, 2016-00
<<Contents>> <<Index>> 6
l Example of Chain Connection (In the case of AFV30/AFV40 for FCU)
AFV30/AFV40
A A E E C C
I I I I N N C C P
4 4
P
O O O O T T 4 4 6 6
M M M M 4 4 0 0 1 1 P P
0 0 1 1 or or S S
1 1 C C U U
P P
4 4
7 7
1 1
UTILITY UNIT (*1)(*1)
A A A A
I I I I I I N N N N
Total Max. length of O O O O O O T T T T
Fiber-optic cable 50 km M M M M M M 4 4 5 5 P P
1 1 0 0 S S
1 1 2 2 U U
Max. length of
Fiber-optic cable 50 km
ANT411: option code “/CU1T”
HKU ANT502: option code “/HU1A”
ANB11
A A
I I I I I I I I N N
O O O O O O O O T T
M M M M M M M M 5 5 P P
1 1 S S
2 2 U U
: Fiber-optic cable
F04E.ai
*1: A dual-redundant configuration is enabled by using 2 identical modules with same model code (CP461 or CP471).
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60F51-01EN Oct. 24, 2017-00
<<Contents>> <<Index>> 7
l Example of Star Connection (In the case of AFV30/AFV40 for FCU)
AFV30/AFV40
C C
E E P P
I I I I I I C C 4 4
O O O O O O 4 6 6
4 1 1 P P
M M M M M M 0 0 or or
C C S S
1 1 P P U U
4 4 ESB bus cable
7 7
1 1 Max. length: 10 m (*2)
UTILITY UNIT (*1)(*1)
ANT10U
A A A A A A
N N N N N N
T T T T T T
4 4 4 4 4 4 P P ANT401(B1, 2) : option code “/CU1T”
0 0 1 1 0 0 S S ANT411(IO7, 8) : option code “/CU1N”
1 1 1 1 1 1 U U ANT401(IO5, 6) : option code “/CU1N”
Max. length of
Fiber-optic cable 5 km
HKU
Max. length of
Fiber-optic cable 50 km
ANB11 ANB11
A A A A
I I I I I I I I N N I I I I I I I I N N
O O O O O O O O T T O O O O O O O O T T
M M M M M M M M 5 5 P P M M M M M M M M 5 5 P P
0 0 S S 1 1 S S
2 2 U U 2 2 U U
HKU
ESB bus cable
Max. length: 10 m ANT512: option code “/HU1B”
ANB10
S S
I I I I I I I I B B
O O O O O O O O 4 4
M M M M M M M M 0 0 P P
1 1 S S
U U
HKU
: Fiber-optic cable
ANT502: option code “/HU1A”
SB401: option code “/CU2T”
F05E.ai
*1: A dual-redundant configuration is enabled by using 2 identical modules with same model code (CP461 or CP471).
*2: The above diagram shows an example of ESB Bus wiring and its termination.
The wiring can be done from left to right or vice versa in between EC401 and ANT401 and among ANT401 modules.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60F51-01EN Oct. 24, 2017-00
<<Contents>> <<Index>> 8
n MODEL AND SUFFIX CODES
Optical ESB Bus Repeater Master Module
Description
Model ANT401 Optical ESB Bus Repeater Master Module 5 km (for N-IO/FIO)
-5 Standard type with no explosion protection
-E Standard type with explosion protection
0 Basic type (only for maintenance purpose)
Suffix
Codes 3 With ISA Standard G3 option and temperature (-20 °C to 70 °C) option (only for maintenance purpose)
E Basic type (for ANT502-E, -F, and A2EN501-1)
With ISA Standard G3 option and temperature (-20 to 70 ˚C) option (for ANT502-E, -F, and
F
A2EN501-1)
Description
Model ANT502 Optical ESB Bus Repeater Slave Module 5 km (for N-IO/FIO)
-5 Standard type with no explosion protection
-E Standard type with explosion protection
0 Basic type (only for maintenance purpose)
Suffix
Codes 3 With ISA Standard G3 option and temperature (-20 °C to 70 °C) option (only for maintenance purpose)
E Basic type (for ANT401-E, -F, and A2EN501-1)
With ISA Standard G3 option and temperature (-20 to 70 ˚C) option (for ANT401-E, -F and
F
A2EN501-1)
/BU1A Connector unit with ESB Bus connector
Note: When Optical ESB bus repeater modules are connected via Optical ESB bus, the master side must be paired with one of
the slave sides as described below.
• ANT401-0 or -3 for master side and ANT502-0, -3, ANB11S-1, -2, or ANB11D-2 for slave side
• ANT401-E or -F for master side and ANT502-E, -F, A2EN501-1, ANB11S-A, -B, or ANB11D-B for
slave side
• A2EN501-1 for master side and ANT502-E or -F for slave side
When using by dual-redundant configuration, the module for ESB bus1 should be the same as the module for ESB bus2.
n APPLICABLE STANDARDS
Refer to the GS “Integrated Production Control System CENTUM VP System Overview” (GS 33J01A10-01EN).
n ORDERING INFORMATION
Specify the model and suffix codes when ordering.
For selecting the right products for explosion protection, please refer to TI 33Q01J30-01E without fail.
n TRADEMARKS
• CENTUM and Vnet/IP are either registered trademarks or trademarks of Yokogawa Electric Corporation.
• All other company or product names appearing in this document are trademarks or registered trademarks of their
respective holders.
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 33J60F51-01EN July 5, 2018-00
Subject to change without notice.