Thyfrec-Vt210S Quick Start Guide: Ac Speed Control Equipment
Thyfrec-Vt210S Quick Start Guide: Ac Speed Control Equipment
Thyfrec-Vt210S Quick Start Guide: Ac Speed Control Equipment
1. Read this manual thoroughly before using the VT210S, and store in
a safe place for reference.
2. Make sure that this manual is delivered to the final user.
MEIDENSHA CORPORATION
Warning
E&OE
Installation
Install the Inverter vertically, so that the cable glands face downwards.
Allow for the correct spacing around the Inverter for ventilation
(X +>50mm, Y +>200mm). Fig. 1.
Please note that TBA must be set in position shown (Fig. 2.)
for 380-400V operation, and in position 1-2 for 415-460V
operation.
Voltage Surge
For long motor cable lengths (>30m), a motor choke can be ordered which
must be fitted between the Inverter and the motor. Motor cables must be
screened at both ends.
Default settings allow the basic running of the motor to prove the system, but first set:
B00-1 set 31 assuming 415V, 50Hz B00-5 set motor rated current (A)
supply, and max freq B00-4 Output Voltage may have
requirement of 50Hz. to be set for non-standard
motors.
On power up, the Inverter display will cycle through a self-diagnostics check, and then show confirming the
drive is in a ready state.
Press FWD on the keypad and the motor will ramp up to 10Hz in a forward direction. The display will change
from to ( local frequency setting A00-0).
Press REV and check that the motor changes direction. Now press STOP, the motor will stop.
Configuration
The Inverter parameter menu system is grouped into Modes and Blocks
according to their functions and frequency of usage.
To manoeuvre around the menu system, pressing the MOD key will change
between the Monitor, A and B block parameters. Pressing the key will
change through the parameters in that block. See Fig. 4.
The display will alternate between the parameter number and its current value.
Press SET to change the parameter value. Increase/decrease the value by
using the and keys, and move to next digit by pressing the key.
When you have set the parameter to the value you want, press SET.
It is possible to reset to default values when the drive is not running, by setting
parameter B06-3 to 9 (page 6-12).
The parameter default values are such that the inverter can be quickly, and
safely, checked after power on. However, some of the default values may
need to be changed to suit specific applications.
Set parameter A05-0 from 2221 to 1111 to release further parameters blocks.
With the drive display showing press STOP + LCL together to toggle between local and remote modes.
From default settings, the inverter is set up to accept the following signal inputs: (page 6-11).
** by default is a normally open contact, coast to stop. Refer to manual (page 6-10) for options.
If necessary, set new Accel/Decel times in A01-0 and A01-1 (page 6-3).
Jog Accel/Decel can be set in B21-2 and B21-3 (page 6-21).
From default the signal reference is obtained from the 0-10V analogue input. This can be from a number of sources
including a potentiometer as shown in Fig. 3.
Torque Boost
A02-0 Increase this value for loads with high Starting Inertia.
(Refer to pages 6-3/6-6).
A worked example of using 10Hz, 13.20Hz, 25Hz, 40.32Hz and 50Hz pre-set speeds is shown below:
Using inputs PSI3-PSI5 as binary inputs (see Fig. 5) it is possible to set any of the speeds. Please note that it is also
possible to set independent accel/decel ramps to each pre-set speed. (Refer to B40-0, B41-x and B42-x on pages
6-37/6-40).
Fig.5.