I.L. 46-717-ll

DESCRIPTION • OPERATION • MAINTENANCE

INSTRUCTIONS

.c
BI-METAL TYPE
HOTTEST SPOT THERMAL INDICATOR
For Sealed Dry-Type Transformers

ls
ua
THE HOTTEST SPOT THERMAL INDI­ transformer, carries a current proportional to load,
CATOR is an auxiliary piece of apparatus used to and has a thermal time constant approximately
indicate the hottest spot in the transformer winding. equal to that of the transformer. The thermometer
This temperature is approximately duplicated on bimetal located inside the heating coil will there­
the bimetal of the dial type thermometer and is

an
fore attain a temperature approximately that of the
read directly on the indicator dial. transformer winding.

The proper current transformer tap is selected


DESCRIPTION from the recording of the hotspot by thermocouple
at the time of the transformer load heat run.

tM
The weatherproof dial type indicator is mounted
on the tank wall of the transformer. The dial is
calibrated from 0 to 250 degrees centigrade and INSTALLATION AND MAINTENANCE
has a resetable maximum temperature hand. The thermal indicator and current transformer
Three signal or alarm contacts are available that is completely mounted and adjusted at the factory
ar
are rated at a maximum current given in Table No. before shipment and should not require any service
1. The contacts close at 200°, 210° and 220° centi­ at the time of installation. If it becomes necessary
grade. The contacts open at 5° less than the closing to repair the instrument contact the nearest West­
lP

temperature. The alarm leads are brought out of inghouse Sales Office.
the instrument through a triple seal connector with
a locating pin to prevent incorrect connections. Table No. 1
The current transformer is mounted outside the
ca

case of the main transformer and is energized from CONTACT LOAD LIMIT

one of the windings depending on which is more


AC (OPEN-CLOSE) OC (CLOSE ONLY)
suitable. The secondary is connected to the ter­ INDUCTIVE- NON-INDUCTIVE
minals of the heating coil which is mounted inside NON-INDUCTIVE ONLY
tri

of the sealed tank. The heating coil therefore carries

I I
Volts Amperes Volts Amperes
a current proportional to the load of the main trans­ ------ -----------

former.
125
I 10 125 I
lec

Y2
250 5 250 !14
OPERATION 460 3 ... I
I
I I
!
The heating coil, located in the hot gas of the

RED
}
.E

LOCATING KEY CLOSES 200° C SIGNAL


SWITCH I {
L...-___J OPENS 195° C CIRCUIT

{ }
BLACK

CLOSES 210°C ALA RM


TO � WHITE S WITCH 2
C.T. ---u.u..J L..._____J OPENS 205°C CIRCUIT
HEAT ING
w

COIL
GREEN

VIEW LOOKING AT
ww

BOTTOM OF CAS E

FIG. l. Wiring Diagram

NEW INFORMATION AUGUST, 1957