Professional Documents
Culture Documents
500 MW Turbogenerator C&I Gyanendra Sharma NPTI Delhi
500 MW Turbogenerator C&I Gyanendra Sharma NPTI Delhi
CONTROL
&
INSTRUMENTATION
Gyanendra Sharma
CAPACITY AND RANGES
TERMINAL VOLTAGE 21 KV
• GENERATOR INSTRUMENTATION
• EXCITER INSTRUMENTATION
• GENERATOR SEAL OIL SYSTEM
• GENERATOR PW COOLING SYSTEM
• GENERATOR GAS SYSTEM
• GENERATOR WASTE GAS SYSTEM
• GENERATOR WASTE FLUID SYSTEM
• MEASUREMENT / MONITORING
• CONTROLS
• ALARMING
• PROTECTION
• DIAGNOSTICS
• LOCAL ALARMS
• UCB WINDOW ALARMS
• CRT ALARMS
• ELECREICAL PROTECTIONS
• GENERATOR MECHANICAL PROTECTIONS
MAX1000+PLUS
(ALSO CALLED MAXDNA)
MEASURING RANGES :
A. ANALYSER :
MICROPROCESSOR BASED
MEASURING RANGES :
1. 0-100 VOL % CO2 IN AIR
2. 100-0 VOL% H2 IN CO2
3. 100-90 VOL% H2 IN AIR
POWER SUPPLY : 220 V AC , + 15%,-20%, 50 HZ
PROTECTION : FLAME PROOF
REPEATABILITY : < 1% OF SPAN
LINEAR DEVIATION < 2% OF SPAN
AMBIENT : +5C TO 50C
ZERO DRIFT < 2% PER WEEK
TEMP EFFECT < 0.5% OF SPAN / 10C
OUTPUT 4 TO 20 MILI AMP
B. ANALYSIS PANEL :
1200 MM(W) X 800 M(D) X 2100MM(H)
• PW COOLING
• SEAL OIL SYSTEM
• GAS DRYING
• BEARING EXHAUST BLOWERS
• EXCITER ANTICONDENSATION HEATERS
• GENERATOR MECHANICAL PROTECTIONS
03/27/2021 500 MW Turbogenerator C&I 36
03/27/2021 500 MW Turbogenerator C&I 37
03/27/2021 500 MW Turbogenerator C&I 38
03/27/2021 500 MW Turbogenerator C&I 39
03/27/2021 500 MW Turbogenerator C&I 40
03/27/2021 500 MW Turbogenerator C&I 41
03/27/2021 500 MW Turbogenerator C&I 42
03/27/2021 500 MW Turbogenerator C&I 43
03/27/2021 500 MW Turbogenerator C&I 44
03/27/2021 500 MW Turbogenerator C&I 45
03/27/2021 500 MW Turbogenerator C&I 46
03/27/2021 500 MW Turbogenerator C&I 47
Plant information network
ENGINEER’S
STATION
MAXSTATIONS
MAXLINK
FIBRE OPTIC
LINK
REMOTE PROESSING UNITS
PLANT SUB-SYSTEMS
REMOTE I/O
• I/O MODULES
•DATA PROCESS. UNIT ( DPU4E)
•NETWORK SWITCHES
•FIBRE OPTIC 100MBPS CABLES
•10MBPS COAXIAL CABLES
•POWER SUPPLIES
•MAXSTATIONS
I/O MODULES (MAXPAC SERIES)
• 16 DISCRETE INPUTS FOR BIN. SIGNALS ( COMMON/ISOLATED)
• 16 DISCRETE ANALOG INPUTS (4-20MA,0-2.5VDC)
(ISOLATED/COMMON)
• 16 THERMOCOUPLE/MV ANALOG INPUTS
• 8 RTD INPUTS ( 3 WIRE TYPES ONLY)
• 4 CHANNEL POSITION OUTPUT TYPE (QPAT)
• 16 DISCRETE BINARY OUTPUTS
• 8 CHANNEL ANALOG OUTPUTS ( 4-20MA)
• 16 CHANNEL FORM-A (NO) RELAY OUTPUTS
• 10 CHANNEL FORM-C (COC) RELAY OUTPUTS
• HEAVY DUTY RELAY OUTPUT 10A INDUCTIVE LOAD RATING
• OPTICAL BUS EXTN. MODULES (SUPPORTS 60 I/OS UPTO 100M)
•KIT WITH 16 100 OHMS RESISTORS
REDUNDANCIES
•DPUs MAY BE MADE REDUNDANT
•I/O MODULES -REDUNDANT,SHARED OR
COMBINATION OF THE TWO
•REMOTE PSUs ARE USUALLY MADE REDUNDANT
•MAXNET (NTWORK A/B) IS ALWAYS REDUNDANT
•MAXLINKS MAY BE MADE REDUNDANT
MAXSTATION SOFTWARES
•MAXTOOLS4E CONFIGURATOR
•MAXVUE EDITOR
•MAXVUE RUNTIME
•SOFTWARE BACKPLANE
•WINDOW NT
•WONDOW CE
•DONGLE HARDWARE SWITCH
MAXSTORIAN
• Historical Data Collection and
Archiving Software for
MAXSTATION
• “Delta-Save” data storage
maximizes system data capacity
• Relational database to simplify
reports and queries for data analysis
• Archival storage to CD-ROM
• Supports interface to plant-
management networks
• Windows-NT based
Switch 1 Switch 2
Switched
Hub
RPUs RPU
MAXSERVER
• Global access of data for data acquisition and control
• Separates discrete sections of DCS - e.g. plant units
• Provides security and assures performance
• Simplifies maintenance
• Allows integration of other systems
03/27/2021 500 MW Turbogenerator C&I 63
Distributed Processing Unit
• 32 Bit Intel Processor
• Windows CE Operating System.
Supports off-line simulation and testing
• Open architecture
• Uses MAXNET Ethernet Data Highway
• Object-Oriented Configuration
• Rack Mounted
• 8 MB flash RAM, 32 MB SDRAM
• Modulating Control, Logic, Data
Acquisition
• Event Reporting to 1 msec Resolution
I/O I/O
I/O I/O