Professional Documents
Culture Documents
An Introduction To Load Flow Analysis
An Introduction To Load Flow Analysis
An Introduction To Load Flow Analysis
School of Engineering
Electrical Power Systems
Introduction
In this exercise you will continue to use the ‘ERACS’ power system analysis software package.
This exercise will concentrate on using the loadflow function.
Getting started
Create the system shown in figure 1. Select appropriate Network, Data State and Working
Library names. The relevant system data are shown in the appendix.
1. Having created the system, run the load flow and determine the real and reactive power
dissipated/absorbed by each transmission line.
Set the susceptance values to zero and determine the impact on the reactive and active
power flows
2. Rerun the loadflow for the following loading conditions on the Tredegar busbar and
determine how it affects the busbar voltage magnitude and angle.
Owing to the addition of industrial customers and certain network changes, the system loading
is adjusted as shown below:
Restore the original line loadings; switch out the line from Old Harbour to Washington at the
Washington busbar, see below. (the line remains energised at Old Harbour)
Rerun the loadflow and determine the changes in the line complex power flows/ bus voltages.
At the closed end of the switched line at Old Harbour the complex power is non-zero, why?
Restore the line at Washington. Change the slack generator voltage to 1.03 and rerun the load
flow. How does this change impact bus voltages and power flows within the network?
Set the negative and zero sequence reactances of the lines to zero and rerun the load flow. How
do these changes affect the results?
Contingency Study
Perform a contingency study on the effect of transmission line outages on the power flows. Reset
the slack voltage to 1.06 pu then switch out each transmission line, one at a time. Tabulate
results to show which outages are critical i.e. cause constraint violations – lines overloaded, bus
voltages outside range (± 5%).
Appendix - System Data
Busbar data
Line data
From Busbar 1 1 2 2 2 3 4
To Busbar 2 3 3 4 5 4 5
# of parallel lines 1 1 1 1 1 1 1
Highest, Nominal and 150 100 100 100 100 100 100
Lowest unit rating, MVA
Conversion indicator pu on pu on pu on pu on pu on pu on pu on
base base base base base base base
+ve/-ve sequence 0.02 0.08 0.06 0.06 0.04 0.01 0.08
resistance/unit length
+ve/-ve sequence 0.06 0.24 0.18 0.18 0.12 0.03 0.24
reactance/unit length
+ve/-ve sequence shunt 0.06 0.05 0.04 0.04 0.03 0.02 0.05
susceptance/unit length
Zero sequence resistance/unit 0.02 0.08 0.06 0.06 0.04 0.01 0.08
length
Zero sequence reactance/unit 0.06 0.24 0.18 0.18 0.12 0.03 0.24
length
Zero sequence shunt 0.06 0.05 0.04 0.04 0.03 0.02 0.05
susceptance/unit length
Generator data
G1 G2
Connected to Busbar 1 2
Generator Type Slack PQ
Number of Generators in Parallel 1 1
Voltage magnitude, pu 1.06 0
Group Assigned Power Output, MW 0 40
Group Assigned Reactive Output, MVAr 0 30
Unit rating, MVA 180 100
Unit Power rating, MW 150 60
Rated voltage, kV 69 69
Frequency 50 50
+ve sequence resistance pu on rating 0.005 0.005
+ve sequence reactance pu on rating 0.15 0.15
-ve sequence resistance pu on rating 0.005 0.005
-ve sequence reactance pu on rating 0.15 0.15
zero sequence resistance pu on rating 0.005 0.005
zero sequence reactance pu on rating 0.15 0.15