OptiX OSN 1800

Hardware Description 1 Indoor Cabinet

1 Indoor Cabinet

This section describes the indoor cabinet and the related cables.

1.1 Introduction to Cabinets


This section describes the types of cabinets supported by the OSN 1800.
1.2 Guidelines for Placing Cabinets
To ensure proper heat dissipation and maintenance of cabinets, adhere to the
guidelines provided in this section when placing cabinets.
1.3 Cabinet Cables

1.1 Introduction to Cabinets


This section describes the types of cabinets supported by the OSN 1800.

Issue 02 (2020-07-30) Copyright © Huawei Technologies Co., Ltd. 1


OptiX OSN 1800
Hardware Description 1 Indoor Cabinet

Table 1-1 Types, appearances, and specifications of the cabinets supported by


OSN 1800
Item N63B Cabinet 19-Inch Cabinet A63B Cabinet (ETSI
300 mm Cabinet
with Middle
Columns)

Appear
ance

NOTE
N63B cabinets use
middle columns.

Weight N63B cabinet: 60 kg 72 kg (158.7 lb.) 61 kg (134.5 lb.)


NOTE (132.3 lb.)
The
data
refers
to the
weigh
t of
the
cabine
t only,
exclud
ing
device
s.

Issue 02 (2020-07-30) Copyright © Huawei Technologies Co., Ltd. 2


OptiX OSN 1800
Hardware Description 1 Indoor Cabinet

Item N63B Cabinet 19-Inch Cabinet A63B Cabinet (ETSI


300 mm Cabinet
with Middle
Columns)

Appear - -
ance of
convex
door

Depth - - 50 mm
of the
protrud
ing
part on
the
convex
door

Dimen 2200 mm x 600 mm x 2200 mm x 600 mm x Excluding the convex


sions 300 mm (86.6 in. x 600 mm (86.6 in. x door: 2200 mm x 600
(H x W 23.6 in. x 11.8 in.) 23.6 in. x 23.6 in.) mm x 300 mm (86.6
x D) in. x 23.6 in. x 11.8
in.)
Including theconvex
door: 2200 mm x 600
mm x 350 mm (86.6
in. x 23.6 in. x 13.8
in.)

Availab 46 U 45 U 47 U
le
space

Issue 02 (2020-07-30) Copyright © Huawei Technologies Co., Ltd. 3


OptiX OSN 1800
Hardware Description 1 Indoor Cabinet

Item N63B Cabinet 19-Inch Cabinet A63B Cabinet (ETSI


300 mm Cabinet
with Middle
Columns)

Fiber N63B: ● Fiber (2 mm): 430 A63B:


capacit ● Fiber (2 mm): 360 PCS ● Fiber (2 mm): 360
ya PCS ● Network cable (5.2 PCS
● Network cable (5.2 mm): 72 PCS ● Network cable (5.2
mm): 60 PCS ● Shielded network mm): 60 PCS
● Shielded network cable (6.8 mm): 60 ● Shielded network
cable (6.8 mm): 50 PCS cable (6.8 mm): 50
PCS ● 21E1 cable (13.4 PCS
● 21E1 cable (13.4 mm): 12 PCS ● 21E1 cable (13.4
mm): 10 PCS ● Trunk cable (5.8 mm): 10 PCS
● Trunk cable (5.8 mm): 54 PCS ● Trunk cable (5.8
mm): 45 PCS ● Trunk cable (3.9 mm): 45 PCS
● Trunk cable (3.9 mm): 120 PCS ● Trunk cable (3.9
mm): 100 PCS mm): 100 PCS
N63B+Fiber A63B+Fiber
management management
cabinetb: cabinetb:
● Fiber (2 mm): ● Fiber (2 mm):
1360 PCS 1360 PCS
● Network cable (5.2 ● Network cable (5.2
mm): 420 PCS mm): 420 PCS
● Shielded network ● Shielded network
cable (6.8 mm): cable (6.8 mm):
350 PCS 350 PCS
● 21E1 cable (13.4 ● 21E1 cable (13.4
mm): 72 PCS mm): 72 PCS
● Trunk cable (5.8 ● Trunk cable (5.8
mm): 315 PCS mm): 315 PCS
● Trunk cable (3.9 ● Trunk cable (3.9
mm): 700 PCS mm): 700 PCS
NOTE
a: Fiber capacity indicates the maximum number of fibers (of the same type) that can be
routed in a cabinet. If cables of multiple types need to be routed in the cabinet, you need
to perform conversion. When selecting a cabinet model, you need to consider the
maximum fiber routing capacity upon expansion.
b: The calculation assumes that one fiber management cabinet is configured at the right
side of the N63B cabinet.

Issue 02 (2020-07-30) Copyright © Huawei Technologies Co., Ltd. 4


OptiX OSN 1800
Hardware Description 1 Indoor Cabinet

1.2 Guidelines for Placing Cabinets


To ensure proper heat dissipation and maintenance of cabinets, adhere to the
guidelines provided in this section when placing cabinets.
Cabinets are usually installed in a row inside a room. Their positions are shown in
Figure 1-1 and Figure 1-2.
To meet the requirements of heat dissipation and maintenance, keep distances
around a cabinet as follows:
● Keep a minimum distance of 1000 mm (39.4 in.) before a cabinet.
● Keep a minimum distance of 800 mm (31.5 in.) beside both sides of a cabinet.
● Keep a minimum distance of 50 mm behind a cabinet (not required when
cabinets are installed in back-to-back mode).

Figure 1-1 Top view of cabinets installed in face-to-face mode

Issue 02 (2020-07-30) Copyright © Huawei Technologies Co., Ltd. 5


OptiX OSN 1800
Hardware Description 1 Indoor Cabinet

Figure 1-2 Top view of cabinets installed in back-to-back mode

NOTE

A fiber management cabinet is required only when there are many fibers to manage. When
no fiber management cabinet is configured, follow the preceding guidelines. For
information about a fiber management cabinet, see 3 Fiber Management Cabinet.

1.3 Cabinet Cables

1.3.1 Cabinet Ground Power Cables


One end of the cabinet ground power cables is connected to ground bar in the
equipment room. The other end is connected to the ground bolts at the top of the
cabinet.

Structure
Figure 1-3 shows the structure of the cabinet ground cable.

Issue 02 (2020-07-30) Copyright © Huawei Technologies Co., Ltd. 6


OptiX OSN 1800
Hardware Description 1 Indoor Cabinet

Figure 1-3 Structure of the cabinet ground cable

1. OT one-hole naked crimping 2. Cable 3. Heat-shrink 4. JG two-hole naked crimping


connector tubing connector

Technical Parameters

Table 1-2 Technical parameters of the cabinet ground cable


Parameter Description

Connector X1 Naked Crimping Terminal, JG2,


16mm2, M6, 95A, Tin Plated

Connector X2 Naked Crimping Terminal, OT, 16mm2,


M8, Tin Plating, Naked Ring Terminal

Cable model Wire, 450/750V, 60227 IEC 02


(RV)16mm2, yellow green, 85A, with a
package exempted from fumigating

1.3.2 Cabinet Door Ground Cables


A cabinet door ground cable uses one OT one-hole naked crimping connector at
each end. It connects the front door, rear door, or a side panel of the cabinet to
the ground.

Structure
Figure 1-4 shows the structure of the cabinet door ground cable.

Issue 02 (2020-07-30) Copyright © Huawei Technologies Co., Ltd. 7


OptiX OSN 1800
Hardware Description 1 Indoor Cabinet

Figure 1-4 Structure of the cabinet door ground cable

1. OT one-hole naked crimping connector

Technical Parameters

Table 1-3 Technical parameters of the cabinet door ground cable


Parameter Description

Connector X1/X2 Naked crimping terminal-OT-6 mm2


(0.01 in.2)-M6-Tin plating-Insulated
ring terminal-12-10AWG

Cable model Single Cable, PGND Feeder Cable,


0.35m, OT6-6, 10UL3386G, yellow
green, OT6-6, LSZH

Issue 02 (2020-07-30) Copyright © Huawei Technologies Co., Ltd. 8