Professional Documents
Culture Documents
VDR G4 (E) Voyage Data Recorder VDR G4 (E) Technical Manual For VDR G4 (E)
VDR G4 (E) Voyage Data Recorder VDR G4 (E) Technical Manual For VDR G4 (E)
VDR G4 (E) Voyage Data Recorder VDR G4 (E) Technical Manual For VDR G4 (E)
G4[e]
Voyage Data Recorder VDR G4[e]
Technical Manual
for VDR G4[e]
Copyright
This manual, the software of mentioned components and operating instructions, are
protected by copyright. No part of this publication may be reproduced, transmitted, tran-
scribed or translated to any language nor may be stored in any retrieval system by any
means, in any written, electronic, mechanical, magnetic, optical, or any other form, without
the expressed written consent of INTERSCHALT maritime systems GmbH.
• INTERSCHALT maritime systems GmbH reserves the right to change or to withdraw this
document without prior notice.
• INTERSCHALT maritime systems GmbH does not guarantee correctness and accuracy
of programs and data, stored on a CD-ROM.
• We appreciate helpful suggestions for improvements and error reports at any time.
• The agreements includes this document and associated appendices.
Revision
Revision: 1.0.5
Product-No.: 106370
Remark
Table of Contents
1 Introduction ............................................................................................................... 1
1.1 Information to this instruction ............................................................................. 1
1.2 Purpose of document ........................................................................................... 1
1.3 Action Instructions ................................................................................................ 1
1.4 Safety Instruction .................................................................................................. 2
1.4.1 Level of Danger ......................................................................................... 2
1.4.2 Danger Symbols ........................................................................................ 2
1.4.3 Designate use ............................................................................................ 2
1.4.4 Non designated use ................................................................................... 3
1.4.5 Target groups ............................................................................................ 3
1.4.6 Modifications, spare parts and accessories ............................................... 3
1.4.7 Operating instructions ................................................................................ 4
1.5 Limited Liability ..................................................................................................... 4
1.6 Structure of the Manual ........................................................................................ 5
1.7 Important terms and abbreviations ..................................................................... 5
2 Functionality ............................................................................................................. 9
2.1 Purpose and Function .......................................................................................... 9
2.2 Configuration of a VDR G4[e] .............................................................................. 10
2.3 Maritime Data Processor (MDP2020) ................................................................. 11
2.4 Interface Control Unit (ICU) ................................................................................ 11
2.5 Remote Control Test Panel (RCTP) ................................................................... 11
2.6 Audio2net module ............................................................................................... 12
2.7 Microphone VCA004 ........................................................................................... 12
2.8 NMEA2net module ............................................................................................... 12
2.9 Tron 40VDR capsule ........................................................................................... 13
2.10 FRM NEMO 2.0 module ....................................................................................... 13
2.11 Framegrabber FGR4 ............................................................................................ 14
2.12 Framegrabber FGR5 ............................................................................................ 14
2.13 Replay and Realtime Monitor software ............................................................. 15
2.14 PLC module ......................................................................................................... 15
3 Web-frontend .......................................................................................................... 17
3.1 Login and Logout ................................................................................................ 17
3.2 MDP2020 .............................................................................................................. 19
3.2.1 Overview of menu .................................................................................... 19
3.2.2 Menu item “System” “Info” .................................................................. 20
3.2.3 Menu item “System” “Init” .................................................................... 22
3.2.4 Menu item “System” “Storage” ............................................................ 24
3.2.5 Menu item “System” “Agents” ............................................................. 26
Revision: 1.0.5 i
Table of Contents VDR G4[e]
Technical Manual
4 Installing .................................................................................................................... 87
4.1 Wiring .................................................................................................................... 88
4.1.1 Maximum Cable Length ........................................................................... 91
ii Revision: 1.0.5
VDR G4[e] Table of Contents
Technical Manual
iv Revision: 1.0.5
VDR G4[e] Table of Contents
Technical Manual
Revision: 1.0.5 v
Table of Contents VDR G4[e]
Technical Manual
vi Revision: 1.0.5
VDR G4[e] List of Figures
Technical Manual
List of Figures
Figure 4-7: Alternative alarm connection between a bridge alarm panel and the ICU . 100
Figure 4-8: Remote Control Test Panel (RCTP) ........................................................... 101
Figure 4-9: Audio2net module ...................................................................................... 102
Figure 4-10: External connections and environment ...................................................... 103
Figure 4-11: Microphone VCA004 .................................................................................. 106
Figure 4-12: NMEA2net module ..................................................................................... 108
Figure 4-13: External connection .................................................................................... 108
Figure 4-14: Tron 40VDR capsule .................................................................................. 111
Figure 4-15: Principle wiring plan ................................................................................... 112
Figure 4-16: NEMO 2.0 module ...................................................................................... 113
Figure 4-17: External connection .................................................................................... 118
Figure 4-18: Recommended assembly of the connecting cable ..................................... 119
Figure 4-19: FGR4 module ............................................................................................. 120
Figure 4-20: External connections FGR4 ....................................................................... 120
Figure 4-21: FGR5 module ............................................................................................. 122
Figure 4-22: Mounting positions of the FGR5 ................................................................. 122
Figure 4-23: External connections FGR5 ....................................................................... 123
Figure 5-1: Login window VDR ..................................................................................... 126
Figure 5-2: Logout-Button ............................................................................................. 126
Figure 5-3: Start-Menu page of RCTP module [FULL] ................................................. 132
Figure 5-4: Info / About RCTP module [FULL] ............................................................. 133
Figure 5-5: IP address Menu [FULL] ............................................................................ 133
Figure 5-6: Display Dimming [FULL] ............................................................................ 134
Figure 5-7: Restart VDR about RCTP module [FULL] .................................................. 134
Figure 5-8: MDP 2020 hosts configuration for the Tron 40VDR capsule [TRIMMED] .. 141
Figure 5-9: MDP 2020 hosts configuration for the FRM NEMO 2.0 [TRIMMED] ......... 144
Figure 5-10: NEMO 2.0 network configuration [TRIMMED] ........................................... 144
Figure 5-11: Initiating the connection with CVA VDRGRAB-NET Control [FULL] .......... 147
Figure 5-12: Connection established [FULL] .................................................................. 147
Figure 5-13: Menu bar -> File -> Load Configuration from File [TRIMMED] .................. 148
Figure 5-14: Load configuration file [FULL] .................................................................... 149
Figure 5-15: Menu bar -> File -> Save Configuration as File [TRIMMED] ...................... 150
Figure 5-16: Save configuration file [FULL] .................................................................... 150
Figure 5-17: Enter desired IP address and subnet mask ............................................... 151
Figure 5-18: “Snap Image” with default offset values: H.: 178 V.: 40 [TRIMMED] ......... 152
Figure 5-19: “Snap Image” with default offset values: H.: 148 V.: 40 [TRIMMED] ......... 153
Figure 5-20: “Snap Image” with default offset values: H.: 178 V.: 20 [TRIMMED] ......... 153
Figure 5-21: Image Quality [FULL] ................................................................................. 154
Figure 5-22: Advanced [FULL] ....................................................................................... 154
Figure 5-23: NMEA connection for network and serial interface .................................... 158
Figure 5-24: Capture -> NMEA -> Interfaces [TRIMMED] .............................................. 160
Figure 5-25: Capture -> NMEA Sentences (1/2) [TRIMMED] ......................................... 163
Figure 5-26: Capture -> NMEA Sentences (2/2) [TRIMMED] ......................................... 163
Figure 5-27: Capture -> I/O devices [TRIMMED] ........................................................... 167
Figure 5-28: Analog Inputs [TRIMMED] ......................................................................... 169
Figure 5-29: Digital inputs [TRIMMED] ........................................................................... 171
Figure 6-1: Shutdown key ............................................................................................. 175
Figure 6-2: Remote Control Test Panel ........................................................................ 176
Figure 6-3: Main menu Remote Control Test Panel “day mode” [FULL] ...................... 177
Figure 6-4: Main menu Remote Control Test Panel “night mode” [FULL] .................... 177
Figure 6-5: Restart VDR about RCTP module [FULL] .................................................. 178
Revision: 1.0.5 ix
List of Figures VDR G4[e]
Technical Manual
x Revision: 1.0.5
VDR G4[e] List of Figures
Technical Manual
Revision: 1.0.5 xi
List of Figures VDR G4[e]
Technical Manual
List of Tables
1 Introduction
This Technical manual represents a standard publication, describing a VDR G4[e] delivered by the
INTERSCHALT maritime systems GmbH.
This instruction is to ensure a most efficient and safety handling with this product. The instruction is part
of the product and must be stored always accessible for your personnel.
Before you start working your personnel should read this instruction carefully and with understanding.
Requirement for a safety work is that all safety instructions and acts are observed.
Furthermore local prevention of accidents and safety instructions are valid for operation of this product.
The present technical manual helps the operating personnel on-board a vessel as well as the service:
Actions which can be done in any order are given with a point:
• Switch on instrument X
• Switch on instrument Y
Revision: 1.0.5 1
Introduction VDR G4[e]
Safety Instruction Technical Manual
Danger Meaning
Symbol
General Danger
All descriptions of the web-frontend and the program interface screenshots end with [TRIMMED] or
[FULL]. In contrast to [FULL], [TRIMMED] screenshots are reduced to the essential meaning to achieve
a document with more clarity and compactness.
The VDR G4[e] is designed exclusively for the purpose described in this manual. Using the system for
other purposes than those mentioned is considered contrary to its designated use.
INTERSCHALT maritime systems GmbH cannot be held liable for any damage resulting from such use;
the risk of such misuse lies entirely with the user.
The prerequisite for the reliable and safe operation of the VDR G4[e] is proper transportation and
storage as well as competent installation and assembly on board.
2 Revision: 1.0.5
VDR G4[e] Introduction
Technical Manual Safety Instruction
Every kind of using which is not described in chapter “Designated use” is not valid and therefore not
allowable.
In case of damages because of a failing use INTERSCHALT maritime systems GmbH takes no liability.
Risks of a failing use are only taken by the user.
All information in this manual refer to device, application place, transport, storage, installation, operation
and maintenance.
Unauthorised modifications, additions or conversions which affect the safety of the VDR G4[e] are not
permitted. Safety devices must not be bypassed, removed or made inactive.
Only use original spare parts and accessories recommended by the manufacturer.
Revision: 1.0.5 3
Introduction VDR G4[e]
Limited Liability Technical Manual
The user is obliged to operate the VDR G4[e] only when it is in good working order.
• Protect the VDR G4[e] against water, do not touch the electric components parts with wet hands
(except the FRM capsule).
• Do not use the device if it disseminates a nasty smell or if there are unusual noises.
• Do not put objects into the devices.
The protection of the VDR components is a prerequisite for safe and secure operation.
In addition to the instructions given in the operating manual, please observe the following:
This information is considering valid norms and regulations, state of the art and our long time experi-
ence.
4 Revision: 1.0.5
VDR G4[e] Introduction
Technical Manual Structure of the Manual
Part 1 INTRODUCTION
gives a short overview of the contents of the technical manual.
Part 2 FUNCTIONALITY
explains the functionality of the VDR G4[e].
Part 3 WEB-FRONTEND
shows and describes the pages of the web-frontend.
Part 4 INSTALLATION
describes installation and connection of each component.
Part 5 COMMISSIONING
describes the measures for setting to work of the VDR G4[e].
Part 6 OPERATING
explains the operating of the VDR G4[e].
Part 7 TROUBLESHOOTING, REPAIR AND MAINTENANCE
describes the recommended routines for locating an error and the error
elimination.
Part 8 DISPOSAL
gives information, how to dispose the modules of the VDR G4[e].
Part 9 APPENDIX
contains standard drawings and information.
Term Meaning
AIS Automatic Identification System
ARP Address Resolution Protocol
CAP Capture
COTS Commercial of the Shelf
DHCP Dynamic Host Configuration Protocol
DVI Digital Visual Interface
DVI-A Digital Visual Interface - Analog
DVI-D Digital Visual Interface - Digital
Revision: 1.0.5 5
Introduction VDR G4[e]
Important terms and abbreviations Technical Manual
Term Meaning
DVI-I Digital Visual Interface - Integrated
EMC Electromagnetic Compatibility
ECS Electronic Chart System
EPIRB Emergency Position Indicating Radio Beacon
FFC Float Free Capsule
FRM Final Recording Medium
FRNC Flame Retardant Non Corrosive
FTP File Transfer Protocol
GND Ground
GPS Global Positioning System
GRP Glass-reinforced Plastic
GSM Global System for Mobile Communications
HDMI High Definition Multimedia Interface
IEC International Electrotechnical Commission
IMO International Maritime Organization
Inmarsat International Maritime Satellite
IP Internet Protocol
ISDN Integrated Services Digital Network
ISPS-Code International Ship and Port Facility Security Code
LAN Local Area Network
MDP Maritime Data Processor
MER Maritime Event Recorder
NAS Network Attached Storage
NMEA National Marine Electronics Association
OPT Operational and performance test
ROV Remotely Operated Vehicle
SARSAT Search and Rescue Satellite-Aided Tracking System
SMB Server Message Block
TCP Transmission Control Protocol
UDP User Datagram Protocol
6 Revision: 1.0.5
VDR G4[e] Introduction
Technical Manual Important terms and abbreviations
Term Meaning
UPS Uninterruptible Power Supply
VDR Voyage Data Recorder
VGA Video Graphics Array
VHF Very High Frequency
XML Extensible Markup Language
Revision: 1.0.5 7
Introduction VDR G4[e]
Important terms and abbreviations Technical Manual
8 Revision: 1.0.5
VDR G4[e] Functionality
Technical Manual Purpose and Function
2 Functionality
All passenger ships and consecutively all of the other SOLAS ships, up from 3000 GT, constructed on
or after 1 July 2002 are to be equipped with voyage data recorders (VDRs) for a permanent acquisition
and storage of specific voyage data. This shall enable accident investigators to review procedures and
instructions in the moments before, during and after an emergency and help to identify the cause of any
accident.
A VDR has to maintain the secure and retrievable recording of information concerning position, move-
ment, physical status, command and control of a vessel for a period covering at least the last 48 hours
of operation.
The VDR G4[e] meets the requirements of the International Maritime Organisation (IMO), the Maritime
Safety Committee (MSC) resolution MSC.333(90) for revised performance standards of VDR and all
performance requirements according IEC 61996-1 Edition 2.0 from 2014-05. Mentioned regulations
specify detailed the data items to be recorded mandatorily, which are listed on chapter 6.9 "Handling
of recorded data" on page 193 of this manual. Additional information may be included as needed in a
particular project.
Data recording runs continuously on the principle of a circle memory. That means, data older than a
defined period of time (depending on the different storage media) will be overwritten.
The following paragraphs shall provide an overview of the components a VDR-G4[e] system standardly
consists of. Configurations vary project-related and may include additional components.
The following table shows the default recording intervals of NMEA, frames and voice for the different
storage mediums of the VDR G4[e].
Revision: 1.0.5 9
Functionality VDR G4[e]
Configuration of a VDR G4[e] Technical Manual
/ ! 8!5%! 3'!
!
*#2
+ -
0
/!(
7 .(.
0
(* !
!
% 7
;/. 3 !,
! /(:0/":0/,!
8!5
3 ! !4
! " 5+ 6-
10 Revision: 1.0.5
VDR G4[e] Functionality
Technical Manual Maritime Data Processor (MDP2020)
The MDP2020 module is the logical centre of the VDR G4[e] system and has the following functions:
• Visual and acoustic (optional) signalling of the VDR warnings/alarms and their acknowledgment.
• Operational and performance test (OPT) of the VDR-system. and the recorded signals
• Menu control with 4 buttons on the RCTP for the selection and testing of the individual groups.
• Various remote control functions for VDR main unit.
Revision: 1.0.5 11
Functionality VDR G4[e]
Audio2net module Technical Manual
The Audio2net module collects and pre processes analogue voice signals, coming from microphones
of the VDR G4[e] or other voice sources, like radios or telephones.
The microphone VCA004 receives audio signals on bridge or other rooms, to be monitored with the
following features:
• Symmetrical analogue signal output with 0dBm for the collected voice signals.
• Low pass for lowering the output signal > 6kHz as standard.
• Microphone test by piezo beeper.
• Microphone test is activated by increasing the supply voltage from 20 V DC to 24 V DC.
The NMEA2net module collects up to 5 NMEA sources and sends data via network interface or serial
interface to the VDR G4[e], using a specific protocol. By configuring different device IDs, up to 7
NMEA2net modules can be used in a system. It has the following main features:
• Received telegrams are buffered and can be provided via network as UDP packet and/or via serial
output.
• DIP switch 4x to set the ID
• Web-frontend for advanced configuration e.g.:
• Baud rate per input
• Interval for sending the buffered data
• Possibility of filtering NMEA telegrams, based on the header
• Network configuration and device ID, for special applications
• Define outputs, network and/or serial
• IP address is obtained by a DHCP request, default adjustment.
12 Revision: 1.0.5
VDR G4[e] Functionality
Technical Manual Tron 40VDR capsule
• If the DHCP request fails for 30 seconds, the static IP address will be used.
• If there is no static IP address adjusted via web-frontend, the default IP address (192.168.95.150)
will be used with device ID (1-7) as offset.
• All serial inputs are electrically isolated against each other and to the system.
• Max. 4500 characters per second can be provided.
The Tron 40VDR capsule is a combined float free FRM and Cospas-Sarsat EPIRB with following
features:
The NEMO 2.0 module constitutes a data recording medium, protected against external influences like
high temperature or water pressure, which has to be connected to a ship data processing interface to
guarantee its overall efficiency.
The acoustic beacon, fixed on the NEMO 2.0 module, fulfils the conditions of SAE AS 8045 and works
in a frequency 37,5 +/-1kHz with a battery operating time of at least 90 days.
• Network volume for MDP2020, offers a specific NAS server with NFS or/and SMB file system.
• Configuration via web-frontend.
• NEMO 2.0 get a static IP address.
Revision: 1.0.5 13
Functionality VDR G4[e]
Framegrabber FGR4 Technical Manual
Radar images are collected as VESA compatible analogue signals. The required image quality is
according to IEC 61996-1:2013. The FGR4 has the following main features:
• The FGR4 collects signals from the video source, equipped with VESA compatible analogue output.
• The resolution according to IEC 61996-1:2013 is maximum 1600x1200 at 60Hz. A lower resolution
is possible.
• If the current configuration cannot capture an image, the FGR4 tries to generate a significant image
with a list of VESA compatible video configurations.
• Significant images are zipped and sent to the VDR G4[e] via network, according to the current config-
uration parameters. This process uses the proprietary transmission protocol of the VDR G4[e].
• For configuration a Windows software tool communicates with the FGR4 via network.
Radar images are collected as VESA compatible analogue signals. The required image quality is
according to IEC 61996-1:2013. The FGR5 has the following main features:
• The FGR5 collects signals from the video source, equipped with VESA compatible analogue output,
DVI (single link) output or HDMI output.
• The FGR5 can collect 2 video sources at the same time. Source 1 is HDMI, Source 2 is DVI (all
types) or VGA.
• The resolution is maximum 1920x1200. A lower resolution is possible.
• Significant images are zipped and sent to the VDR G4[e] via network, according to the current config-
uration parameters. This process uses the Radar protocol according IEC 62388 Annex H.4 or the
proprietary transmission protocol of the VDR G4[e].
• Approved transfer protocol according IEC 62388 Annex H4 and IEC 61996-1:2013.
• Transfer protocol according IEC 61162-450 (binary transfer) and IEC 61996-1:2013.
• Transfer of compressed and uncompressed images via network.
• Image compression to bmp.gz, bmp as zip file and png.
• Two independent network ports: 1x Gigabit PoE and 1x Gigabit without PoE.
• Configuration via web-frontend
14 Revision: 1.0.5
VDR G4[e] Functionality
Technical Manual Replay and Realtime Monitor software
This module is a software solution for MS Windows XP, windows 7 and Windows 10. To collect specific
data from each vessel, the system is sub-divided into a common part and specific part of the vessel,
integrated as DLL.
The Replay and Realtime Monitor is deposited at the MDP2020 module and can be downloaded from
there. It has the following main features:
IO system 750, a product of WAGO Kontakttechnik GmbH, serves as PLC module. The IO system
captures analogue and digital values and bases upon the Ethernet coupler 750-352.
Revision: 1.0.5 15
Functionality VDR G4[e]
PLC module Technical Manual
16 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual Login and Logout
3 Web-frontend
This chapter shows and describes the web-frontend of the VDR G4[e] and all components. For all
shown screenshots, the login level “service” is used.
The appearance of the screenshots depends on the used browser and the language settings of the
service notebook. For all screenshots the browser Mozilla Firefox is used.
Logout Button
Revision: 1.0.5 17
Web-frontend VDR G4[e]
Login and Logout Technical Manual
Menubar
Pictogram
Device list
Manuals
Tools for
commissioning and
troubleshooting
Replay system
Refresh button
ICU NMEA2NET
This list contains all available This list contains all available
ICUs. NMEA2nets.
• ICU01 • N2N01
• ... • ...
AUDIO2NET Other
This list contains all available This list contains all other avail-
Audio2nets. able components.
• A2N02 • FGR4/FGR5
• ... • Jotron
• PLC
18 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Listed
NMEA2net has been added its configuration to MDP2020.
Green checkmark
NMEA2net is reachable by MDP2020 module.
Red X
NMEA2net is not reachable for theMDP2020. (No communication).
Dustbin
With a click on the dustbin the selected NMEA2net configuration will
be deleted. During next reboot of the NMEA2net module the config-
uration is rewritten.
3.2 MDP2020
Revision: 1.0.5 19
Web-frontend VDR G4[e]
MDP2020 Technical Manual
Ship
IMO number ... is a permanent number assigned to each quali-
fying ship for identification.
Ship name ... is the name of the ship.
Callsign In broadcast and radio communications, a call sign
is a unique designation for a transmitting station.
Shipyard ... are places which repair and build ships.
MMSI number ... is a series of nine digits which are sent in digital
form over a radio frequency channel in order to
uniquely identify ship stations, ship earth station,
coast stations, coast earth stations and group
calls.
Ship owner ... is the owner of a commercial ship.
20 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Ship
Hull number ... is a serial identification number given to a boat
or ship by shipyard.
Height [m] ... is the distance between waterline and highest
point of the ship.
Phone number ... is the telephone number of the ship.
Draught [m] ... is the distance between waterline and the
deepest point of ship.
System
Dimension A B C D [m] Ship dimension and position of reference GPS
antenna.
GPS reference GPS reference position.
MDP serial number Serial number of the MDP2020 module.
VDR serial number Generated serial number of the whole VDR
system. Format: IS-<IMO-no>-G4e
Certificate Current certificate number of type approval.
Replay
ECS dongle number See manual of Replay Software.
ECS hardware ID See manual of Replay Software.
ECS registration key See manual of Replay Software.
Revision: 1.0.5 21
Web-frontend VDR G4[e]
MDP2020 Technical Manual
Replay
Caps license This license is needed for special Replay System
capabilities like “print report”.
LAN of Replay System Selects the corresponding LAN interface for the
replay system.
22 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 23
Web-frontend VDR G4[e]
MDP2020 Technical Manual
24 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 25
Web-frontend VDR G4[e]
MDP2020 Technical Manual
The following figure shows the settings of a selected agents. The settings of the exemplary agent
“Frame” are shown. The other agents have the same structure.
26 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Parameter
Name Name of the parameter.
Value Value of the parameter.
Button “Remove” Remove the corresponding parameter.
Button “Add” Adds a new parameter.
Revision: 1.0.5 27
Web-frontend VDR G4[e]
MDP2020 Technical Manual
28 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 29
Web-frontend VDR G4[e]
MDP2020 Technical Manual
30 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Button “Add new host” Creates an new host (network device) entry.
Button “Save” Saves the current settings and removes selected
host entries. Afterwards a restart of the VDR G4[e]
is required.
Revision: 1.0.5 31
Web-frontend VDR G4[e]
MDP2020 Technical Manual
32 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
The following figure shows the settings of a selected NMEA network and serial connection. The shown
settings of an NMEA connection has exemplary character. The other NMEA connections have the
same structure.
Revision: 1.0.5 33
Web-frontend VDR G4[e]
MDP2020 Technical Manual
Receive filter
Checkbox Activates/deactivates the receive filter.
Function Select between blacklist/whitelist for the filter.
Active Activate/deactivate the entry in the list.
Id (only network) Each sentence in the list has a unique id.
Header Header of the NMEA sentence.
Min. reception interval (ms) Minimum time interval between 2 NMEA
sentences.
Result This sentence will be received or ignored.
Button “Remove” Removes the corresponding NMEA sentence from
the list.
Button “Add” Adds a new NMEA sentence to the list.
Transmit filter
Checkbox Activate/deactivate the transmit filter.
Active Activate/deactivate the entry in the list.
Id (only network) Each sentence in the list has a unique id.
Header Header of the NMEA sentence.
Max. transmission interval Maximum time interval between 2 NMEA
(ms) sentences.
Result This sentence will be sent or ignored.
Button “Remove” Removes the corresponding NMEA sentence from
the list.
Button “Add” Adds a new NMEA sentence to the list.
The following figure shows the settings of a selected NMEA serial connection. The shown settings of
an NMEA serial connection has exemplary character. The other NMEA serial connections have the
same structure.
34 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 35
Web-frontend VDR G4[e]
MDP2020 Technical Manual
Button “Clear exp. sent.” Clear the entries in field “Expected sentences” of
all NMEA interfaces.
Button “Save” Saves the current settings. Afterwards a restart of
the VDR G4[e] is required.
36 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 37
Web-frontend VDR G4[e]
MDP2020 Technical Manual
Settings “Common”
38 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Last receipt
Revision: 1.0.5 39
Web-frontend VDR G4[e]
MDP2020 Technical Manual
40 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 41
Web-frontend VDR G4[e]
MDP2020 Technical Manual
General errors
42 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 43
Web-frontend VDR G4[e]
MDP2020 Technical Manual
44 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Button “Abort” Leaves the edit mode without saving the changes.
Button “Save” Leaves the edit mode and saves the changes.
Revision: 1.0.5 45
Web-frontend VDR G4[e]
MDP2020 Technical Manual
46 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Button “Abort” Leaves the edit mode without saving the changes.
Button “Save” Leaves the edit mode and saves the changes.
Revision: 1.0.5 47
Web-frontend VDR G4[e]
MDP2020 Technical Manual
48 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 49
Web-frontend VDR G4[e]
MDP2020 Technical Manual
50 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
Revision: 1.0.5 51
Web-frontend VDR G4[e]
MDP2020 Technical Manual
52 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual MDP2020
• S.M.A.R.T info
• Merlog
• Systemlog
• Errlog
Revision: 1.0.5 53
Web-frontend VDR G4[e]
MDP2020 Technical Manual
You have the possibility to download the log files. For further information see chapter "Menu item
“Service” “Options” “Get Logs”" on page 51.
54 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual Interface Control Unit ICU
Menubar
Revision: 1.0.5 55
Web-frontend VDR G4[e]
Interface Control Unit ICU Technical Manual
For a detailed description see chapter 3.2.7 "Menu item “Capture” “NMEA”" on page 32.
56 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual Interface Control Unit ICU
For a detailed description see chapter 3.2.5 "Menu item “System” “Agents”" on page 26.
Revision: 1.0.5 57
Web-frontend VDR G4[e]
Interface Control Unit ICU Technical Manual
58 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual Interface Control Unit ICU
Button “Add new host” Creates a new host (network device) entry.
Button “Save” Save the current settings and removes selected
host entries.
Revision: 1.0.5 59
Web-frontend VDR G4[e]
Interface Control Unit ICU Technical Manual
60 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual Audio2net module
This chapter shows and describes the web-frontend of the Audio2net module.
Menubar
Revision: 1.0.5 61
Web-frontend VDR G4[e]
Audio2net module Technical Manual
62 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual Audio2net module
SNMP
Enabled Enable/Disable the SNMP service.
Traps Enable/Disable the SNMP traps.
Trap host ip IP address of the Trap host.
Contact Contact for this VDR system.
Button “Save” Saves the current settings. This button is visible
when changes are made.
Revision: 1.0.5 63
Web-frontend VDR G4[e]
Audio2net module Technical Manual
Testresults
Result Description
No microphone configured and no microphone
connected.
64 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual NMEA2net module
This chapter shows and describes the web-frontend of the NMEA2net module.
Revision: 1.0.5 65
Web-frontend VDR G4[e]
NMEA2net module Technical Manual
Menubar
Status of module
- Load of network queue
- Load of serial queue
- Error state of the ports
66 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual NMEA2net module
Revision: 1.0.5 67
Web-frontend VDR G4[e]
Tron 40VDR capsule Technical Manual
This chapter shows and describes the web-frontend of the Tron 40VDR capsule.
You can enter the web-frontend of the Tron 40VDR capsule on two ways:
68 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual Tron 40VDR capsule
Revision: 1.0.5 69
Web-frontend VDR G4[e]
Tron 40VDR capsule Technical Manual
70 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual FRM NEMO 2.0
This chapter shows and describes the web-frontend of the NEMO 2.0 module.
You can enter the web-frontend of the NEMO 2.0 module on two ways:
Revision: 1.0.5 71
Web-frontend VDR G4[e]
FRM NEMO 2.0 Technical Manual
Logout Button
Menubar
72 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual FRM NEMO 2.0
Revision: 1.0.5 73
Web-frontend VDR G4[e]
FRM NEMO 2.0 Technical Manual
74 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual FRM NEMO 2.0
Revision: 1.0.5 75
Web-frontend VDR G4[e]
FGR 5 Technical Manual
3.8 FGR 5
This chapter shows and describes the web-frontend of the FGR5. You can enter the web-frontend of
the FGR5 module on two ways:
For access to all submenu items, except “About” “System information” you have to log in. The login
dialog is shown in the following picture:
76 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual FGR 5
Figure 3-80: Position of eth0 = LAN0 with POE and eth1 = LAN1
Revision: 1.0.5 77
Web-frontend VDR G4[e]
FGR 5 Technical Manual
78 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual FGR 5
Input selection
Set HDMI ratio The setting of the aspect ratio affect on the HDMI
input.
Set DVI/VGA ratio The setting of the aspect ratio affect on the DVI/
VGA input.
Revision: 1.0.5 79
Web-frontend VDR G4[e]
FGR 5 Technical Manual
80 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual FGR 5
Revision: 1.0.5 81
Web-frontend VDR G4[e]
FGR 5 Technical Manual
Network parameter
Transfer protocol Select between the proprietary “IMS Transfer”
protocol or the “Radar TCP” protocol according
IEC 91996-1:2013. Default: “Radar TCP”.
TCP destination IP Destination IP of the receiver.
TCP network destination port TCP port of the receiver.
82 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual FGR 5
Revision: 1.0.5 83
Web-frontend VDR G4[e]
FGR 5 Technical Manual
84 Revision: 1.0.5
VDR G4[e] Web-frontend
Technical Manual FGR 5
The buttons “Log” are enabled when the corresponding log is activated. For further information see
chapter 7.9.6 "Logfiles" on page 238.
Revision: 1.0.5 85
Web-frontend VDR G4[e]
FGR 5 Technical Manual
86 Revision: 1.0.5
VDR G4[e] Installing
Technical Manual
4 Installing
This part describes all required measures for installing the VDR G4[e]
After delivering of the VDR G4[e] each device should be inspected for visible signs of damage. The
installation of each module as well as the connections to be performed, are described in the following
paragraphs.
All VDR G4[e] modules can be mounted without vibration dampers directly on a bulkhead or in a rack.
The mounts should be stable enough to carry the weight of the modules and to prevent the generation
of resonant frequencies.
Electronics Units
Dimensions, weights, spaces required for service and maintenance and special installation instructions
are stated in the outline drawings and installation drawings (see chapter 9 "Appendix" on page 245)
of the corresponding unit. In general, the following points also apply:
• The lifetime of the components of all electronics units generally decreases with increasing ambient
temperature; it is therefore advisable to install such units in air-conditioned rooms to ensure low
humidity and a temperature below 30°C. If there are no such facilities - e.g. deck house or space
near or below the water line - these rooms must at least be dry, adequately ventilated and kept at a
suitable temperature in order to prevent the formation of condensation inside these units.
• With most electronic units, cooling takes place via the surface of the casing.
The cooling must not be impaired by partial covering of the unit as a result of insulation (if any) of the
room (the wall on which the casing is mounted), or by installation of the unit in a confined cabinet.
Furthermore, the distance from the ceiling and the floor or from a unit situated underneath must be at
least 500 mm and on the right and left side at least 100 mm.
• For service purposes, a power socket (220/230V AC) and adequate lighting are necessary in the
vicinity of each electronic unit.
• In the area of the wheel house, the distance of each electronics unit from the magnetic standard
compass or the magnetic steering compass must not be less than the permitted magnetic protection
distance.
This distance is measured from the centre of the magnetic system of the compass to the nearest point
on the corresponding unit concerned and shall be indicated on the electronic unit.
• When selecting the site for a unit, the maximum cable lengths have to be considered according to
the notes in the cabling documents (remarks, cable list).
• The accessibility for maintenance and service (stated in the outline drawings or installation draw-
ings) must be considered.
• When a unit is being installed, the base, floor or bulkhead must be checked to ensure that it is flat
and stable in order to avoid twisting of the unit when the fixing screws are tightened, because such
twisting could impair mechanical as well as electrical or electronic functions. Any unevenness should
be compensated for by means of spacing-washers.
Revision: 1.0.5 87
Installing VDR G4[e]
Wiring Technical Manual
• The grounding screws of the units must be connected to the body of the ship (ground); the wire used
should have a cross sectional area of at least 6 mm².
Aboard a vessel with a fibreglass network (GRP), a grounding network with a high conductance - taking
into consideration the working frequencies of the other equipment - must be provided in order to
achieve satisfactory EMC (electromagnetic compatibility).
• In the interests of safety during maintaining or servicing, the shipyard or customer should provide a
common isolating switch or circuit breaker (in conjunction with a contractor, if necessary) for all inter-
connected equipment.
• Transportation damage, even if apparently insignificant at first glance, must immediately be exam-
ined and be reported to the freight carrier. The moment of setting-to-work of the equipment is too
late, not only for reporting the damage but also for the supply of replacements.
• The commissioning and first set-to-work of the system has to be done exclusively by technicians
authorised by INTERSCHALT maritime systems GmbH.
• After hand-over of the equipment in good operating condition to the customer, the Acceptance Test
should be filled in completely and then forwarded to INTERSCHALT maritime systems GmbH, as
proof of such fulfilment. These requirements have to be fulfilled in order to avoid the risk of losing
the warranty.
4.1 Wiring
Cable types, cable data, maximum cable length, special instructions for cable laying and connection
details are defined in the cabling documents of the corresponding equipment (consisting of schematic
diagram, remarks, cable list and connection diagram).
In order to ensure proper functioning of the equipment, the cable types should be selected according
to the cable lists. The designations for the cables are based on the German Standards DIN. Therefore
cable types as well as Interface connections should be discussed and agreed with INTERSCHALT
maritime systems GmbH if they are not equal to German DIN Standards.
• For the cables inside the cabinets, an extra length of 1 metre is necessary at each end. If the height
of the unit exceeds 0.5 m, an extension by 1.0 m plus the height of the cabinet is necessary.
• The cables must be marked by the electrician at both ends with the cable numbers corresponding
to the connection diagrams documents.
• Where necessary, particular cable glands - marked with letters and/or numbers - are assigned to the
cables. The identification letters and numbers are stated in the connection diagrams; they are either
fixed to the unit or can be seen from the outline drawings.
88 Revision: 1.0.5
VDR G4[e] Installing
Technical Manual Wiring
• All cables should be kept as short as possible, especially coaxial cables to minimize attenuation of
signal.
• All outdoor installed connectors (e.g. on coaxial cables) should be waterproof by design to protect
the cable against water penetration.
• Coaxial cables should be installed in separate signal cable channels/tubes and at least 100 mm
away from power supply cables. Crossing of cables should be done at right angles (90°). Coaxial
cables should not be exposed to sharp bends, which may lead to change the characteristic imped-
ance of the cable. The minimum bend radius should be 5 times the cable’s outside diameter.
• It must be ensured that all cables - including their screens - are inserted in the units in adequate
lengths and do not end before reaching the destination equipment. This is not valid for the use of
cable glands with grounding inserts.
• With multicore cables, it is useful to strip down and lace the single wires according to the terminal
sequence.
• Receptacle-type cable terminals included in the delivery must be crimped to the connecting leads by
means of a suitable pair of AMP pliers. If a terminal board of a unit has no tabs for the above
mentioned receptacles, other suitable cable terminals must be used.
• Existing cable grippers in the units must be used.
• All cable connections must be carefully checked after completion of the cable work and all cable
screens must be grounded via the shortest possible connections - if not stated otherwise in the
cabling documents/connection diagram.
• All cables must be secured by means of suitable clamps (pull-relief) before entering the units.
• When soldering stripped coaxial cables to connectors, it must be ensured that the central conductor
and the screening do not produce a short circuit.
• It must be ensured that cables do not block any moving parts within a unit.
• Stuffing tubes exposed to the open air must, without fail, be sealed with compound.
• Power leads must be protected by slow-blow fuses according to their cross section.
Revision: 1.0.5 89
Installing VDR G4[e]
Wiring Technical Manual
Grounding
Grounding is important for EMC purposes as well as for protecting people’s lives.
The purposes are covered by the standard grounding of the system’s housings to the ship’s metallic
structure (bolted or welded). Regardless of the type of ship’s grounding (e.g. star pattern or ground
plane pattern), no potential difference should be measurable between two different ground connectors.
Potential differences cause compensation currents on the cable shields. If the ship has no metallic
structure, all conductively connected metallic parts form an artificial ground.
Whenever possible, metallic housings should be screwed or welded directly to the ship’s metallic struc-
ture.
All ground connections should have a low RF-impedance, and should be resistant against vibration and
corrosion.
Grounding conductors on an open-air deck must be made of corrosion-protected steel, and inside the
ship they must be made of copper.
EMC Purposes
The shields of all cables must be connected at both ends if no other instructions are given.
Protective Ground
All removable metallic parts of the housings are grounded by means of separate, flexible cables to the
main structure of the housing. It is important to connect this ground-cable again after parts have been
dismounted or exchanged.
90 Revision: 1.0.5
VDR G4[e] Installing
Technical Manual Wiring
Ethernet LAN
The Ethernet LAN twisted pair cabling (100BaseT) must not exceed a length of 100 m.
Cable to Microphone
The Microphones could be connect to the VDR G4[e] while using a 2x2x0.75 FRNC ship cable or while
using a 8x0.68 Ethernet STP cable. The maximum length of this cable is 100 m.
Video cable
The signals from the Radar are transmitted using a DVI respectively a DSub cable. The maximum
length of this cable is 5 m.
The grounding should be done in such a way that the connection can be inspected in a convenient
manner.
Revision: 1.0.5 91
Installing VDR G4[e]
Maritime Data Processor MDP 2020 Technical Manual
! "
%
&
'
(
#$
The MDP 2020 module has a width of 170 mm and is mounted on a 35 mm DIN rail.
The configuration of the MDP 2020 module has already been performed by INTERSCHALT maritime
systems GmbH, so that from customer side no further settings are required. The following paragraphs
nevertheless describe the modules, the settings of which are necessary for a trouble free operation.
92 Revision: 1.0.5
VDR G4[e] Installing
Technical Manual Maritime Data Processor MDP 2020
Terminal Description
Position see previous figure
GBit Subnet1 VDR intern network, Connection to ICU
GBit Subnet2 Multicast network or navigation system
GBit Subnet3 Additional network system or ship network
X8 USB USB flash drive, Emergency Backup Volume
S2 STOP USB Stop USB recording
Terminal Description
Position see previous figure
Power 24V External Power Supply from ICU
Pin 1 24V
Pin 2 0V
Pin 3 Guard, alternative grounding of MDP 2020 module,
usually free
RS422-1 RS 422 connection to Bridge Alarm Management system
(BAMS) if available. Otherwise spare for serial data.
Pin 1 Tx+
Pin 2 Tx-
Pin 3 Rx+
Pin 4 Rx-
Pin 5 Analog GND (Guard)
RS422-2 RS 422 connection to AIS NMEA
Pin 1 Tx+
Pin 2 Tx-
Pin 3 Rx-
Pin 4 Rx+
Pin 5 Analog GND (Guard)
ON/OFF Key Switch
Pin 1 Common, current flow to key switch
Pin 2 Common, current flow to key switch
Revision: 1.0.5 93
Installing VDR G4[e]
Maritime Data Processor MDP 2020 Technical Manual
$%&'
(&
!
,,-./0
&!1
"#
"#
)#*
$
"#
Figure 4-3: Internal connections and environment
Connec- Descriptions
tions
X2 Power to SSD
X3 Data to SSD
DIP Description
switch
J1 Reset to default. For further details see chapter 7.1.5
"Reset to defaults" on page 206.
94 Revision: 1.0.5
VDR G4[e] Installing
Technical Manual Interface Control Unit (ICU)
Button Description
S5 Reset
S4 MDP 2020 “Off”
! "
%
&
'
(
#$
The ICU module has a width of 392mm and is mounted on a 35 mm DIN rail. The battery (9500 mAh)
has a width of 125 mm and a depth of 67 mm. The battery (15300 mAh) has a width of 125 mm and a
depth of 98 mm.
The configuration of the ICU module has already been performed by INTERSCHALT maritime systems
GmbH, so that from customer side no further settings are required. Default ID is 1, but are used in a
project more than one ICU, then the next receives the ID 2, etc.When using more than one ICU the ID
of the Audio2net Module have be to adjusted accordingly higher.
The following paragraphs nevertheless describe the modules, the settings of which are necessary for
a trouble free operation.
Revision: 1.0.5 95
Installing VDR G4[e]
Interface Control Unit (ICU) Technical Manual
P1 P2 P3 P4 P5 P6 P7 P8 P9 P10
X11 X13 X9 X15 X17
Pin1 Pin2
Figure 4-5: External connections
For installation connect the terminals like shown in the following table for a standard VDR:
Terminal Description
P1 NMEA2net (for NMEA2net with ID 1)
P2 Tron 40VDR
P3 Framegrabber Units
P4 MDP 2020
P5 Audio2net 1 (for Audio2net with ID 2)
P6 Audio2net 2 (for Audio2net with ID 3)
P7 LAN switch
P8 Always free for Authority
P9 Remote Control Test Panel
P10 USB Port not used
96 Revision: 1.0.5
VDR G4[e] Installing
Technical Manual Interface Control Unit (ICU)
Terminal Description
X1 1 NMEA2net (for more: Relay for power supply)
Remote Control Test Panel
Pin 1 24V
Pin 2 0V
X2 Tron 40VDR
Pin 1 24V
Pin 2 0V
X3 1 Framegrabber Unit (for more: Relay for power supply)
Pin 1 24V
Pin 2 0V
X4 MDP 2020
Pin 1 24V
Pin 2 0V
X5 LAN switch
Pin 1 24V
Pin 2 0V
X6 Not used
Pin 1 24V
Pin 2 0V
X7 1 PLC (for more: Relay for power supply)
Pin 1 24V
Pin 2 0V
X8 NEMO 2.0
Pin 1 24V
Pin 2 0V
X9 RS 422 spare for serial data (RS422-1)
Pin 1 TX+
Pin 2 TX-
Pin 3 RX+
Pin 4 RX-
Pin 5 Analog GND (Guard)
Revision: 1.0.5 97
Installing VDR G4[e]
Interface Control Unit (ICU) Technical Manual
Terminal Description
X10 RS 422 spare for serial data (RS422-2)
Pin 1 TX+
Pin 2 TX-
Pin 3 RX+
Pin 4 RX-
Pin 5 Analog GND (Guard)
X11 Indication Emergency Backup (optional)
default
J10 on 2-3 Dry relay contact as output
Pin 1 Usually opened
Pin 2 Common
alternative
J10 on 1-2; 3-4 24V as output
Pin 1 24V
Pin 2 0V
X12 Not used
X13 VDR Alarm
see Figure 4-6: "Default alarm connection between a
bridge alarm panel and the ICU" on page 100.
default
J22 on 2-3 Dry relay contact as output
Pin 1 Common
Pin 2 Normally opened
see Figure 4-7: "Alternative alarm connection
between a bridge alarm panel and the ICU" on page 100.
alternative
J22 on 1-2, 3-4 24 as output
Pin 1 24V
Pin 2 0V
X14 Key Switch
Pin 1 Common current flow to key switch
Pin 2 Common current flow to key switch
98 Revision: 1.0.5
VDR G4[e] Installing
Technical Manual Interface Control Unit (ICU)
Terminal Description
X15 VHF1
Pin 1 RX+
Pin 2 RX-
X16 VHF2
Pin 1 RX+
Pin 2 RX-
X17 Rechargeable Battery
Pin 1 Temperature Sensor +
Pin 2 Temperature Sensor -
Pin 3 0V
Pin 4 21V
X18 24V External Power Supply
Pin 1 24V
Pin 2 0V
Pin 3 Guard, alternative grounding of ICU module, usually
Button Description
S1 not used
S2 Battery level indicator
LED Description
D43...D46 Battery level indication
Revision: 1.0.5 99
Installing VDR G4[e]
Interface Control Unit (ICU) Technical Manual
Figure 4-6: Default alarm connection between a bridge alarm panel and the ICU
relay contact
Figure 4-7: Alternative alarm connection between a bridge alarm panel and the ICU
! "
%
&
'
(
#$
The Remote Control Test Panel has a dimension of 160x240x52 mm (including wiring). Install the
Remote Control Test Panel into the related console cut-out.
In case of implementing the VDR G4[e] into systems with no possible free input of the central bridge
alarm system the Remote Control Test Panel is needed to display the VDR G4[e] main alarm. Since a
powered-down VDR G4[e] should also signal an alarm, the supply voltage for the alarm unit must be
provided independently and not be supplied from the VDR G4[e] itself. The RCTP is able to signal the
failure “VDR offline”. The RCTP is also used for the performance test. The data gets the RCTP via
network cable from Port 9 of the ICU.
For installation connect the terminals like shown in the following table:
Terminal Description
spec. socket POWER SUPPLY
Description see following table.
RS422/485-1 RESERVED
not required
RS422/485-2 SERIAL INTERFACE
RS422 Sensor Input 2 (not required)
RJ45 socket ETHERNET INTERFACE
Network Connection to ICU Port 9
The pin assignment of the Power Supply connector is shown in the following table:
Pin Description
1 +24 V Main Power (from ICU X1 Pin 1)
2 0 V Main Power (from ICU X1 Pin 2
3 0 V Emergency Power (from highest avaiable
external 24V power supply).
4 +24 V Emergency Power (from highest avaiable
external 24V power supply).
Button Description
ACK Alarm / Acknowledge
Up Arrow key up
Dn Arrow key down
Enter Menu / Enter
! "
%
&
'
(
#$
The Audio2net module has a dimension of 125x125x60 mm and is mounted on a 35 mm DIN rail.
The configuration of the Audio2net module has already been performed by INTERSCHALT maritime
systems GmbH, so that from customer side no further hardware settings are required. The following
paragraphs nevertheless describe the modules, the settings of which are necessary for a trouble free
operation.
The first module has ID 2, the second module has ID 3 etc. This is at a standard VDR. Take into consid-
ersation the number of ICU modules. The ID of the Audio2net module is shifted depending up on the
number of the ICU‘s. For example, 2 ICU modules, then the first Audio2net module begins with the ID
3, etc.
X1 S3 P1 S1 S2
X2 X3 X4 X5
S1 Rotary Switch
The rotary switch S1 identifies the Audio2net module clearly in the network. The settings 0 and 1 are
invalid for operating.
Table 4-14: Enter the settings (with only one ICU) as follows and without jumps
S2 reset button
For using the Reset Button, see chapter 7.4.2 "Reset to defaults" on page 218.
LED Description
LED “link” orange LAN connection exists
LED “act.” green LAN connection is active
! "
%
&
'
(
#$
The faceplate of the microphone has a dimension of 137x80 mm. For the inner life an opening of 67 mm
as a diameter and 80 mm as depth is required. 3 mm holes are required to attach the microphone unit
using countersunk screws.
4.6.1 Position
Place the microphones so that all voice communication at or near the conning station, the radar screen,
the chart tables and in the bridge wings can be collected. The microphones should also register in- and
outgoing signals from intercoms and public address systems as well as any acoustic alarms from equip-
ment mounted on the wheelhouse.
In the bridge interior the microphones are installed in the ceiling. In the exterior locations, install the
microphone units out of spray and wind in order to reduce unwanted noise.
Place the microphones as far as possible from loudspeakers, ventilation ducts, neon tubes and other
sources of acoustic interference.
For indoor and outdoor operating one microphone type is used. Outdoor microphones are installed in
the wing console. If no wing console is existing the microphones are delivered with housing. In this case
place the housing splash-proof.
The connection cable must be of sufficient length that the microphones can be installed and later
removed for maintenance. A shielded cable of at least 2 twisted pairs is required.
! "
%
&
'
(
#$
The NMEA2net module has a dimension of 64x150x34 mm and is mounted on a 35 mm DIN rail.
The configuration of the NMEA2net module has already been performed by INTERSCHALT maritime
systems GmbH, so that from customer side no further settings are required. The following paragraphs
nevertheless describe the modules, the settings of which are necessary for a trouble free operation.
Adjust the correct ID of the device. Adjust 0 for resetting the device to factory settings.
More NMEA2net modules must be installed over a Moxa switch or additional ICU‘s. Not included in the
basic equipment of the VDR G4[e].
LED Description
D2 RX Port 1
D3 RX Port 2
D4 RX Port 3
D5 RX Port 4
D6 RX Port 5
D9 TX Port 1 (programming)
D10 TX Port 5
D11 Control LED for +3.3 V
! "
%
&
'
(
#$
The Tron 40VDR, as (FRM) with special protective properties of data, is an integral part of the VDR
G4[e]. The Tron 40VDR is an EPIRB combined with a storage device. It is a float free final recording
medium (FRM), developed for using with the VDR G4[e]. It shall be released automatically by hydro-
static release unit with appropriate water depth of 1.5-4.0 m, if vessel sinks. To protect the capsule from
being damaged, it is placed in a bracket with docking-station-module. The EPIRB with the flash drive
is recovered and analyzed in a case of accident
For wiring Tron 40VDR capsule please refer to Technical Manual Tron 40VDR capsule.
The Tron 40 VDR has a total dimension of 200 mm diameter, 400 mm height and a weight of 1.9 kg. It
meets the requirements of IEC 61996-1:2013.
- DO NOT OPEN -
REPORT TO AUTHORITIES
4.8.1 Placement
The Tron 40VDR must be installed on the open wheelhouse deck. The capsule should float freely. So
should be minimised the risk of obstruction after release. The Tron 40VDR should be located so, that
it only need a short detour to take it along during evacuation of the ship in case of an emergency.
For connections of the Tron 40VDR like shown in the following table:
%
&
'
(
#$
The NEMO 2.0 module, as (FRM) with special protective properties of data, is an integral part of the
VDR G4[e]. The module is developed for using with the VDR G4[e].
The NEMO 2.0 is made of two parts. The upper part, the case, is closed in itself. It contains the insu-
lating material, the flash storage and the processor PCB board. The upper part with its included flash
drive will be recovered and analysed in case of an accident and the mounting plate remains on the ship.
Both parts are secured by dint of a clamp with attached anti-tamper seal.
The NEMO 2.0 has a total dimension of 342x218x180 mm and a weight of 12.2 kg (mounting plate
3,0 kg + data capsule 9.2 kg). It is coated with an orange-coloured reflective foil, in addition, bounded
with a reflective adhesive tape at the edges, according to IMO A.861 (20). The NEMO 2.0 is labelled
as shown below upon a reflecting underground, entirely according to the requirements of IEC 61996-
1:2013.
- DO NOT OPEN -
REPORT TO AUTHORITIES
The serial number is placed on an adhesive label laterally, well legible fixed on the NEMO 2.0.
Acoustic beacon
The acoustic beacon, fixed on the NEMO 2.0, fulfils the conditions of SAE AS 8045
and works in a frequency 37,5 kHz +/- 1 kHz with a battery durability of at least 90 days.
4.9.1 Placement
Device damage
During the installation, protect the base plate and the
upper component against humidity.
Before reassembling, control the device by a visual
inspection concerning an orderly status and the exist-
ence of the desiccant bag, same as the fit of gasket
seal.
The following extract from IEC 61996-1:2013 defines the location of the NEMO 2.0 module:
“The protecting capsule has to be placed near the bridge in the exterior deck-area, to maximise the
plausibility of preservation and salvage of data after an accident. The capsule has to be fixed afar from
hemp rope or similar and other possible impediments, but as near as practically possible at the ship's
axis.
Criteria to be considered in appointment of the optimal position have to enclose the following, but are
not confined of:
Eth1 RJ 45 Socket
Eth0 Terminal
For connections of the NEMO 2.0 processor unit install terminals like shown in the following table:
Table 4-25: LED Status of the NEMO 2.0 (in the device)
LED Status
SATA LEDs
D1 Red, Link established
D2 Yellow, Activity
LAN LEDs
D3 Red, Link established
D4 Yellow, Activity
! "
%
&
'
(
#$
The FGR4 module has a dimension of 157x115x92 mm and is mounted on a 35 mm DIN rail.
The configuration of the FGR4 module has already been performed by INTERSCHALT maritime
systems GmbH, so that from customer side no further settings are required. The following paragraphs
nevertheless describe the modules, whose settings are necessary for a trouble free operation.
1 2 3 4 5
For installation connect the terminals of the FGR4 module like shown in the following table:
The external frame grabber has two connections to the ICU module. The power supply is connected
with an external DC/DC-converter at X3. The network cable which is connected at P3. Place the FGR4
module near the video source and use a max. 5 m video cable for connection. Following cable types
can be used:
DVI (male) to DVI (male); DVI (male) to VGA (male); DVI (male) to RGBHV (male)
! "
&
'
(
)
#$%
The FGR5 module has a dimension of 193x119x58 mm and is mounted on a 35 mm DIN rail.
The following paragraphs nevertheless describe the modules, whose settings are necessary for a
trouble free operation.
The FGR5 can be mounted backboard upright or sidewall upright. The factory default position is back-
board upright. A sidewall upright mounted FGR5 has a less installation deeps, but needs a larger instal-
lation width. The cables will now connected from the side.
If the FGR5 should be mounted sidewall upright, then the DIN rail bracket at the backboard has to be
unscrewed and screwed at the sidewall. The position of the DIN rail bracket is shown in the following
figure.
1 2 3 4 5
9 8 7
Grounding necessary
You have to make a connection between the ground
bolt of the FGR5 (Position 6) and the designated Earth
connection of the system. The cross section of the wire
should be 4 mm² or greater.
For installation connect the terminals of the FGR5 module like shown in the following table:
The external frame grabber has two connections to the ICU module, the power supply which is
connected at X3 and the network cable which is connected at P3. Place the FGR5 module near the
video source and use a max. 5 m video cable for connection.
5 Commissioning
General
The VDR G4[e] is a modular system. The configuration of the modules has already been performed by
the manufacturer, so that from customer side no further settings are required.
The commissioning of the VDR G4[e] takes place via web-frontend. Commission the modules
NMEA2net and Audio2net one after the other. The Remote Control Test Panel can not be configured
via a web-frontend.
The appearance of the screenshots depends on the used browser and the language settings of the
service notebook. For all shown screenshots the browser Mozilla Firefox is used.
Device damage
Do not apply AC line voltage to any terminal.
Logout Button
For a correct commissioning carry out the steps in the following table:
For a correct commissioning carry out the steps in the following table:
For a correct commissioning carry out the steps in the following table:
The RCTP is not only one display for VDR alarm, it is also used for the performance test. The perfor-
mance test checks the status of the recorded data on accuracy.
Infos about
- Version VDR
- IP Addresses
- Company
- Version RCTP
Settings:
Dimming mode
Remote control from bridge panel
or
Local control about arrow keys
IP address settings
- Press the buttons “Ack” and “Ent” at
same time to open the edit modus.
- Use Button “Enter” to mark the
selected IP mask.
- Use “Arrow” keys to change the IP
address.
Display dimming
Step 1
- Select Menu “Restart VDR”
Step 2
- Simultaneously pressing both arrow
keys
Cancel restart
- Use button “ACK” to cancel restart
If the Audio2net module is not accessible or is used as stand alone device it is also possible to access
the configuration web page via IP address of the Audio2net module directly.
If the system does not identify the Audio2net module a microphone test will be repeated 6 times and
will be completed with an error.
• Initial operation
• Reset to defaults (deletes the actual configuration)
• Enhance with additional Audio2net modules
For a correct commissioning via IP address of the MDP 2020 module follow the steps below:
Result Description
No microphone configured and no microphone
connected.
The audiodata of 2 microphones are merged into one channel. Each Audio2net has 2 channels.
For a correct commissioning via IP address of the MDP 2020 module follow the steps below:
The configuration between MDP 2020 and Tron 40VDR is necessary in following situations:
• Commissioning
• Replacement of the capsule
• Replacement of the MDP 2020
• Reset to defaults of the MDP 2020
For a correct commissioning carry out the steps in the following table:
Figure 5-8: MDP 2020 hosts configuration for the Tron 40VDR capsule [TRIMMED]
The configuration between MDP 2020 and NEMO 2.0 is necessary in following situations:
• Commissioning
• Replacement of the capsule
• Replacement of the MDP 2020 module
• Reset to defaults of the MDP 2020 module
Figure 5-9: MDP 2020 hosts configuration for the FRM NEMO 2.0 [TRIMMED]
To work properly and send images with a good quality the FGR4 has to be configured.
Figure 5-11: Initiating the connection with CVA VDRGRAB-NET Control [FULL]
If available, upload an existing configuration file to FGR4 module. This is a comfortable way to set a
replaced device to current configuration or to configure a new FGR4 module to a known video source.
For load of the configuration data from local file to FGR4 follow the steps below:
Figure 5-13: Menu bar -> File -> Load Configuration from File [TRIMMED]
It is possible to safe the current configuration to local file for archiving or as an important intermediate
step.
Recommend settings:
Figure 5-15: Menu bar -> File -> Save Configuration as File [TRIMMED]
Normally the FGR4 has the IP address 192.168.95.180. This IP address is a factory default and the
standard IP address of first FGR4 with ID=1 in a default VDR G4[e] installation.
It is also possible to change the IP address via internal web page of FGR4, see chapter 7.8.3
"Changing the IP address via internal web-frontend of FGR4" on page 230.
For grabbing a test image with current settings follow the steps below:
Figure 5-18: “Snap Image” with default offset values: H.: 178 V.: 40 [TRIMMED]
Figure 5-19: “Snap Image” with default offset values: H.: 148 V.: 40 [TRIMMED]
Figure 5-20: “Snap Image” with default offset values: H.: 178 V.: 20 [TRIMMED]
Advanced
The advanced mode is for internal use of INTERSCHALT maritime systems GmbH service and quali-
fied service partner personnel only.
2 Open the web-frontend of the FGR5. The factory default IP address is:
LAN0: 192.168.200.2
LAN1: 192.168.95.180
3 Enter menu item “Network” If you don’t want to change the network
“Settings”. settings, continue with step 7.
4 Enter the desired IP address and
subnet mask.
5 Press the button “Save data” and then
the button “Restart network”.
6 If you have changed the IP address,
than you have to open the web-fron-
tend with the new IP address again.
7 Enter menu item “Image” “Aspect If you don’t want to change the image
ratio”. aspect ratio, continue with step 10.
8 Make the appropriate settings.
9 Press the button “Store Settings” and
then the button “Restart FGR5”.
10 Enter menu item “Image” “Transfer If you don’t want to change the image
Settings”. transfer settings, continue with step
13.
11 Make the appropriate settings.
12 Press the button “Store Settings” and
then the button “Reload Configura-
tion”.
13 Enter the IP address of the FGR5 into
the hosttable of the MDP.
14 Enter the Device-ID of the signal-
source(s) into the “Video Capture”-
settings of the MDP.
The commissioning without web-frontend is not described in this manual. If you want to perform this,
than please read the installation manual of the FGR5.
Each interface (network or serial) for transmitting and receiving NMEA telegrams can be configured.
Settings for NMEA, transmit filter and receive filter can be made here. The settings can be found at:
Receive filter
Checkbox Activates/deactivates the receive filter.
Function Select between blacklist/whitelist for the filter.
Active Activate/deactivate the entry in the list.
Id (only network) Each sentence has a unique client id.
Header Header of the NMEA sentence.
Min. reciption interval (ms) Minimum time interval between 2 NMEA
sentences.
Result This sentence will be received or ignored.
Button “Remove” Removes the corresponding NMEA sentence from
the list.
Button “Add” Adds a new NMEA sentence to the list.
Transmit filter
Checkbox Activate/deactivate the transmit filter.
Active Activate/deactivate the entry in the list.
Id (only network) Each sentence has a unique client id.
Header Header of the NMEA sentence.
Max. transmission interval Maximum time interval between 2 NMEA
(ms) sentences.
Result This sentence will be sent or ignored.
Button “Remove” Removes the corresponding NMEA sentence from
the list.
Button “Add” Adds a new NMEA sentence to the list.
Any NMEA input source of MDP 2020 module whatever directly (serial) or indirectly (network)
connected has its own NMEA interface ID. Thus, even in retrospect, each NMEA telegram can be
assigned to the source. For this reason the NMEA interface list is created from VDR G4[e] automatically
and can be edited if required. Once, a manually deleted interface starts to send again, the list item will
also be recreated.
The NMEA description list is created from VDR G4[e] automatically and shows all types of telegrams,
received by VDR G4[e]. The list can be edited with short and long descriptions.
5.10.4 NMEA2net
PLC devices like WAGO PLC digitalise analogue and digital inputs. VDR G4[e] polls this PLC devices
and generate PAVBADC (analogue) and PAVBIOP (digital) NMEA telegrams.
There are maximum 5 devices. The first device can not be deactivated or configured because it is part
of the MDP 2020 module and is used for internal control functions. Usually one PLC device with device
number 2 is installed.
For a correct commissioning carry out the steps in the following table:
I/O Device No. of PLC Name of PLC Default IP of PLC Default Port of IP
Device 1 Internal device of the VDR
Device 2 first PLC1 192.168.95.190 7096
Device 3 second PLC2 192.168.95.191 7096
Device 4 third PLC3 192.168.95.192 7096
Device 5 fourth PLC4 192.168.95.193 7096
Proprietary PAVBADC NMEA telegrams are generated by VDR G4[e] via polling connected PLC
devices with analogue input modules.
Edit mode
Proprietary PAVBIOP NMEA telegrams are generated by VDR G4[e] via polling connected PLC devices
with digital input modules.
Edit mode
6 Operating procedures
The purpose of the Voyage Data Recorder is to maintain a secure and retrievable storage of information
concerning the position, movement, physical status, command and control of a vessel for a period
covering at least the most recent 720 hours of operation.
The recording takes place continuously according to the principle of a circle memory. It means all data
older then a defined period of time (depending on the different storage media) will be overwritten.
The VDR G4[e] meets all requirements of the International Maritime Organisation (IMO) resolution
A.861(20.) and the International Electrotechnical Commission (IEC) 61996-1:2013. In these documents
the amount of data to be recorded are specified detailed.
Start the VDR G4[e] by using the ON/OFF key switch. After the VDR G4[e] is started up a microphone
test will be carried out.
With the ON/OFF key switch you can start and power down the VDR G4[e]:
Only in case of maintenance shutdown the VDR G4[e] manually by using the same key switch (see
previous figure) as used during the starting up procedure.
The VDR G4[e] needs a shutdown time between 60 seconds and 150 seconds
In normal operation no activities by the operator are required and the VDR G4[e] runs autonomously
and continuously and no VDR G4[e] errors occur respectively no alarms will be indicated by the
assigned RCTP. Any fault preventing normal operating will be displayed.
This check can be carried out with the Remote Control Test Panel (RCTP) by using the function Perfor-
mance Test, see chapter 6.4.1 "Performance Test" on page 179. An alternative possibility is the
Replay and Realtime monitor, if installed.
An annual check of the VDR G4[e] is required by the flag state authorities and the class societies.
Figure 6-3: Main menu Remote Control Test Panel “day mode” [FULL]
Step 1
- Select with the arrow keys the sub-
menu.
Step 2
- Press the button “Menu/Enter”.
Step 3
- Change neccessary settings.
Figure 6-4: Main menu Remote Control Test Panel “night mode” [FULL]
Step 1
- Select Menu “Restart VDR”
Step 2
- Simultaneously pressing the arrow
keys
Cancel restart
- Use button ”ACK” to cancel restart
Restart RCTP
Step 1
- Select Menu “Restart Panel”
Step 2
- Simultaneously pressing the arrow
keys
Cancel restart
- Use button ”ACK” to cancel restart
Dimming mode
Overview Testgroups
Info page
Storage device
Audio devices
Audio devices
Radar device
Radar device
Figure 6-16: Performance test step 2 radar device 1 for details [FULL]
NMEA sentences
Each page displays the current status of 10 NMEA sentences. With the display scroll buttons may be
viewed further pages for all recorded NMEA sentences. Inhalt ist zu korrigieren
History page
Actual Alarms
Refer to additional VDR G4[e] Replay & Realtime Monitoring System Users Guide.
Start the VDR Data Transfer about -> “VDR Data Replay IS-ID” -> Archive -> New -> Connect.
After starting the program, there are several options for downloading the data:
Download the data from the “Jotron FRM” (Float Free Capsule)
The replay period for each type of data may be defined using the sliding bar. The top bar identifies the
start point of the replay period; the bottom bar the end point. The actual times selected are shown on
the right side of the sliding scale.
It is desirable, that the reports for the performance test are downloaded it must be set the hook for “PI-
Test Reports”.
For a land-based download it is required to set a TCP/IP data connection between the shore office and
the vessel and the VDR G4[e] shall be integrated in the ship’s network, then the currently recorded data
may be retrieved directly by the office using the VDR Data Transfer tool.
Because of the potentially very large volume of data to be transferred, the user should be careful with
the selection of the data to be transferred. Especially the transfer of radar images and audio should be
avoided wherever possible.
If a removable storage medium from the vessel e.g. with emergency backup data is available in the
shore office, this volume can be inserted in the replay computer and then used as data source for a
download.
This part describes retrieving of data from the FRM or a long-term recording medium.
Following a total loss of the ship, the diving capsule remains attached to the ship and should be
salvaged by specialists. The salvage should take place within 30 days after the sinking. Over longer
periods the underwater sustainability of the capsule is not guaranteed. After salvage the diving capsule
must be sent to the authorities in order to recover the data stored on the FRM.
If the storage device has been damaged in any way, return the device to the FRM manufacturer for
recovery of the data.
The storage of a backup can be made about ordered USB flash drive from INTERSCHALT maritime
systems GmbH.
In case of incidents like nearly accidents not followed by a shutdown of the VDR G4[e], the data can be
stored by the emergency backup. With this function the recorded data is copied to a USB flash drive for
analysis at a later time. The storage capacity of the USB flash drive determines the size of the data set
in hours and the number of backups
The emergency backup runs in the background and has no influence to other operations of the VDR
G4[e] which continues to record as usual. The emergency backup can be started at any time. This
backup should then be archived (using the replay system) as soon as possible and before a new emer-
gency backup is started. This ensures the VDR G4[e] from data loss. In case that the emergency lasts
longer, or a new emergency arises, save the emergency backup data before making another backup.
After activating an emergency backup the VDR G4[e] blocks a new emergency backup e. g. for a delay
of 12 hours. During this blocked time a new emergency backup will be buffered and activated after the
delay of 12 hours. If the recording time is higher as 12 hours, so the block time also. Default setting is
one emergency backup. For special system requirements this setting can be modified during commis-
sioning or service.
Select the Backup option in the menu of the Remote Control Test Panel (RCTP).
The VDR G4[e] stores the mandatory data on the USB flash drive. The storage volume can be used for
the authority as evidence data source.
If it is necessary to download the VDR G4[e] data, this USB flash drive has to be dismounted and
removed from MDP 2020 module. Then it can be at least copied to a PC with USB Port.
The emergency backup data can be retrieved from the USB flash drive directly. Using the USB flash
drive, download of emergency backup works more quickly as retrieving the data with a replay computer.
After retrieving the emergency backup from USB flash drive, put the stick on the VDR G4[e] again.
To get the data from USB flash drive follow the steps below:
To convert the data to replay format you have to install and use the Interschalt Replay System.
To transfer or convert the VDR G4[e] data to a PC please follow the steps below:
5 Select the option File -> The application “VDR Data Transfer”
New.... starts.
6 Select the option File -> A directory/ file select menu is shown.
Import.
7 Select the path to the USB flash drive and Subdirectory ../data contains the
the path with the wanted data set. actual data set.
Subdirectory ../embackup### contains
one of the emergency backup.
8 Choose the download range using the
sliders and press the button “Transfer”.
9 Download completed and archive local To protect a data set from being over-
data set. written, it can be archived.
An automatic restart will be activated by the integrated hardware watchdog within 13 seconds of an
uncontrolled function caused by a malfunction.
If the VDR G4[e] automatically shuts down after 2 hours of operation following a power failure an auto-
matic restart will be carried out once power is resupplied.
In addition, the VDR G4[e]] carries out a weekly automatic restart every Sunday at 00:30 UTC. This
restart is in order to ensure a stable normal operating condition and to help prevent undefined system
conditions occurring during months of autonomous operation.
General
The VDR G4[e] includes a general data file “R<IMO-No.>.xml”, containing compulsory data according
to IEC 61996-1:2013. This file is stored on all available storage mediums, including the FRM. Whenever
data is downloaded, this file is included and is then available in the local archive.
The VDR G4[e] maintains a log file named "Merlog". This file records all information concerning to the
system start, as well as all events, warnings and error messages occurring during operation. For further
information see Figure 7-1: "Merlog file [TRIMMED]" on page 200.
Once the file has reached a size of 500kB it will be saved as “Merlog.bak” and a new file will be started.
The Merlog file is copied every hour onto all installed and removable data storage devices and onto the
FRM. When downloading data, the Merlog file may optionally be included in the download and is then
available in the local archive.
A screen shot of each of the 2 radars and the ECDIS is grabbed every 15 seconds and stored for a
period of at least 30 days in the local storage. The screen shot is stored as a colour image in the original
resolution (up to a maximum of 1600x 1200 pixels at 60 Hz with a FGR4 module).
The sources may have different resolutions and properties, however they should also supply VESA-
compatible signals.
Only ethernet images can be transmit and recorded with higher resolution.
All bridge microphones and VHF radio communication channels will be recorded by the VDR G4[e] in
accordance with IEC 61996-1:2013. Microphones are placed in the ceiling at navigation main console
and other working areas in order to record the communication on the bridge. Each Audio2net module
has 4 ports and 2 channels. How many modules remain active during a blackout, is dependent on the
capacity of the battery.
One VHF radio communication channel is also stored digitally. All audio data is stored in the harddisc
for at least 720 hours in accordance with IEC 61996-1:2013.
There is also a possibility to record an additional radio channel.
VDR G4[e] has to record data required by IEC 61996-1:2013. However, it is also possible to record addi-
tional data. In principle any data telegram may be recorded including those of manufacturer-specific or
proprietary formats. Data may be received as analogue or digital values. These are converted into data
telegrams and forwarded to the VDR G4[e]. Other interfaces not complying to the International Standard
IEC 61996-1:2013 can also be integrated in a similar manner. All optional data telegrams received by
the VDR G4[e] are as well stored in the FRM for at least 48 hours.
This service does not mean the service at the VDR G4[e] itself but the service at devices connected to
the VDR G4[e] like GPS, Radar, Engine and so on.
Sometimes after service inspection it can happen, that the VDR G4[e] does not save all necessary data
transmitted from one of the systems on board a vessel. Service inspections are the reason therefore.
For this case INTERSCHALT maritime systems GmbH together with the Maritime Casualty Investiga-
tion Authorities recommend to check, if all necessary data from the connected systems are recorded
by the VDR G4[e] correctly.
Check the data before completing the service inspection, to claim the missing data if necessary. In case
it is not possible to do this, check the data as soon as possible after finishing service inspection.
Use the Operational Performance Test (OPT) to check the data, see chapter 6.4.1 "Performance
Test" on page 179.
A further very good possibility to check the incoming VDR data is the Replay System. The Replay
System is part of the standard scope of delivery of the VDR G4[e] and is stored on the Authority CD
allocated at the VDR G4[e] for the Maritime Casualty Investigation Authorities. The installation file for
the replay system can be find on the welcome page of the VDR G4[e].
Following requirements are necessary for installation and operation of the Replay System:
• A computer with an operating system like Windows XP, Windows 7 or Windows 10 offering multi-
media and voice output.
• Permanent or temporary connection of this computer to the VDR G4[e] network or to the USB port
for use of the orange coloured USB stick of the VDR G4[e].
Install the Replay System on your computer. Find the appropriate manual on Authority CD. The stored
data can be downloaded via VDR G4[e] network from the VDR G4[e] directly (see 6.5 "Retrieving the
data with a Replay Computer" on page 185). Alternatively use the orange coloured USB stick to down-
load the current data (see 6.5 "Retrieving the data with a Replay Computer" on page 185). In case
of interrupts during the download onto the orange coloured USB stick you find the actual data in subdi-
rectory .../data.
Connect the USB stick back to the VDR G4[e] when the
download is done or the stick is not need anymore.
After service inspection of a system which transmits data to the VDR G4[e] following 3 types of data
have to be verified carefully:
• Video data, coming from radar and ECDIS equipment. Check these data visually by displaying these
in the Replay System. Observe the following items:
• Images are provided by all radar devices?
• Colour attribution is correct?
• No colour is missing?
• The image quality is good. Do you have to adjust the quality because of transmitter changes
(output changes of images)?
• The image is shown completely?
• There are no black bars on one or more sites?
• The image is sharp and not blurred?
• Voice data, supplied by radio transceivers and microphones. Check this data by audio test. Observe
the following items:
• Voice data are available from all connected radio transceivers.
• Communication is good. Microphones are not serviced by external service personnel.
• It is recommended to perform an audio test from time to time.
Status data of all systems, recorded and stored as NMEA data. Only standardised NMEA data are
decoded and displayed in the Replay System. It is easy to detect if data are transmitted and are plau-
sible. Some data which are recorded are not displayed. Activate the NMEA monitor (Show Other
button) in the Replay System and use it, to check the recorded data. These data are listed in a box. The
plausibility check is difficult in this case.
The data recorded by the VDR G4[e] are listed in the configuration file of the VDR G4[e]. Download this
configuration file from the VDR G4[e] generally after installing the Replay System. Use the web-frontend
of the VDR G4[e] or utility VDR Transfer when establishing a first connection.
It is also possible to purchase a convenient version of the Replay System optionally. In this case not
only standardised NMEA data will be decoded and displayed comfortable. Furthermore the ship and
other objects like ARPA targets and AIS targets can be displayed in an electronic sea chart (ECS)
comfortable.
Device damage
Do not power off the module or do not interrupt power
supply while update is in process.
Step 1
Browse for new firmware image
file (*.tar.gz) and click on the
button “Upload firmware”.
Result
Upload of file begins.
Step 2
Wait until firmware is uploaded.
Result
Firmware is uploaded and the
upload itself is verified.
Step 3
Click on the button “Next” to check
the firmware file.
Result
Result of the firmware file check is
displayed.
Step 4
Click on the button “Yes (restart)”.
Result
MDP module will restart and
running the update process.
Step 5
Wait until the MDP 2020 module
is ready (look at the power leds
(extern devices) of MDP 2020
module).
Result
Firmware updated has finished.
Step 1
Browse for xml file (R<imo>.xml)
and click on the button “Upload
configuration”.
Result
Upload of file begins.
Step 2
Wait until the configuration file is
uploaded.
Result
Firmware is uploaded and the
upload itself is verified.
Step 3
Click on the button “Next” to check
the configuration file.
Result
Result of file check is displayed.
Step 4
Click on the button “Yes (restart)”.
Result
MDP module will restart and
replace the current configuration
file with the uploaded configura-
tion file.
Step 5
Wait until the MDP 2020 module
is ready (look at the power leds
(extern devices) of MDP 2020
module).
Result
Configuration updated has
finished.
$%&'
(&
!
,,-./0
&!1
"#
"#
)#*
$
"#
The following IP addresses are available, if the Jumper “Reset to Defaults” is set:
Step 8
Push the button “Next”.
Step 9
Check system values and push the
button “Next”.
Step 10
Select respective images and install.
Step 11
Example “Progress” in working.
Step 12
Progress ready; wait until button “Leave”
is active and click button “Leave”.
Device damage
Do not power off the module or do not interrupt power
supply while update is in process.
Step 1
Click on the blue arrow.
Step 2
Browse for new firmware image
file (*.tar.gz) and click on the
button “Upload firmware”.
Result
Upload of file begins.
Step 3
Wait until firmware is uploaded.
Result
Firmware is uploaded and the
upload itself is verified.
Step 4
Click on the button “Next” to
check the firmware file.
Result
Result of firmware file check is
displayed.
Step 5
Click on the button “Yes”.
Step 6
Open the Service - Option.
Step 7
Press the button “Restart VDR”.
Result
Firmware updated has finished.
Jumper Description
J1 Pin 1/2 power off during restart
Pin 2/3 continous power for X4
J6 for P1 Pin 1/2 and Pin 3/4 closed
J8 for P2 Result POL
J13 for P3
J15 for P4 Pins open
J7 for P5 result no POL
J12 for P6 for power than use Terminal X1, etc.
J14 for P7
J16 for P8
J10 See chapter 4.3.1 "External connec-
tions" on page 96.
J22 See chapter 4.3.1 "External connec-
tions" on page 96.
Device damage
Do not power off the module or do not interrupt power
supply or disconnect LAN connection while update is in
process.
Step 1
Press the buttons “ACK.” and “ENTER”
at the same time to start the update
process.
Result
The RCTP will search for new firmware
on the MDP2020.
Step 2
Use the “Arrow” buttons to select the
command field “Update”. Now press
the button “ENTER”.
Step 3
The new firmware will be downloaded
and installed.
Step 4
Restart the RCTP.
Result
Firmware update has finished.
The update procedure take between 3 and 5 minutes depending on the version of the firmware.
Device damage
Do not power off the module or do not interrupt power
supply while update is in process.
Step 1
Click on the blue arrow.
Result
Firmware update page appears.
Step 2
Browse for new firmware image
file (*.tar.gz) and click on the
button “Send”.
Result
Upload of file begins.
Step 3
Wait until firmware is uploaded.
Result
Processing upload and validating
Firmware file upload.
Step 4
Click the button “Continue” to end
with upload process.
Result
Module is restarting and performs
update.
Step 5
Wait until the module is recon-
nected.
Step 6
Wait until the module is recon-
nected.
Step 7
After 5 minutes (maximum) of
restarting the module the configu-
ration page appears.
Result
Firmware update is done.
If the reconnect needs longer than 180 seconds or update process fails, following page will appear:
Software Damage
While reconnecting (restarting) do not power off the
module and do not interrupt power supply.
For setting the NMEA2net module to default value follow the steps below:
At the moment, no update is intended for the Tron 40VDR capsule. Should it be necessary, then the
update will be performed via the web-frontend “Webmin” of the capsule.
Step 1
Select Networking “Network
Configuration” tab “Network
Interfaces”.
Step 2
“Eth0” shows the IPv4 address for
the capsule.
Step 3
Click on “eth0” and the page “Edit
Bootup Interface” opens.
Step 4
Step 5
Select “Routing and Gateways”.
Check the following settings
Tab “Boot time configuration”
Default router activate Gateway
IP to “192.168.95.205”
And “eth0” in the pulldown menu
Button “Save”
Arrow key “return to network
configuration”
Figure 7-45: Configuration Routing and Gateway Tron 40VDR
Step 6
Select Hostname and DNS Client.
Check the following settings
Hostname “VDR”
Resolution “Hosts file”
Order “Multicast DNS (minimal)”
Button “Save”
Arrow key “return to network
configuration”
7.6.3 Troubleshooting
Help with other problems you gather from the manual Tron 40VDR FF Capsule. Special info and docu-
mentation of Webmin see http://www.webmin.com.
Interval Action
Monthly The Tron 40VDR Float Free Capsule shall be checked
using the self-test function on the product. Self-test guid-
ance is explained in the product manual.
Yearly The Tron 40VDR Float Free Capsule comes under IMO
regulation MSC.1/Circ 1040 Rev.1 and as such the
annual inspection should be performed by an authorised
radio-surveyor or individuals trained and authorised by
Jotron AS to carry out this work. Jotron also recom-
mends a special inspection of the docking-station/
module. A clean surface of the docking-station and the
memory-module fitted on the Tron 40VDR Float Free
Capsule will secure reliable and safe data transfer.
Every two years The HRU (Hydrostatic release unit) must be changed.
The expiry date is marked on the HRU.
Five year service The Tron 40VDR Float Free Capsule also comes under
IMO regulation MSC 1039 and as such the Tron 40VDR
Float Free Capsule must be serviced in accordance with
this regulation or be replaced by an exchange unit. Only
individuals and or companies authorised, trained and
certified by Jotron AS are allowed to carry out the SBM-
service of the Tron 40VDR Float Free Capsule.
10 year maintenance Jotron recommends that the recording-module is
changed every 10 years. The FB-40 bracket should also
be changed every 10 years due to potential cracking in
the mounting-hole areas or the fragile top-cover.
At the moment there is no update for the NEMO 2.0 capsule is provided.
If an update for the FRM shall be required, then the steps for the procedure in the manual are incorpo-
rated into a new revision of the Technical Manual.
Reboot
Format Flash Drive
Check Flash Drive
Following kits for Replacement of NEMO 2.0 flash drive are available:
• APT-Set SSD-Flash Kit for NEMO 2 32 GB
Article number: 107779
• APT-Set SSD-Flash Kit for NEMO 2 64 GB
Article number: 107780
Quantity Item
1 SSD-Flash 32 GB
1 Foam rubber string D6
1 O-ring
8 Sealing gasket
8 Screw M4x16
1 drying agent set
Quantity Item
1 SSD-Flash 64 GB
1 Foam rubber string D6
1 O-ring
8 Sealing gasket
8 Screw M4x16
1 drying agent set
For replacing the flash drive of NEMO 2.0 module follow the steps below:
7.8.1 General
The “4-way” dip switch can be used to configure the RS232 connector (RxD and TxD signals).
Switches 1 and 4 should never be ‘on’ at the same time, and neither should 2 and 3. For “normal” use
of the RS232 with a PC, 2 and 4 should be switched on.
The figure below shows the position of the dip switches inside the unit in relation to the RS232 port and
a larger image of the switch is shown for clarity. To change the position of this bank of dip switches, the
cover needs to be removed first.
If the FGR4 is not accessible by CVA-Grabnet tool it is also possible to access the configuration web
page via IP address of the FGR4 directly.
Device damage
Do not power off the module or do not interrupt power
supply while update is in process.
• Step 1: Connect the network cable of the PC to a free network connection of the FGR5 or to the
internal FGR5 network.
• Step 2: Enter the IP address into the address bar of the browser. The web-frontend of the FGR5
will open.
Step 3
Press Menu-Item “Administration”
“Update”.
A login is required.
Step 4
Press the button “Browse...” and select
the new file for update. Then press the
button “Update”.
Result:
Upload of the file begins. For the next 2
minutes the system will show no reac-
tion.
Step 5
Upload finished.
Step 6
Press Menu-Item “Administration”
“Reboot”.
Result:
System Update has completed.
Device damage
Do not power off the module or do not interrupt power
supply while update is in process.
• Step 1: Connect the network cable of the PC to a free connection of the FGR5 or to the internal
FGR5 network.
• Step 2: Enter the IP address into the address bar of the browser. The web-frontend of the FGR5
will open.
Step 3
Press Menu-Item “Administration”
“Update”.
A login is required.
Step 4
Press the button “Browse...” and select
the new file for update. Then press the
button “Update”.
Result:
Upload of file begins.n For the next 2
minutes the system will show no reac-
tion.
Step 5
Upload finished.
Step 6
Press Menu-Item “Administration”
“Reboot”.
Result:
System Update has completed.
If you want to perform an auto adjust of the VGA parameters, you have to perform following steps:
• Step 1: Connect the network cable of the PC to a free network connection of the FGR5 or to the
internal FGR5 network.
• Step 2: Enter the IP address into the address bar of the browser. The web-frontend of the FGR5
will open.
Step 3
Press Menu-Item “Image”
“Processing settings”.
A login is required.
Step 4
Press the button “VGA auto adjust”.
• Step 5: The message “Auto adjust is started. Please wait about 60 sec.” is shown at the end of the
page.
• Step 6: After 60 seconds the main menu will be shown. The auto adjust is completed.
Corresponds the result of the “VGA Auto adjust” function not what you expected, you can also manually
enter the values.
If you want to perform an auto adjust of the VGA parameters, you have to perform following steps:
• Step 1: Connect the network cable of the PC to a free network connection of the FGR5 or to the
internal FGR5 network.
• Step 2: Enter the IP address into the address bar of the browser. The web-frontend of the FGR5
will open.
Step 3
Press Menu-Item “Image”
“Processing settings”.
a login is required.
Step 4
Enter the desired values in the fields
“Hor. adjust pxl” and “Pxl phase adjust”.
• Step 5: Press the button “Store settings” at the end of the page.
• Step 6: Press the button “Reload configuration” at the end of the page.
• Step 7: Analyse the grabbed image. Corresponds the result of the grabbed image what you
expected, then the adjust is finished. Otherwise goto step 4 and modifiy the parameter.
7.9.6 Logfiles
If you want to look into the logfiles, you have to perform following steps:
• Step 1: Connect the network cable of the PC to a free network connection of the FGR5 or to the
internal FGR5 network
• Step 2: Enter the IP address into the address bar of the browser. The web-frontend of the FGR5
will open.
Step 3
Enter menu item “Information” “Show
logfile”.
A login is required.
Step 4
Press the appropriate button to show the
corresponding logfile.
If you want to access to the FGR5 over FTP, you have to perform following steps:
• Step 1: Connect the network cable of the PC to a free network connection of the FGR5 or to the
internal FGR5 network
• Step 2: Open a FTP connection to the FGR5.
Step 3
Goto path /mnt/emmc/p3.
In case an error cannot be located, please call the service department of INTERSCHALT maritime
systems GmbH:
After reaching the end of the product useability, the product must be dismantled and an environmentally
responsible disposed.
8.2 Disposal
The unit respectively, the decomposed components shall be given to recycling. In disposal
and recycling please note the locally applicable regulations and rules.
Bring the product directly to a specialized recycling company and do not use the municipal collecting
points. These may be used only for private used products according to the WEEE directive.
If you have no way to dispose the waste electronic equipment properly, please contact us concerning
return and disposal.
9 Appendix
9.1 USB-Datastick 64 GB
ClampDuration: 0x3C
ClockGeneratorControls: 0xD4
PLLDivideRatioMSB: 0x87
PLLDivideRatioLSB: 0x00
Width: 68616439 [0x041700F7]
Height: 81788976 [0x04E00030]
DVIorAnalogControl: 0x00000000
0x20: 041700F7
0x24: 04E00030
0x28: 00000000
x_len: 1600, y_len: 1200
send picture
send picture
send picture
send data to slow 30.534351 packets per second.
end failed
close socket.
restart network
down eth0
Process returned 0
up eth0
bf537_mac: hardware init finished
Process returned 0
send picture
Type-No.: Artikel-No.:
3 1+ 2- ON FO1
AB E
23 6
CD
45
789
1 2
- +
Shld
Abmessungen (HxBxT) / Dimensions (HxWxD) 125x125x60mm Spannungsversorgung / Supply Voltage 24VDC (+30% / -30%)
Seitenelemente / Sideparts UM 108-SEFE/R (/L) ; Polyamid PA-F Leistungsaufnahme / Power Consumption 8W (with 4 microph. and Beep ON)
Strangprofil / Lengthprofile UM 108-PROFIL 100CM ; PVC Compass Sicherheitsabstand / Compass safe distance 0,30 m
Certificate No:
TAA000006N
TYPE APPROVAL CERTIFICATE
This is to certify:
That the Peripheral Equipment
Issued to
Moxa Inc.
New Taipei City, Taiwan
Application :
Product(s) approved by this certificate is/are accepted for installation on all vessels classed
by DNV GL.
Location classes:
Temperature D
Humidity B
Vibration A
EMC B
Enclosure Required protection according to the Rules
to be provided upon installation on board
This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
Product description
The units are classed and approved for 12V to 48V DC supply voltage.
The approved units are listed below:
Video server
VPort 351 series
Vport 351
Vport 351-M-SC
Vport 351-S-SC
Vport 351-T
Vport 351M-SC-T
Vport 351S-SC-T
Optional Accessory
SFP-1FE series
SFP-1FEMLC-T
SFP-1FESLC-T
SFP-1FELLC-T
Place of manufacture
Fl.4, No. 135. Lane 235, Baoqiao Rd.,
Xindian Dist., New Taipei City, Taiwan
Application/Limitation
The Type Approval covers hardware listed under Product description. When the hardware is used in
applications to be classed by DNV GL, documentation for the actual application is to be submitted for
approval by the manufacturer of the application system in each case. Reference is made to DNV GL rules
for classification of ships Pt.4 Ch.9 Control and monitoring systems.
Periodical assessment
The scope of the periodical assessment is to verify that the conditions stipulated for the type are
complied with, and that no alterations are made to the product design or choice of systems, software
versions, components and/or materials.
The main elements of the assessment are:
Ensure that type approved documentation is available
Inspection of factory samples, selected at random from the production line (where practicable)
Review of production and inspection routines, including test records from product sample tests and
control routines
Ensuring that systems, software versions, components and/or materials used comply with type
approved documents and/or referenced system, software, component and material specifications
Review of possible changes in design of systems, software versions, components, materials and/or
performance, and make sure that such changes do not affect the type approval given
Ensuring traceability between manufacturer’s product type marking and the type approval certificate
Periodical assessment is to be performed at least every second year and at renewal of this certificate.
END OF CERTIFICATE
Headquarter Manufacturer
INTERSCHALT maritime systems GmbH INTERSCHALT maritime systems GmbH
Osterbrooksweg 42 Eichkamp 15
22869 Schenefeld 24217 Schönberg
Phone: +49 40 83033‐0 Phone: +49 4344 307‐0
Fax: +49 40 8302617 Fax: +49 4344 307‐291
Email: service@interschalt.de Email: Steinsohn.Service@interschalt.de