IOEX Installation guide

Input Output Expander (IOEX)


for ADVC Controller Range

Scope of this document


This document describes the installation procedures for the IOEX
with ADVC Controller.
Limitations
This document is copyright and is provided solely for the use of the
purchaser. It is not to be copied in any way, nor its contents
divulged to any third party, nor to be used as the basis of a tender
or specification without the express written permission of the
manufacturer.
Disclaimer
The advisory procedures and information contained within this
document have been compiled as a guide to the safe and effective
operation of products supplied by Schneider Electric Recloser
Solutions.
It has been prepared in conjunction with references from sub-
assembly suppliers and the collective experience of the
manufacturer.
In-service conditions for use of the products may vary between
customers and end-users. Consequently, this document is offered
as a guide only. It should be used in conjunction with the customers
own safety procedures, maintenance program, engineering
judgment and training qualifications.
No responsibility, either direct or consequential, for injury or
equipment failure can be accepted by the manufacturer resulting
from the use of this document.
Copyright
© 2010 by Schneider Electric.
All rights reserved. No part of the contents of this document may be
reproduced or transmitted in any form or by any means without the
written permission of the manufacturer.

Document part number


ADVC2-1194 – Revision 01

Schneider Electric (Australia) Pty Limited


80 Schneider Road,
Eagle Farm,
Qld 4009
AUSTRALIA
Tel: +61 7 3635 7500
Fax: +61 7 3635 7560
1 Introduction
The IOEX (Input Output Expander Module) is an ADVC Controller Range accessory that accepts external control
signals from third party devices. It provides optically isolated inputs and voltage-free outputs. These allow
connection of an external protection relay or Remote Terminal Unit (RTU). The electronic circuit is installed in a die
cast, sealed enclosure which is attached to the upper accessory mounting tray of an ADVC ULTRA controller.

IOEX enclosure

8 x Inputs – Optically Isolated Input Terminals

Output Isolated 12 Vdc power supply


terminals
- Negative Isolated power source to
+ Positive external switches.

RS232 Communications connection to ADVC


Controller Electronics

Input IOEX power supply terminals


Negative Power supply to IOEX
Positive electronics from the ADVC
Controller electronics

8 x Outputs – Voltage-free Output terminals

1.1 Compatibility
The IOEX is compatible with the ULTRA model of the ADVC Controller range where the upper accessory tray is
used to mount the IOEX module. The controller electronics includes a regulated power supply for the IOEX
module/s. Connection to the power supply is via two terminals mounted on the side accessory tray.
RS232 communications is used to interface the IOEX module/s to the control electronics.
The ULTRA model includes the following features to accommodate the IOEX module/s:
 Upper accessory tray for up to two IOEX modules
 Additional holes in the base of the controller for IOEX cable entry.
 Cable tie point on the cubicle side to secure the cables.

1.2 Parts supplied with the IOEX


The following parts are supplied with each IOEX module.
 1 x IOEX module Note:
 1 x RS232 cable Shielded cable (not supplied)
 1 x Power cable for external connections and
 4 x M5 stainless steel screws and washers. the EMC gland are essential
 1 x EMC cable gland for reliable operation.

2 Specifications
Isolated power supply output: 12 – 15 Vdc , 100 mA max.
IOEX power supply input: 18 – 36 Vdc, 200 mA max. supplied by controller electronics.
Optically isolated inputs: 8 inputs per IOEX module.
ON = 12 – 150 Vdc, 12 – 150 Vac.
OFF = 0 – 3 Vdc, 0 – 3 Vac.
Voltage-free outputs: 8 outputs per IOEX module.
150VDC at 1A Maximum or
150VAC RMS at 2A Non-inductive Maximum
Dimensions [mm]: 188 high, 119.5 wide, 37 deep.
Controller connection: RS232 – DB9 Male/Female cable (part number ADC-640).

IOEX Installation Guide (ADVC2-1194) Page 2 Schneider Electric


3 IOEX installation
The IOEX must be fitted to the upper accessory mounting tray.

3.1 Removing and installing the mounting tray


It is very easy to remove the upper accessory mounting tray:
1. Undo and remove the self locking nuts and washers;
3 2. Rotate the accessory tray to the slide-out position by lifting
Brackets
the bottom of the tray away from the cubicle; and
3. Slide the tray to your left.
Hinges
To install the upper tray, locate the accessory tray hinges to the left
of the brackets in the top corner of the cubicle. Use the corner as a
1 2 1 guide and slide the tray to your right. The self-locating hinges will
guide the tray into the brackets. Continue to slide the tray until the
Upper accessory tray removal
hinges are completely inside the brackets. Rotate the tray into the
lock-down position and fasten the nuts.

3.2 Attaching the IOEX


Method:
1. Remove the Upper Accessory Mounting Tray
from the ADVC ULTRA cubicle (see 3.1);
2. Two mounting options are provided on the tray
(Left and Right). Select a convenient option;
3. Align the IOEX to the 4 holes as indicated.
Using the screws and washers provided, Mounting
attach the IOEX to the tray. Tighten the screws option Right
to 4Nm of torque; and Mounting
4. Fit the tray containing the IOEX in the Upper option Left
Accessory Mounting Space using the existing
mounting points (see 3.1).

Mounting holes

3.3 Connect the IOEX to the controller

Connect the IOEX power supply lead to the terminals Side Accessory Tray IOEX
on the side accessory tray. The terminals are marked
with the following symbols.

Ground terminal

IOEX Positive power terminal

Using the RS233 cable (ADC-640), connect one of


the RS232 ports (A, B, C or D) on the ADVC
Controller to the IOEX.
Before you can use the IOEX, make “IOEX available”
in the WSOS Feature Selection tool, download the
configuration map and select the IOEX
communication port. Please see:
ADVC Operation Guide (ADVC2-1160) and
Configurable IOEX manual (N00-685).

IOEX Installation Guide (ADVC2-1194) Page 3 Schneider Electric


4 Electrical connections
4.1 Using the built-in isolated supply 4.2 Using an external source
The IOEX has a built-in isolated power supply that can It is also possible to use a custom AC or DC source for
be used as field excitation voltage. The following field excitation of the external switches. This supply
connection diagram describes using this DC voltage as must be isolated from earth.
a source to supply the external switches. Field excitation voltage: 12 Vac/dc up to 150 Vac/dc.

Note: Note:
Field excitation MUST NOT be The field excitation power
provided from the battery nor supply must be isolated from
the radio power supply. earth.

- -
+ +
Field excitation voltage
12 – 150 Vac/dc
IOEX IOEX
External External
1 Input 1 Input 1
1
2 Input 2 Input 2
2
3 Input 3 Input 3
3
4 Input 4 Input 4
4
5 Input 5 Input 5
5
6 Input 6 Input 6
6
7 Input 7 Input 7
7
8 Input 8 Input 8
8

4.3 Voltage-free outputs 4.4 Shielded cable


For the external connections, shielded cable with the
following main characteristics is recommended:
Field excitation voltage Operating Temperature: -55°C to +105°C
12 – 150 Vac/dc Voltage Rating: 600 V
IOEX Outputs
Product Description:
Internal  Conductor: Stranded Tinned Copper
Output 1  Area Conductor: 0.22 mm²
1 A
 External Diameter: 6 - 12 mm
2 Output 2  Screen diameter: 5 mm minimum
B
Output 3  Insulation: Colour-Coded PVC
3 C
 Shield: Braided Tinned Copper
4 Output 4 (90% Coverage)
D
Output 5  Jacket: PVC
5 E
6 Output 6
F
7 Output 7
G
8 Output 8
H
External device Picture of the shielded cable (not supplied)
inputs

IOEX Installation Guide (ADVC2-1194) Page 4 Schneider Electric


4.5 Customer Cable Installation
4.5.1 EMC gland specification
An M20 EMC cable gland with the following main
characteristics is required:
 Diameter, cable max: 12 mm  Plating: Nickel
 Diameter, cable min: 6 mm  Thread size: M20
 Diameter, cable screen min: 5 mm  Length, thread: 8 mm
 Material: Brass  IP Rating: IP68

4.5.2 EMC gland installation

Clamping ring Gland body


Sleeve
‘O’ ring

Seal Braid connection

Earth braid

Cable sheath

Method Illustrations
Note:
Correct installation of the 120 cm
EMC gland is essential
for reliable operation.

1.
At 120 cm from the cable-end that will be connected to the
IOEX, remove 2 cm of the plastic sheath to expose the
earth braid. 2 cm

Push the end of the cable that will be connected to the


IOEX through the cable gland in the direction as shown.

2.
Note:
Pushing the cable in the
opposite direction will
damage the gland.

IOEX Installation Guide (ADVC2-1194) Page 5 Schneider Electric


Method Illustrations
Continue pushing the cable through the gland, until the
2 cm
earth braid aligns with the gland.

3.

Ensure the earth braid is in contact with the braid


4.
connection ring in the gland.

Ensure the seal and clamping mechanism is overlapping


5. with the plastic sheath. Tighten the gland sleeve to firmly
grip the cable in place.

Select a 20mm hole in the base of the controller. The two


holes on the right hand side are provided for this purpose.

6. FTIM and IOEX


cable holes

Remove the plug and fit the cable with gland.


4.5.3 Cable termination
1. Use cable ties to secure the cable to the cubicle Note:
wall.
Shielded cable is
2. Cut the cable to the appropriate length, and
essential for reliable
terminate the cable at the IOEX connectors. operation. See 4.4.