Professional Documents
Culture Documents
BA-BMS-Burner For Rotary Kiln
BA-BMS-Burner For Rotary Kiln
customer: BENIN
Anlage:
plant:
MAIN BURNER
Kommissions-Nr.:
Commission-No.:
MAIN BURNER
OPERATION MANUAL
BURNER MANAGEMENT SYSTEM
CONTENT
F1 – F8 the function keys are for screen selection – see “description of function”
Other functions or selection of screens have to be done for each screen inside the screen
with touch keys.
Inside screens
Closed/off position
Open/on position
Actor is faulty
Status of group
Operation interlock
starting interlock
Operation
OI SI OP STEP
Operation and starting interlock not OK – no operation
0 possible
OI SI OP STEP
Operation interlock OK but starting interlock not OK – no start
0 possible
OI SI OP STEP
0 Operation and starting interlock OK – start possible
OI SI OP STEP
1-16 Group is in start sequence
OI SI OP STEP
16 Group is started sucessfull and in operation
OI SI OP STEP
51-66 Group is in stop sequence
OI SI OP STEP
66 Group is stopped sucessfull – ready to start
Description of functions
à Go to next screen
ß Go to previous screen
à Go to next screen
ß Go to previous screen
Basics of operation
The controller watches and controls the ignition and operation of fuels on a safe way.
In REMOTE mode the commands start and stop and the set points will give from central control room
(CCR). In LOCAL mode the commands start and stop and the set points will control from the local
HMI (human machine interface).
Additional for the regulating of fuel flow a possibility to switch between automatic control and manual
control is given.
Password - level
To change any settings or parameter a password with the right user is necessary. The default setting
of password is :
If it is necessary to write a new value in the desired parameter field user have to touch the parameter
field à a key board and the login screen is automatically open and the user can write by touching the
soft keys the user name and password and after the new value.
If the value is right press ENTER à new set point will transferred to the controller and the screen
switch back to origin screen. Is the value wrong press ESC à old value is shown in the field.
Normally if the data interchange to CCR is ok the time and data will synchronised all the time to the
time and date of CCR.
If the communication is disturbed you can set time and/or date manually via HMI.
If you have written in the actual time and date you have to press CLOCK .
ACKNOWLEGE / RESET
If a fault is present in the controller a fault memory is activated and the group goes in safe position
(closed valves).
By each new fault a signal – new fault - is activated. To reset the signal you have to press the ACK
button.
Is the reason of the fault solved you have to reset the fault memory by pressing again ACK button.
Otherwise the starting interlock of the group give not the enable signal for starting.
If the communication is disturbed (the feedback of LIVE signal does not come back in adjusted time)
automatically the controller goes in LOCAL mode – so the operator can react immediately.
If the controller is in REMOTE mode the set point from remote system is shown in the field. Any
change of set point is not possible.
Before you start any fuel or Ignitor call the relevant picture.
A stopping of any fuel or ignitor is always possible. To start a fuel or ignitor the starting interlock has to
be fulfilled.
The starting interlock is fulfilled if operation and starting interlock is green (see “Status of group”)
For start you have to press in same time START (see “Select screen with softkey”).
For stop you have to press in same time STOP (see “Select screen with softkey”).
Screen START
Screen IGNITOR
The starting interlock is fulfilled if operation and starting interlock is green (see “Status of group”)
For start you have to press in same time START (see “Select screen with softkey”).
For stop you have to press in same time STOP (see “Select screen with softkey”).
The starting interlock is fulfilled if operation and starting interlock is green (see “Status of group”)
For start you have to press in same time START (see “Select screen with softkey”).
For stop you have to press in same time STOP (see “Select screen with softkey”).
proportional factor – GAIN with proportional factor you make regulator slower or faster
increase factor à regulator is faster
decrease factor à regulator is slower
dimension: less
integral time – TI with integral time you make the regulator more or less sensitive
dimension: seconds
Screen COAL
Screen MESSAGES
Screen SYSTEM
LOGIC
The start and Stop of fuel is realised by sequences. For trouble shooting the indication of the steps
is very important.
PROFIBUS DP – COMMUNICATION
For the data interchange between GRECO controller and DCS-system (scada system) there is a
communication device installed.
To DCS system
Start address Q 100.0 (outputs)
Length 64 bytes consistent