-7.3000516/112.0467815

Work Order Number :-


MU_PM-EJN-202102-59

Evidence Work Order Number :-

Person Incharge :-
samsudin
Team Leader :-
bayu rajasa

Site ID Information :-
20BJO009

View of Site :-

View of Outdoor Equipment :-

Remote monitoring is installed :-


OK

Data connection model :-


Webbox

Remote Monitoring Brand :-


HUAWEI

Check Remote Monitoring Network Comm :-


OK

Check Remote Monitoring Sensor Comm :-


OK

Punchlist #1 :-
NO

Punchlist #2 :-
NO

PLN #1 :-
YES
PLN capacity (KVA) :-
21120

Photo of PLN capacity (KVA) :-

PLN Phase :-
3

Photo of PLN Phase :-

PLN meter reading :-


217665

Photo of PLN meter reading :-

ID Pelanggan :-
518041034467

Overall Stand Meter (KWH) Condition :-


OK
Photo of Overall Stand Meter (KWH) Condition :-

Full View KWH Meter :-


ok

Photo of Full View KWH Meter :-

MCB PLN Capacity (Ampere) :-


32

Photo of MCB PLN Capacity (Ampere) :-

Check seal in KWH Meter Body :-


OK

Photo of Check seal in KWH Meter Body :-


Check seal in Meter KWH :-
OK

Photo of Check seal in Meter KWH :-

Check seal in MCB KWH :-


OK

Photo of Check seal in MCB KWH :-

Quantity Of Seal (P2TL) :-


8

Photo of Quantity Of Seal (P2TL) :-

R - N Voltage (V) :-
208
Photo of R - N Voltage (V) :-

S - N Voltage (V) :-
224

Photo of S - N Voltage (V) :-

T - N Voltage (V) :-
202

Photo of T - N Voltage (V) :-

N - G Voltage (V) - less than 1V :-


1

Photo of N - G Voltage (V) - less than 1V :-


R - S Voltage (line to line) :-
368

Photo of R - S Voltage (line to line) :-

R - T Voltage (line to line) :-


348

Photo of R - T Voltage (line to line) :-

S - T Voltage (line to line) :-


355

Photo of S - T Voltage (line to line) :-

PLN Load phase R (Ampere) :-


7.1
Photo of PLN Load phase R (Ampere) :-

PLN Load phase S (Ampere) :-


6.1

Photo of PLN Load phase S (Ampere) :-

PLN Load phase T (Ampere) :-


5.0

Photo of PLN Load phase T (Ampere) :-

PLN Load phase N (Ampere) :-


1.1

Photo of PLN Load phase N (Ampere) :-


Illegal electricity connection ? :-
NO

Photo of Illegal electricity connection :-

Arrester :-
YES

Photo of ACPDB Outdoor Arrester :-

Photo of ACPDB Indoor Arrester :-

Photo of MDP Arrester :-


Photo of Rectifier Arrester :-

PLN #2 :-
NO

Punchlist PLN #1 :-
NO

Punchlist PLN #2 :-
NO

Punchlist PLN #3 :-
NO

Punchlist PLN #4 :-
NO

Punchlist PLN #5 :-
NO

ACPDB #1 :-
YES

ACPDB (AC Power Distrubution Box) :-


1 box ac

ACPDB View and condition :-


ACPDB Outdoor View and condition :-

ACPDB indoor View and condition :-

S - N Voltage (V) :-
213

Photo of S - N Voltage (V) :-

T - N Voltage (V) :-
216

Photo of T - N Voltage (V) :-

N - G Voltage (V) < 1V :-


1
Photo of N - G Voltage (V) < 1V :-

R - S Voltage (line to line) :-


363

Photo of R - S Voltage (line to line) :-

R - T Voltage :-
365

S - T Voltage :-
358

ACPDB Outdoor Load phase R (Ampere) :-


0

Photo of ACPDB Outdoor Load phase R (Ampere) :-

ACPDB Outdoor Load phase S (Ampere) :-


0
Photo of ACPDB Outdoor Load phase S (Ampere) :-

ACPDB Outdoor Load phase T (Ampere) :-


0

Photo of ACPDB Outdoor Load phase T (Ampere) :-

ACPDB Outdoor Load phase N (Ampere) :-


0

Photo of ACPDB Outdoor Load phase N (Ampere) :-

ACPDB Indoor Load phase R (Ampere) :-


6.3

Photo of ACPDB Indoor Load phase R (Ampere) :-


ACPDB Indoor Load phase S (Ampere) :-
6.4

Photo of ACPDB Indoor Load phase S (Ampere) :-

ACPDB Indoor Load phase T (Ampere) :-


6.3

Photo of ACPDB Indoor Load phase T (Ampere) :-

ACPDB Indoor Load phase N (Ampere) :-


0.5

Photo of ACPDB Indoor Load phase N (Ampere) :-

ACPDB Grounding condition :-


OK
Photo of ACPDB Grounding condition :-

ACPDB Indoor Grounding condition :-


OK

Photo of ACPDB Indoor Grounding condition :-

R-N Voltage (V) :-


438

Photo of R-N Voltage (V) :-

ACPDB #2 :-
NO

ACPDB #3 :-
NO

ACPDB #4 :-
NO

Punchlist ACPDB #1 :-
NO

Punchlist ACPDB #2 :-
NO
Punchlist ACPDB #3 :-
NO

MDP Available ? :-
NO

Punchlist MDP #1 :-
NO

Punchlist MDP #2 :-
NO

Punchlist MDP #3 :-
NO

Measurement of grounding system with earth tester at control Box :-


OK

Photo of Measurement of grounding system with earth tester at control Box :-

Measurement of grounding at IGB :-


OK

Photo of Measurement of grounding at IGB :-

Measurement of grounding at EGB :-


OK
Photo of Measurement of grounding at EGB :-

Measurement of grounding at tray :-


OK

Photo of Measurement of grounding at tray :-

Measurement of grounding at busbar bottom of tower :-


OK

Photo of Measurement of grounding at busbar bottom of tower :-

Measurement of grounding at fencing :-


OK

Photo of Measurement of grounding at fencing :-


Measurement of grounding at pole of KWH meter :-
OK

Photo of Measurement of grounding at pole of KWH meter :-

Measurement of grounding at KWH meter :-


OK

Photo of Measurement of grounding at KWH meter :-

Measurement of grounding at Leg tower 1 :-


OK

Photo of Measurement of grounding at Leg tower 1 :-

Measurement of grounding at Leg tower 2 :-


OK
Photo of Measurement of grounding at Leg tower 2 :-

Measurement of grounding at Leg tower 3 :-


OK

Photo of Measurement of grounding at Leg tower 3 :-

Measurement of grounding at Leg tower 4 :-


OK

Photo of Measurement of grounding at Leg tower 4 :-

Punchlist Grounding #1 :-
NO

Punchlist Grounding #2 :-
NO

Punchlist Grounding #3 :-
NO

Air Conditioning unit 1 Applicability :-


YES

Air conditioning unit location #1 :-


1
Brand :-
DAIKIN

Photo of Brand :-

Model :-
FT50BVM

Capacity (PK) :-
1.5

Capacity (Ampere) :-
12.6

Photo of Capacity (Ampere) :-

Piping condition (Any leaking sign?) :-


OK

Photo of Piping condition (Any leaking sign?) :-

Indoor unit status :-


OK
Photo of Indoor unit status :-

Outdoor unit status :-


OK

Photo of Outdoor unit status :-

Temperature setting (Celcius) :-


25

Photo of Temperature setting :-

Air temperature acceptable? :-


OK

Photo of Air temperature acceptable? :-


Current Arus (A) :-
3

Photo of Current Arus (A) :-

Last service/repair date :-


2021-02-02

Air Conditioning unit 2 Applicability :-


NO

Air Conditioning unit 3 Applicability :-


NO

Air Conditioning unit 4 Applicability :-


NO

Air Conditioning unit 5 Applicability :-


NO

Air Conditioning unit 6 Applicability :-


NO

Air Conditioning unit 7 Applicability :-


NO

Air Conditioning unit 8 Applicability :-


NO

Punchlist Air conditioning #1 :-


NO

Punchlist Air conditioning #2 :-


NO

Punchlist Air conditioning #3 :-


NO

Punchlist Air conditioning #4 :-


NO

Punchlist Air conditioning #5 :-


NO
How many fan available ? :-
1

All fans function ? :-


YES

Air filter available and clean? :-


NA

DC Fan condition :-
OK

Photo of DC Fan condition :-

Punchlist Ventilation system #1 :-


NO

Punchlist Ventilation system #2 :-


NO

Punchlist Ventilation system #3 :-


NO

Person Signature :-

You might also like