General
Function Name Parameter Parameter Value
Name Description
PRIMVAL: 1 FrequencySel 50Hz
PRIMVAL: 1 PhaseRotation Normal=L1L2L3
CT ratio
Function Parameter Parameter Parameter Value Parameter
Name Name Value Description Unit
TRM_40 NAMECH1 W1_CT1_IL1
TRM_40 ChannelType1 1 CurrentProtection
TRM_40 RatedTrans1 1 A
TRM_40 CTStarPoint1 1 ToObject
TRM_40 CTsec1 1 A
TRM_40 CTprim1 400 A
TRM_40 NAMECH2 W1_CT1_IL2
TRM_40 ChannelType2 1 CurrentProtection
TRM_40 RatedTrans2 1 A
TRM_40 CTStarPoint2 1 ToObject
TRM_40 CTsec2 1 A
TRM_40 CTprim2 400 A
TRM_40 NAMECH3 W1_CT1_IL3
TRM_40 ChannelType3 1 CurrentProtection
TRM_40 RatedTrans3 1 A
TRM_40 CTStarPoint3 1 ToObject
TRM_40 CTsec3 1 A
TRM_40 CTprim3 400 A
TRM_40 NAMECH4 W2_CT1_IL1
TRM_40 ChannelType4 1 CurrentProtection
TRM_40 RatedTrans4 1 A
NHÀ MÁY ĐIỆN MẶT TRỜI Số: 01-2020/NMDMT ĐẨM TRÀ Ổ
ĐẦM TRÀ Ổ Tờ số: 3 /5
Differential Protection
Function Parameter Name Parameter Parameter Value Parameter
Name Value Description Unit
T2WPDIF: 1 GlobalBaseSelW1 1
T2WPDIF: 1 GlobalBaseSelW2 2
T2WPDIF: 1 ConnectTypeW1 1 WYE (Y)
T2WPDIF: 1 ConnectTypeW2 1 WYE (Y)
T2WPDIF: 1 ClockNumberW2 0 0 [0 deg]
T2WPDIF: 1 ZSCurrSubtrW1 1 On
T2WPDIF: 1 ZSCurrSubtrW2 1 On
T2WPDIF: 1 TconfigForW1 0 No
T2WPDIF: 1 TconfigForW2 0 No
T2WPDIF: 1 Operation 1 On
T2WPDIF: 1 SOTFMode 1 On
T2WPDIF: 1 IDiffAlarm 0.2 IB
T2WPDIF: 1 tAlarmDelay 10 s
T2WPDIF: 1 IdMin 0.3 IB
NHÀ MÁY ĐIỆN MẶT TRỜI Số: 01-2020/NMDMT ĐẨM TRÀ Ổ
ĐẦM TRÀ Ổ Tờ số: 4 /5
REF protection
Function Name Parameter Parameter Parameter Parameter
Name Value Value Unit
Description
W1_REFPDIF; REFPDIF: 1 GlobalBaseSel 1
W1_REFPDIF; REFPDIF: 1 Operation 1 On
W1_REFPDIF; REFPDIF: 1 IdMin 20 %IB
Overcurrent Protection
Function Name Parameter Parameter Parameter Parameter
Name Value Value Unit
Description
W1_OC4PTOC; OC4PTOC: 1 GlobalBaseSel 1
W1_OC4PTOC; OC4PTOC: 1 MeasType 31 DFT
W1_OC4PTOC; OC4PTOC: 1 2ndHarmStab 15 %
W1_OC4PTOC; OC4PTOC: 1 Operation 1 On
W1_OC4PTOC; OC4PTOC: 1 StartPhSel 1 1 out of 3
W1_OC4PTOC; OC4PTOC: 1 DirMode1 1 Non-
directional
W1_OC4PTOC; OC4PTOC: 1 Characterist1 15 IEC Def.
Time
W1_OC4PTOC; OC4PTOC: 1 I1> 600 %IB
W1_OC4PTOC; OC4PTOC: 1 t1 0.10 s
W1_OC4PTOC; OC4PTOC: 1 I1Mult 1
W1_OC4PTOC; OC4PTOC: 1 HarmBlock1 On
W1_OC4PTOC; OC4PTOC: 1 DirMode2 1 Non-
directional
W1_OC4PTOC; OC4PTOC: 1 Characterist2 15 IEC Def.
Time
W1_OC4PTOC; OC4PTOC: 1 I2> 225 %IB
W1_OC4PTOC; OC4PTOC: 1 t2 3.00 s
W1_OC4PTOC; OC4PTOC: 1 I2Mult 1
NHÀ MÁY ĐIỆN MẶT TRỜI Số: 01-2020/NMDMT ĐẨM TRÀ Ổ
ĐẦM TRÀ Ổ Tờ số: 5 /5
Lưu ý
+ Đề nghị kiểm tra đúng cực tính biến dòng điện dùng cho chức năng bảo vệ so lệch và chống
chạm đất hạn chế MBA
+ Chức năng quá tải (OC4PTOC: I3> ) chỉ đi cảnh báo, không cắt máy cắt
+ Các chức năng bảo vệ khác trong rơ le đề nghị không sử dụng và khóa lại. Các tham số thời
gian, tự động, điều khiển khác, đề nghị đặt theo hướng dẫn của nhà chế tạo và phù hợp với
thực tế vận hành